A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V. Magnetically latch, control voltage 220-240 V, AC/DC latch
Technical Specifications

Dimensions

Product Net Width142 mm
Product Net Depth / Length160 mm
Product Net Height196 mm
Product Net Weight2.9 kg

Technical

Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO2
Number of Auxiliary Contacts NC2
Rated Operational VoltageMain Circuit 690 V
Rated Frequency (f)Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 275 A
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 200 A, (1000 V) 55 °C 200 A, (1000 V) 70 °C 180 A, (690 V) 40 °C 275 A, (690 V) 55 °C 250 A, (690 V) 70 °C 180 A
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 185 A, (440 V) 55 °C 185 A, (500 V) 55 °C 170 A, (690 V) 55 °C 170 A, (1000 V) 55 °C 95 A, (380 / 400 V) 55 °C 185 A, (220 / 230 / 240 V) 55 °C 185
Rated Operational Power AC-3 (Pe)(415 V) 90 kW, (440 V) 90 kW, (500 V) 110 kW, (690 V) 132 kW, (380 / 400 V) 90 kW, (220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Making Capacity AC-310 x Ie AC-3
Short-Circuit Protective DevicesgG Type Fuses 160 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A, cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1600 A
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour, (AC-2 / AC-4) 150 cycles per hour, (AC-3) 300 cycles per hour
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 275 A, (220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 275 A, (220 V) 3 Poles in Series, 40 °C 275 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 275 A, (220 V) 3 Poles in Series, 40 °C 275 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V, acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Mechanical Durability5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 220 ... 240 V, 60 Hz 220 ... 240 V, DC Operation 220 ... 240 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 35 V·A, Holding at Max. Rated Control Circuit Voltage 60 Hz 40 V·A, Pull-in at Max. Rated Control Circuit Voltage 50 Hz 550 V·A, Pull-in at Max. Rated Control Circuit Voltage 60 Hz 600 V·A
Operate TimeBetween Coil De-energization and NC Contact Closing 40 ... 50 ms, Between Coil De-energization and NO Contact Opening 43 ... 53 ms, Between Coil Energization and NC Contact Opening 45 ... 85 ms, Between Coil Energization and NO Contact Closing 50 ... 90 ms
Connecting Capacity Main CircuitBar 24 mm², Rigid Al-Cable 25 ... 150 mm², Rigid Cu-Cable 6 ... 185 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm², Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm², Flexible 2x0.75 ... 2.5 mm², Solid 2 x 1 ... 4 mm², Stranded 2 x 1 .... 4 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20, acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Connecting Terminals (delivered in open position) Main PolesFlat type c/w screws and bolts
Terminal TypeMain Circuit: Bars

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V
Horsepower Rating UL/CSA(200 V AC) Three Phase 50 hp, (208 V AC) Three Phase 50 hp, (220 ... 240 V AC) Three Phase 60 hp, (440 ... 480 V AC) Three Phase 125 hp, (550 ... 600 V AC) Three Phase 150 hp

Environmental

Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C, Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C, Close to Contactor for Storage -40 ... +70 °C
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27Shock Direction: A 5 g, Shock Direction: B1 5 g, Shock Direction: B2 5 g, Shock Direction: C1 5 g, Shock Direction: C2 5 g
RoHS StatusFollowing EU Directive 2011/65/EU

Why Proax for ABB AM185-30-22-79?

Proax is an authorized distributor of ABB AM185-30-22-79 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate NamesAM185302279
Pack Size1
Recommended

CAD$4,580.21

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability