By ABB
SKU
MPN
1SVR750660R0200
Weight
0.277 kg
The CM-IWN.1S serves to monitor insulation resistance in accordance with IEC 61557-8 in unearthed IT AC systems, IT AC systems with galvanically connected DC circuits, or unearthed IT DC systems with a voltage up to 400 V AC and 600 V DC. The measuring range can be extended up to 690 V AC and 1000 V DC by using the coupling unit CM-IVN. It can be configured to the requirements of the applications and therefore used multi-functional.
Documents
Technical Specifications
Dimensions
Product Net Width | 45 mm |
Product Net Height | 85.6 mm |
Product Net Depth / Length | 104.8 mm |
Product Net Weight | 0.241 kg |
Technical
Function | Unearthed AC systems |
Function | Unearthed DC systems |
Function | Unearthed mixed AC / DC systems |
Function | Up to 400 V AC |
Function | Up to 600 V DC |
Measuring Range | 1 ... 200 kΩ |
Rated Control Supply Voltage (Us) | 24 ... 240 V AC/DC |
Rated Frequency (f) | Measuring Circuit 15 ... 400 Hz |
Output | 2 x 1 c/o or 1 x 2 c/o contacts, configurable |
Terminal Type | Screw Terminals |
Rated Operational Current AC-12 (Ie) | (230 V) 4 A |
Rated Operational Current AC-15 (Ie) | (230 V) 3 A |
Rated Operational Current DC-12 (Ie) | (24 V) 4 A |
Rated Operational Current DC-13 (Ie) | (24 V) 2 A |
Minimum switching capacity | 24 V |
Minimum switching capacity | 10 mA |
Rated Impulse Withstand Voltage (Uimp) | Measuring Circuit / Output Circuit 6 kV |
Rated Impulse Withstand Voltage (Uimp) | Output Circuit 1 / Output Circuit 2 4 kV |
Rated Impulse Withstand Voltage (Uimp) | Supply Circuit / Measuring Circuit 6 kV |
Rated Impulse Withstand Voltage (Uimp) | Supply Circuit / Output Circuit 6 kV |
Rated Insulation Voltage (Ui) | Measuring Circuit / Output Circuit 600 V |
Rated Insulation Voltage (Ui) | Output Circuit 1 / Output Circuit 2 300 V |
Rated Insulation Voltage (Ui) | Supply Circuit / Measuring Circuit 600 V |
Rated Insulation Voltage (Ui) | Supply Circuit / Output Circuit 300 V |
Degree of Protection | Housing IP50 |
Degree of Protection | Terminals IP20 |
Overvoltage category | III |
Pollution degree | 3 |
Short-Circuit Protective Devices | Output Circuit NC - F Type Fuses 6 A |
Short-Circuit Protective Devices | Output Circuit NO - F Type Fuses 10 A |
System Leakage Capacitance (CE) | 20 µF |
Electrical Durability | AC-12 100000 cycle |
Mechanical Durability | 30000000 cycle |
Connecting Capacity | Flexible with Ferrule 1x 0.5 ... 2.5 mm² |
Connecting Capacity | Flexible with Ferrule 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm² |
Connecting Capacity | Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Flexible 1x 0.5 ... 2.5 mm² |
Connecting Capacity | Flexible 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Rigid 1x 0.5 ... 4 mm² |
Connecting Capacity | Rigid 2x 0.5 ... 2.5 mm² |
Tightening torque | 0.6 ... 0.8 N·m |
Wire Stripping Length | 8 mm |
Recommended Screw Driver | 0.8 x 4 |
Mounting Position | 1 ... 6 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Standards | CAN/CSA C22.2 No.14 |
Standards | IEC/EN 63000 |
Standards | IEC/EN 61326-2-4 |
Standards | IEC/EN 61557-1 |
Standards | IEC/EN 61557-8 |
Standards | UL 508 |
Technical UL/CSA
Maximum Operating Voltage UL/CSA | Output Circuit 300 V AC |
Contact Rating UL/CSA | B300 |
Connecting Capacity UL/CSA | Flexible 1x 18-14 AWG |
Connecting Capacity UL/CSA | Flexible 2x 18-16 AWG |
Connecting Capacity UL/CSA | Rigid 1x 20-12 AWG |
Connecting Capacity UL/CSA | Rigid 2x 20-14 AWG |
Tightening Torque UL/CSA | 7.08 in·lb |
Pilot Duty UL/CSA | B300 |
Flammability According to UL94 | V-0 |
Why Proax for ABB CM-IWN.1S?
Proax is an authorized distributor of ABB CM-IWN.1S and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | CMIWN1S |
Pack Size | 1 |
Recommended
- The CM-MPN.52S is a multifunctional relay from the CM three-phase monitors range. It operates with a rated control supply voltage / three-phase measuring voltage of 350-580 V AC 50/60 Hz and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. This relay monitors all phase parameters such as over/undervoltage, phase unbalance and phase failure. The corresponding threshold values are adjustable. The CM-MPN.52S also offers selection of phase sequence monitoring, automatic phase sequence correction as well as an ON or OFF tripping delay. The output contacts can be configured as 1x2 c/o (SPDT) contacts (common signal) or 2x1 c/o (SPDT) contact (separate signal for over- and undervoltage thresholds) operation. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.