Official Distributor
SKU
MPN
PT 2,5-PE/L/N/MT
Weight
0.033 kg
Series PT
PT 2,5-PE/L/N/MT - Protective conductor terminal
Protective conductor terminal, Protective conductor connection, connection method: Push-in connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, Feed-through level, connection method: Push-in connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, mounting: NS 35/7,5, NS 35/15, color: gray
Technical Specifications
Product properties
Number of Positions | 4 |
Number of Connections | 8 |
Insulation characteristics
Overvoltage category | III |
Degree of pollution | 3 |
Electrical properties
Rated surge voltage | 6 kV |
Connection data
Number of connections per level | 2 |
Nominal cross section | 2.5 mm² |
Protective conductor connection
Stripping length | 8 mm ... 10 mm |
Internal cylindrical gage | A3 |
Internal cylindrical gage | B3 |
Connection in acc. with standard | IEC 60947-7-2 |
Conductor cross section rigid | 0.14 mm² ... 4 mm² |
Cross section AWG | 26 ... 12 (converted acc. to IEC) |
Conductor cross section flexible | 0.14 mm² ... 4 mm² |
Conductor cross section, flexible [AWG] | 26 ... 12 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Nominal cross section | 2.5 mm² |
Feed-through level
Stripping length | 8 mm ... 10 mm |
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section rigid | 0.14 mm² ... 4 mm² |
Cross section AWG | 26 ... 12 (converted acc. to IEC) |
Conductor cross section flexible | 0.14 mm² ... 4 mm² |
Conductor cross section, flexible [AWG] | 26 ... 12 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Nominal Current | 18 A |
Maximum Load Current | 20 A (with 4 mm² conductor cross-section) |
Nominal Voltage | 500 V |
Nominal cross section | 2.5 mm² |
Disconnect zone
Stripping length | 8 mm ... 10 mm |
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section rigid | 0.14 mm² ... 4 mm² |
Cross section AWG | 26 ... 12 (converted acc. to IEC) |
Conductor cross section flexible | 0.14 mm² ... 4 mm² |
Conductor cross section, flexible [AWG] | 26 ... 12 (converted acc. to IEC) |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.14 mm² ... 2.5 mm² |
Nominal Current | 18 A |
Maximum Load Current | 20 A (with 4 mm² conductor cross-section) |
Nominal Voltage | 500 V |
Nominal cross section | 2.5 mm² |
Protective conductor connection Connection cross sections directly pluggable
Conductor cross section rigid | 0.34 mm² ... 4 mm² |
Conductor cross section, rigid [AWG] | 20 ... 12 (converted acc. to IEC) |
Conductor cross section flexible | 0.5 mm² ... 2.5 mm² |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Feed-through level Connection cross sections directly pluggable
Conductor cross section rigid | 0.34 mm² ... 4 mm² |
Conductor cross section, rigid [AWG] | 20 ... 12 (converted acc. to IEC) |
Conductor cross section flexible | 0.5 mm² ... 2.5 mm² |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Disconnect zone Connection cross sections directly pluggable
Conductor cross section rigid | 0.34 mm² ... 4 mm² |
Conductor cross section, rigid [AWG] | 20 ... 12 (converted acc. to IEC) |
Conductor cross section flexible | 0.5 mm² ... 2.5 mm² |
Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 2.5 mm² |
Dimensions
Width | 5.2 mm |
End cover width | 2.2 mm |
Height | 142.4 mm |
Depth on NS 35/7,5 | 70.2 mm |
Depth on NS 35/15 | 77.7 mm |
Material specifications
Color | gray |
Flammability rating according to UL 94 | V0 |
Insulating material group | I |
Insulating material | PA |
Surge voltage test
Result | Test passed |
Temperature-rise test
Requirement temperature-rise test | Increase in temperature ≤ 45 K |
Result | Test passed |
Short-time withstand current 2.5 mm² | 0.3 kA |
Result | Test passed |
Power-frequency withstand voltage
Test voltage setpoint | 1.89 kV |
Result | Test passed |
Mechanical data
Open side panel | Yes |
Mechanical strength
Result | Test passed |
Attachment on the carrier
DIN rail/fixing support | NS 35 |
Result | Test passed |
Test for conductor damage and slackening
Rotation speed | 10 (+/- 2) rpm |
Revolutions | 135 |
Conductor cross section/weight | 0.14 mm² / 0.2 kg |
Conductor cross section/weight | 2.5 mm² / 0.7 kg |
Conductor cross section/weight | 4 mm² / 0.9 kg |
Result | Test passed |
Aging
Temperature cycles | 192 |
Temperature cycles | 192 |
Result | Test passed |
Result | Test passed |
Needle-flame test
Time of exposure | 30 s |
Result | Test passed |
Oscillation/broadband noise
Specification | DIN EN 50155 (VDE 0115-200):2022-06 |
Spectrum | Service life test category 1, class B, body mounted |
Frequency | f1 = 5 Hz to f2 = 150 Hz |
ASD level | 0.964 (m/s²)²/Hz |
Acceleration | 3.12g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Result | Test passed |
Shocks
Specification | DIN EN 50155 (VDE 0115-200):2022-06 |
Pulse shape | Half-sine |
Acceleration | 5g |
Shock duration | 30 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Result | Test passed |
Ambient conditions
Ambient Temperature (Operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Ambient temperature (assembly) | -5 °C ... 70 °C |
Ambient temperature (actuation) | -5 °C ... 70 °C |
Permissible humidity (operation) | 20 % ... 90 % |
Permissible humidity (storage/transport) | 30 % ... 70 % |
Standards and Regulations
Connection in acc. with standard | IEC 60947-7-2 |
Connection in acc. with standard | IEC 60947-7-1 |
Connection in acc. with standard | IEC 60947-7-1 |
Mounting
Mounting Type | NS 35/7,5 |
Mounting Type | NS 35/15 |
Why Proax for Phoenix Contact 1336376?
Proax is an authorized distributor of Phoenix Contact 1336376 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 1336388 - Knife-disconnect terminal block, Protective conductor connection, connection method: Push-in connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, Feed-through level, connection method: Push-in connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, mounting: NS 35/7,5, NS 35/15, color: gray
- Bloc de jonction à plusieurs étages, nombre de connexions: 8, nombre de pôles: 4, type de raccordement: Raccordement Push-in, Raccordement du conducteur de protection, Section de référence: 2,5 mm2, section : 0,14 mm2 - 4 mm2, type de raccordement: Raccordement Push-in, Étage de traversée, Section de référence: 2,5 mm2, section : 0,14 mm2 - 4 mm2, type de montage: NS 35/7,5, NS 35/15, coloris: gris
- 3210208 - Disconnect terminal block, The max. load current must not be exceeded by the total current of all connected conductors.Current and voltage are determined by the plug used., nom. voltage: 400 V, nominal current: 20 A, connection method: Push-in connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, mounting: NS 35/7,5, NS 35/15, color: gray
- 3210194 - Disconnect terminal block, The max. load current must not be exceeded by the total current of all connected conductors.Current and voltage are determined by the plug used., nom. voltage: 400 V, nominal current: 16 A, connection method: Push-in connection, Rated cross section: 2.5 mm2, cross section: 0.14 mm2 - 4 mm2, mounting: NS 35/7,5, NS 35/15, color: gray