160, 3 pole fast transition manual change-over switch. Operating angle 90° to achieve fast switching. Minimum OFF-time between transfer from I-II or II-I is 20 ms. Including a black plastic IP65 I-0-II pistol type handle (see the table below), shaft and bolt set for the cable connection. Handle not padlockable and no door interlocking.
Technical Specifications

Dimensions

Product Net Width170 mm
Product Net Width6.69 in
Product Net Height150 mm
Product Net Height5.91 in
Product Net Depth / Length160 mm
Product Net Depth / Length6.3 in
Product Net Weight3.245 kg
Product Net Weight7.15 lb

Technical

Rated Operational Current AC-21A (Ie)(380 ... 415 V) 160 A
Rated Operational Current AC-21A (Ie)(500 V) 160 A
Rated Operational Current AC-21A (Ie)(690 V) 160 A
Rated Operational Current AC-21A (Ie)(500 V) 160 A
Rated Operational Current AC-21A (Ie)(690 V) 160 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 160 A
Rated Operational Current AC-22A (Ie)(500 V) 160 A
Rated Operational Current AC-22A (Ie)(690 V) 160 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 160 A
Rated Operational Current AC-23A (Ie)(500 V) 160 A
Rated Operational Current AC-23A (Ie)(690 V) 160 A
Rated Operational Current AC-31B (Ie)(380 ... 415 V) 160 A
Rated Operational Current AC-33B (Ie)(380 ... 415 V) 160 A
Rated Operational Power AC-23A (Pe)(380 ... 415 V) 90 kW
Rated Operational Power AC-23A (Pe)(500 V) 110 kW
Rated Operational Power AC-23A (Pe)(690 V) 160 kW
Conventional Free-air Thermal Current (Ith)Θ = 40 °C 160 A
Conventional Thermal Current (Ithe)Fully Enclosed 160 A
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)1000 V
Rated Operational Voltage1000 V
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 8 kiloampere rms
Power Loss2.4 W
Pollution degree3
Handle colorBlack
Handle TypeHandle and shaft included
Switches Operating MechanismMechanism at the End of the Switch
Switches Operating Mechanism03 (Left Side)
Distance Between PhasesStandard
Position of Line TerminalsTop In - Bottom Out, Bottom In - Top Out
Operating modeFront operated
Mounting TypeBase mounting
Number of Poles3
Degree of ProtectionFront IP20
Terminal Width20 mm
Transition TypeFast

Technical UL/CSA

Ampere Rating160 A

Why Proax for ABB OT160E03CFP?

Proax is an authorized distributor of ABB OT160E03CFP and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability