By ABB
SKU
MPN
1SVR760669R9400
Weight
0.196 kg
The CM-IVN.P serves to extend the measuring range of the insulation monitoring relay CM-IWN.x for monitoring the insulation resistance up to 690 V AC and 1000 V DC in accordance with IEC 61557-8.
Technical Specifications
Dimensions
Product Net Width | 45 mm |
Product Net Height | 85.6 mm |
Product Net Depth / Length | 104.8 mm |
Product Net Weight | 0.165 kg |
Technical
Function | Accessory - Coupling unit for voltage expansion of CM-IWN.1 |
Function | Up to 690 V AC |
Function | Up to 1000 V DC |
Rated Frequency (f) | Measuring Circuit 15 ... 400 Hz |
Terminal Type | Screwless Terminals |
Rated Impulse Withstand Voltage (Uimp) | Input Circuit / PE 8 kV |
Rated Insulation Voltage (Ui) | Input Circuit / PE 1000 V |
Degree of Protection | Housing IP50 |
Degree of Protection | Terminals IP20 |
Overvoltage category | III |
Pollution degree | 3 |
Connecting Capacity | Flexible with Ferrule 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Flexible 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Rigid 2x 0.5 ... 1.5 mm² |
Wire Stripping Length | 8 mm |
Recommended Screw Driver | 0.8 x 4 |
Mounting Position | 1 ... 6 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Standards | CAN/CSA C22.2 No.14 |
Standards | IEC/EN 63000 |
Standards | IEC/EN 61326-2-4 |
Standards | IEC/EN 61557-1 |
Standards | IEC/EN 61557-8 |
Standards | UL 508 |
Technical UL/CSA
Connecting Capacity UL/CSA | Flexible 2x 18-16 AWG |
Connecting Capacity UL/CSA | Rigid 2x 20-16 AWG |
Why Proax for ABB CM-IVN.P?
Proax is an authorized distributor of ABB CM-IVN.P and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | CMIVNP |
Pack Size | 1 |
Recommended
- The CM-MPN.52S is a multifunctional relay from the CM three-phase monitors range. It operates with a rated control supply voltage / three-phase measuring voltage of 350-580 V AC 50/60 Hz and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. This relay monitors all phase parameters such as over/undervoltage, phase unbalance and phase failure. The corresponding threshold values are adjustable. The CM-MPN.52S also offers selection of phase sequence monitoring, automatic phase sequence correction as well as an ON or OFF tripping delay. The output contacts can be configured as 1x2 c/o (SPDT) contacts (common signal) or 2x1 c/o (SPDT) contact (separate signal for over- and undervoltage thresholds) operation. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.