ABBOfficial Distributor

By ABB

SKU
MPN
GJL1311911R8100
Weight
0.36 kg
The VB7A-30-10 mini reversing contactor is a compact 3 pole contactor with 1 auxiliary contact, screw terminals and mechanical interlock and safety blocking. They are ideally suited for applications where reliability is a must and space is at a premium. Mini reversing contactors are used in residential buldings, commercial buildings and industrial applications for the control of three-phase motor loads up to 5.5 kW (AC-3). Further features are the silent coil, a switch position indication and the integrated possibility for rail or wall mounting.
Technical Specifications

Dimensions

Product Net Width96.2 mm
Product Net Height57.5 mm
Product Net Depth / Length46.7 mm
Product Net Weight0.355 kg

Technical

Number of Poles3
Rated Operational VoltageAuxiliary Circuit 690 V AC
Rated Operational VoltageAuxiliary Circuit 250 V DC
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational VoltageMain Circuit 220 V DC
Rated Frequency (f)Main Circuit 60 Hz
Rated Frequency (f)Main Circuit 50 Hz
Rated Frequency (f)Main Circuit DC
Rated Impulse Withstand Voltage (Uimp)Main Circuit 6 kV
Rated Insulation Voltage (Ui)690 V
Rated Insulation Voltage (Ui)acc. to UL/CSA 600 V
Number of Main Contacts NC0
Number of Main Contacts NO3
Rated Operational Current AC-1 (Ie)(220 / 240 V) 40 °C 20 A
Rated Operational Current AC-1 (Ie)(220 / 240 V) 55 °C 16 A
Rated Operational Current AC-1 (Ie)(380 / 440 V) 40 °C 20 A
Rated Operational Current AC-1 (Ie)(380 / 440 V) 55 °C 16 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 6 A
Rated Operational Current AC-1 (Ie)(690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe)(230 V) Three Phase 3 kW
Rated Operational Power AC-3 (Pe)(400 V) Three Phase 5.5 kW
Rated Operational Power AC-3 (Pe)(500 V) Three Phase 5.5 kW
Rated Operational Power AC-3 (Pe)(690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A
Number of Auxiliary Contacts NC0
Number of Auxiliary Contacts NO1
Conventional Free-air Thermal Current (Ith)Main Circuit 20 A
Rated Control Circuit Voltage (Uc)220 ... 240 V AC
Coil Operating Limits(acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Degree of ProtectionMain Circuit Terminals IP20
Pollution degree3
Mechanical Durability10000000 cycle
Minimum switching capacityAuxiliary Circuit 17 V
Minimum switching capacityAuxiliary Circuit 5 mA
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Maximum Electrical Switching Frequency(AC-15) 600 cycles per hour
Maximum Electrical Switching Frequency(AC-3) 600 cycles per hour
Maximum Electrical Switching Frequency(DC-1) 600 cycles per hour
Maximum Electrical Switching Frequency(DC-13) 600 cycles per hour
Maximum Electrical Switching Frequency(DC-3) 600 cycles per hour
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 1 ... 2.5 mm²
Connecting Capacity Main CircuitFlexible with Insulated Ferrule 1/2x 1 ... 2.5 mm²
Connecting Capacity Main CircuitFlexible 1/2x 1 ... 2.5 mm²
Connecting Capacity Main CircuitRigid 1/2x 1 ... 4 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 1 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Insulated Ferrule 1/2x 1 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible 1/2x 1 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitRigid 1/2x 1 ... 4 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Insulated Ferrule 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitRigid 1/2x 1 ... 4 mm²
Wire Stripping LengthAuxiliary Circuit 9 mm
Wire Stripping LengthMain Circuit 9 mm
Tightening torqueControl Circuit 0.8 ... 1.1 N·m
Tightening torqueMain Circuit 0.8 ... 1.1 N·m
Recommended Screw DriverM3
Recommended Screw DriverPozidriv 1
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Mounting on DIN RailTH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Lossat Rated Operating Conditions AC-1 per Pole 1.4 W
StandardsIEC/EN 60947-1
StandardsIEC/EN 60947-4-1
StandardsIEC/EN 60947-5-1
StandardsUL 60947-1
StandardsUL 60947-4-1

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Full Load Amps Motor Use(115 V AC) Single Phase 13.8 A
Full Load Amps Motor Use(200 V AC) Three Phase 7.8 A
Full Load Amps Motor Use(220 ... 240 V AC) Three Phase 9.6 A
Full Load Amps Motor Use(230 V AC) Single Phase 10 A
Full Load Amps Motor Use(440 ... 480 V AC) Three Phase 7.6 A
Full Load Amps Motor Use(550 ... 600 V AC) Three Phase 6.1 A
Horsepower Rating UL/CSA(115 V AC) Single Phase 0.75 Hp
Horsepower Rating UL/CSA(200 V AC) Three Phase 2 Hp
Horsepower Rating UL/CSA(220 ... 240 V AC) Three Phase 3 Hp
Horsepower Rating UL/CSA(230 V AC) Single Phase 1.5 Hp
Horsepower Rating UL/CSA(440 ... 480 V AC) Three Phase 5 Hp
Horsepower Rating UL/CSA(550 ... 600 V AC) Three Phase 5 Hp
General Use Rating UL/CSA(600 V AC) 16 A
Contact Rating UL/CSAA600
Connecting Capacity Main Circuit UL/CSAStranded 1/2x 22-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSAStranded 1/2x 22-10 AWG
Tightening Torque UL/CSAAuxiliary Circuit 7 in·lb
Tightening Torque UL/CSAControl Circuit 7 in·lb
Tightening Torque UL/CSAMain Circuit 7 in·lb

Why Proax for ABB VB7A-30-10-80?

Proax is an authorized distributor of ABB VB7A-30-10-80 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesVB7A301080
Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability