Proax
CADEN
proax logo
Cart

OT160G03

ABBOfficial Distributor

By ABB

SKU
ABBOT160G03
MPN
1SCA135134R1001
Weight
0.8 kg
3-pole, front operated, base mounted switch-diconnector with protected clamp terminals, handle and shaft are not included
Technical Specifications

ABB EcoSolutions

End Of Life Disassembling Instructions1SCC301116M0201
Environmental Information1SCC301267D0201
Environmental Product Declaration - EPD1SCC301281D0201

Dimensions

Product Net Width123 mm
Product Net Height130 mm
Product Net Depth / Length73 mm
Product Net Weight0.8 kg

Technical

Cable Cross-SectionCu 10 ... 70 mm²
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 160 A
Conventional Thermal Current (Ithe)Fully Enclosed 160 A
Degree of ProtectionFront IP20
Distance Between PhasesStandard
Handle TypeHandle and shaft not included
Mechanical Durability20000
Mounting TypeBase mounting
Number of Poles3P
Operating modeFront and Side
Pollution degree3
Position of Line TerminalsTop In - Bottom Out
Position of Line TerminalsBottom In - Top Out
Power Lossat Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)(200 A fuse, 500 V) 100 kA
Rated Conditional Short-Circuit Current (Inc)(200 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 160 A
Rated Operational Current AC-21A (Ie)(500 V) 160 A
Rated Operational Current AC-21A (Ie)(690 V) 160 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 160 A
Rated Operational Current AC-22A (Ie)(500 V) 160 A
Rated Operational Current AC-22A (Ie)(690 V) 160 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 160 A
Rated Operational Current AC-23A (Ie)(500 V) 160 A
Rated Operational Current AC-23A (Ie)(690 V) 160 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 45 kW
Rated Operational Power AC-23A (Pe)(400 ... 415 V) 75 kW
Rated Operational Power AC-23A (Pe)(500 V) 90 kW
Rated Operational Power AC-23A (Pe)(690 V) 132 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 12 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 4 kA
Special FunctionsNo
StandardsIEC 60947-3 / UL 98 / CSA C22.2 NO.4
Switches Operating MechanismMechanism at the End of the Switch
Switches Operating Mechanism03 (Left Side)
Terminal TypeScrew Terminals
Tightening torqueacc. IEC 60947-1 6 N·m

Technical UL/CSA

Maximum Operating Voltage UL/CSA600 V
Ampere Rating125 A
Horsepower Rating UL/CSA(240 V AC) Single Phase 20 Hp
Horsepower Rating UL/CSA(440 ... 480 V AC) Single Phase 30 Hp
Tightening torqueacc. IEC 60947-1 6 N·m
Tightening Torque UL/CSA53 in·lb

Why Proax for ABB OT160G03?

Proax is an authorized distributor of ABB OT160G03 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability