Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
Weight
2.76 kg
Series TRIO3-PS

TRIO3-PS/3AC/24DC/40/8C/IOL - Power supply unit

Primary-switched power supply unit, TRIO POWER, Push-in connection, 8-channel electronic circuit breaker, IO-Link, DIN rail mounting, input: 3-phase, output: 24 V DC / 40 A, adjustable from 24 V DC ... 28 V DC

  • Power reliability in one device due to the integrated multi-channel device protection
  • Low installation costs due to 70% less wiring and installation effort
  • Easy commissioning through intuitive manual operation or parameterization via IO-Link
  • High availability due to prioritized load management with intelligent self-monitoring functionality
  • Space-saving due to its low overall width and capability of being mounted side by side
Technical Specifications

AC operation

Supply system configurationStar network (TN, TT, IT (PE))
Nominal input voltage range3x 400 V AC ... 500 V AC
Input voltage range3x 400 V AC ... 500 V AC -20 % ... +10 %
Input voltage range2x 400 V AC ... 500 V AC ±10 %
Typical national grid voltage3x 400 V AC
Typical national grid voltage3x 480 V AC
Voltage type of supply voltageAC
Inrush Current< 21 A (25 °C)
Inrush current integral (I2t)< 0.77 A2s
Frequency range (fN)50 Hz ... 60 Hz ±10 %
Mains buffering timetyp. 21 ms (3x 400 V AC)
Mains buffering timetyp. 21 ms (3x 480 V AC)
Current consumption3x 1.5 A (3x 400 V AC)
Current consumption3x 1.2 A (3x 500 V AC)
Current consumption2x 2.6 A (2x 400 V AC)
Current consumption2x 2.1 A (2x 500 V AC)
Protective circuitTransient protection; Varistor
Power factor (cos phi)0.94 (3x 480 V AC)
Device mains fuse6.3 A internal (device protection)
Recommended breaker for input protection3x 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE< 3.5 mA

Output data

Efficiencytyp. 94.4 % (3x 400 V AC)
Efficiencytyp. 94.6 % (3x 480 V AC)
Nominal Output Voltage24 V DC
Setting range of the output voltage (USet)24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)40 A
Dynamic Boost (IDyn.Boost)max. 60 A (5 s)
No. of channels8
Nominal current per channel1 A
Nominal current per channel2 A
Nominal current per channel3.8 A
Nominal current per channel4 A
Nominal current per channel6 A
Nominal current per channel8 A
Nominal current per channel10 A
Waiting time after switch off of a channel5 s
Switch-on delay of the channels100 ms
Short-circuit-proofyes
No-load proofyes
Derating60 °C ... 70 °C
Crest factortyp. 1,54 (3x 400 V AC)
Crest factortyp. 1,53 (3x 480 V AC)
Output power (PN)960 W
Output power (PDyn. Boost)max. 1440 W (5 s)
Connection in parallelno
Connection in seriesNo
Max. capacitive load30 mF
Feedback voltage resistance≤ 35 V DC
Protection against overvoltage at the output (OVP)≤ 35 V DC
Residual rippletyp. 13 mVPP (with nominal values)
Control deviation< 1 % (change in load, static 10 % ... 90 %)
Control deviation< 3 % (change in load, dynamic 10 % ... 90 %)
Control deviation< 0.1 % (change in input voltage ±10 %)
Rise time≤ 1 s (UOut = 10 % ... 90 %)
Minimum no-load power dissipation< 1.37 W (3x 400 V AC)
Maximum no-load power dissipation< 0.77 W (3x 480 V AC)
Minimum nominal load power dissipation< 45.75 W (3x 400 V AC)
Power loss nominal load max.< 42.52 W (3x 480 V AC)
Integrated fuse protectionyes

Signal relay 13/14

Position3.x
Position marking3.1 (13), 3.2 (14)
Switch contact (floating)OptoMOS
Switching voltagemax. 30 V DC (SELV)
Current carrying capacitymax. 100 mA
State conditionUOut > 21 V DC and IOut < 0.9 x IN (Contact closed)
State conditionUOut < 21 V DC or IOut > 0.9 x IN  (averaging over 60 s) (Contact open)
State conditionChannel triggered or defective or OVP active

Input

Position1.x

Connection technology

Position marking1.1 (L1), 1.2 (L2), 1.3 (L3), 1.4 ()

Conductor connection

Connection MethodPush-in connection
rigid0.2 mm² ... 4 mm²
rigid1.5 mm² (recommended)
flexible0.2 mm² ... 2.5 mm²
flexible1.5 mm² (recommended)
flexible with ferrule without plastic sleeve0.25 mm² ... 2.5 mm²
flexible with ferrule without plastic sleeve1.5 mm² (recommended)
flexible with ferrule with plastic sleeve0.25 mm² ... 1.5 mm²
flexible with ferrule with plastic sleeve1.5 mm² (recommended)
rigid (AWG)24 ... 12 (Cu)
rigid (AWG)16 (recommended)
Stripping length10 mm (rigid/flexible)
Stripping length8 mm (Ferrule)

Output

Position2.x

Connection technology

Position marking2.1, 2.2, 2.3, 2.4, 2.5, 2.6, 2.7, 2.8 (+)

Conductor connection

Connection MethodPush-in connection
rigid0.2 mm² ... 4 mm²
rigid1.5 mm² (recommended)
flexible0.2 mm² ... 2.5 mm²
flexible1.5 mm² (recommended)
flexible with ferrule without plastic sleeve0.25 mm² ... 2.5 mm² (Cu)
flexible with ferrule without plastic sleeve1.5 mm² (recommended)
flexible with ferrule with plastic sleeve0.25 mm² ... 1.5 mm²
flexible with ferrule with plastic sleeve1.5 mm² (recommended)
rigid (AWG)24 ... 12 (Cu)
rigid (AWG)16 (recommended)
Stripping length10 mm (rigid/flexible)
Stripping length8 mm (Ferrule)

Output

Position2.x

Connection technology

Position marking2.9, 2.10 (-)

Conductor connection

Connection MethodPush-in connection
rigid0.75 mm² ... 16 mm²
rigid10 mm² (recommended)
flexible0.75 mm² ... 16 mm²
flexible10 mm² (recommended)
flexible with ferrule without plastic sleeve0.75 mm² ... 16 mm² (Cu)
flexible with ferrule without plastic sleeve10 mm² (recommended)
flexible with ferrule with plastic sleeve0.75 mm² ... 10 mm²
flexible with ferrule with plastic sleeve10 mm² (recommended)
rigid (AWG)20 ... 4 (Cu)
rigid (AWG)8 (recommended)
Stripping length18 mm (rigid/flexible)
Stripping length18 mm (Ferrule)

Signal

Position3.x

Connection technology

Position marking3.1 (13), 3.2 (14)

Conductor connection

Connection MethodPush-in connection
rigid0.2 mm² ... 1.5 mm²
rigid0.5 mm² (recommended)
flexible0.2 mm² ... 1.5 mm²
flexible0.5 mm² (recommended)
flexible with ferrule without plastic sleeve0.25 mm² ... 1.5 mm² (Cu)
flexible with ferrule without plastic sleeve0.5 mm² (recommended)
flexible with ferrule with plastic sleeve0.25 mm² ... 0.75 mm²
flexible with ferrule with plastic sleeve0.5 mm² (recommended)
rigid (AWG)24 ... 16 (Cu)
rigid (AWG)20 (recommended)
Stripping length10 mm (rigid/flexible)
Stripping length8 mm (Ferrule)

Communication

Position5.x

Connection technology

Position marking5.1 (L+), 5.2 (C/Q), 5.3 (L-)

Conductor connection

Connection MethodPush-in connection
rigid0.2 mm² ... 1.5 mm²
rigid0.5 mm² (recommended)
flexible0.2 mm² ... 1.5 mm²
flexible0.5 mm² (recommended)
flexible with ferrule without plastic sleeve0.25 mm² ... 1.5 mm² (Cu)
flexible with ferrule without plastic sleeve0.5 mm² (recommended)
flexible with ferrule with plastic sleeve0.25 mm² ... 0.75 mm²
flexible with ferrule with plastic sleeve0.5 mm² (recommended)
rigid (AWG)24 ... 16 (Cu)
rigid (AWG)20 (recommended)
Stripping length10 mm (rigid/flexible)
Stripping length8 mm (Ferrule)

IO-Link

SpecificationV1.1
InterfaceIO-Link
Number of interfaces1
Connection MethodPush-in connection
Position5.x
Position marking5.1 (L+), 5.2 (C/Q), 5.3 (L-)
Transmission physics3-wire, standard industrial cable
Reverse polarity protectionyes
Transmission Speed38.4 kbps (COM2)
Cycle Time40 ms
Amount of Process Data6 Byte (Input data)
Device ID040117hex/262423dez
Vendor ID00B0hex / 176dez

LED signaling

Types of signalingLED DC OK – signal state operation (UN = 24 V DC, IOut = IN)
FunctionVisual operating state display
Colorred, yellow, green (multicolor LED)
LED offSupply voltage input AC not present (Off)
LED on (green), DC OKUOut > 21 V DC and IOut < 0.9 x IN (On (green), DC OK)
LED on (yellow), IOut > 90%UOut > 21 V DC and IOut > 0.9 x IN (On (yellow), IOut > 90% )
LED on (flashing red) OVPUOUT > OVP (Over voltage protection) (On (flashing red))

Electrical properties

Number of phases3.00
Insulation voltage input/output5.3 kV DC (type test)
Insulation voltage input/output3.1 kV DC (routine test)

Product properties

Product familyTRIO POWER
MTBF (IEC 61709, SN 29500)> 1200000 h (25 °C)
MTBF (IEC 61709, SN 29500)> 660000 h (40 °C)
MTBF (IEC 61709, SN 29500)> 265000 h (60 °C)
Environmental protection directiveRoHS Directive 2011/65/EU
Environmental protection directiveWEEE
Environmental protection directiveReach

Insulation characteristics

Protection classI
Degree of pollution2

Item dimensions

Width128 mm
Height135 mm
Depth167 mm
Depth160 mm (Device depth (DIN rail mounting))

Installation dimensions

Installation distance right/left (active)15 mm / 15 mm
Installation distance right/left (passive)0 mm / 0 mm (≤ 40 °C)

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable: 0 mm horizontally, 30 mm vertically
Mounting Positionhorizontal DIN rail NS 35, EN 60715
With protective coatingNo

Material specifications

Flammability rating according to UL 94V0 (Housing, terminal blocks)
Hood versionPolycarbonate
Side element versionAluminum

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (start-up type tested)-40 °C
Maximum altitude≤ 5000 m (> 2000 m, Derating: 10 %/1000 m)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock (operation)11 ms, 15g, je Raumrichtung (IEC 60068-2-27)
Vibration (Operation)10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6)
Vibration (Operation)50 Hz ... 150 Hz, 0,7g, 90 min.

Overvoltage category

EN 61010-1III (≤ 2000 m)
EN 61010-1II (≤ 5000 m)
EN 61010-2-201III (≤ 2000 m)
EN 61010-2-201II (≤ 5000 m)

Safety of power supply units up to 1100 V (insulation distances)

Standard designationSafety of power supply units up to 1100 V (insulation distances)
Standards/specificationsDIN EN 61558-2-16

Electrical safety

Standard designationElectrical safety
Standards/specificationsIEC 61010-2-201 (SELV)

Electronic equipment for use in power installations

Standard designationEquipping high voltage installations with electronic equipment
Standards/specificationsEN 50178/VDE 0160 (PELV)

Safety for measurement, control, and laboratory equipment

Standard designationSafety for equipment for measurement, control, and laboratory use
Standards/specificationsIEC 61010-1

Protective extra-low voltage

Standard designationProtective extra-low voltage
Standards/specificationsIEC 61010-1 (SELV)
Standards/specificationsIEC 61010-2-201 (PELV)

Safe isolation

Standard designationSafe isolation
Standards/specificationsIEC 61558-2-16
Standards/specificationsIEC 61010-2-201

Limitation of harmonic line currents

Standard designationLimitation of harmonic line currents
Standards/specificationsEN 61000-3-2

Mains variation/undervoltage

Standard designationMains variation/undervoltage
Standards/specificationsSEMI F47
Standards/specificationsEN 61000-4-11

UL

IdentificationUL/C-UL Listed UL 61010-1
IdentificationUL/C-UL Listed UL 61010-2-201

UL/CSA

IdentificationUL 1310 / CSA C22.2 No. 223 (NEC Class 2)

UL

IdentificationUL 2367 (Standard for Safety for Solid State Overcurrent Protectors)

ANSI/UL

IdentificationPROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS
Identification(EN)  This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only.(FR)  Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles.
Identification(EN)  WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.(FR)  AVERTISSEMENT : risque d'explosion - ne pas connecter ou déconnecter les équipements sauf si l'alimentation a été coupée ou si la zone est réputée non dangereuse.
Identification(EN)  If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.(FR)  Si l'équipement est utilisé d'une manière non spécifiée par le fabricant, la protection fournie par cet équipement peut être altérée.
Identification(EN)  This equipement must be installed in a suitable, tool secured/key locked enclosure.(FR)  Cet équipement doit être installé dans un boîtier approprié, verrouillé par une clé ou dont l'ouverture nécessite l'utilisation d'un outil.

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
Interference emissionInterference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
Noise immunityImmunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial)
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Conducted noise emissionEN 55016
Conducted noise emissionEN 61000-6-3 (Class B)
Noise emissionEN 55016
Noise emissionEN 61000-6-3 (Class B)

Harmonic currents

Standards/regulationsEN 61000-3-2
Standards/regulationsEN 61000-3-2 (Class A)
Frequency Range0 kHz ... 2 kHz

Flicker

Standards/regulationsEN 61000-3-3
Standards/regulationsEN 61000-3-3
Frequency Range0 kHz ... 2 kHz

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge6 kV (Test Level 3)
Discharge in air8 kV (Test Level 3)
CommentsCriterion B

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range1 GHz ... 6 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Inputasymmetrical 2 kV (Test Level 3)
Outputasymmetrical 2 kV (Test Level 3)
Signalasymmetrical 1 kV (Test Level 3)
CommentsCriterion A

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Inputsymmetrical 1 kV (Test Level 3)
Inputasymmetrical 2 kV (Test Level 3)
Outputsymmetrical 0.5 kV (Test Level 2)
Outputasymmetrical 1 kV (Test Level 2)
Signalasymmetrical 1 kV (Test Level 2)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
I/O/Sasymmetrical
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Voltage dips

Standards/regulationsEN 61000-4-11
Voltage480 V AC
Frequency50 Hz
Voltage dip70 %
Number of periods25 periods
Additional textClass 3
CommentsCriterion A
Voltage dip40 %
Number of periods10 periods
Additional textClass 3
CommentsCriterion B
Voltage dip0 %
Number of periods1 period
Additional textClass 3
CommentsCriterion A

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.
Criterion CTemporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

Why Proax for Phoenix Contact 1362792?

Proax is an authorized distributor of Phoenix Contact 1362792 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability