1157954
SKU
PHX1157954
MPN
REL-SR- 24DC/3X1AU/1X2AU/FG
Weight
0.022 kg
Series REL-SR
REL-SR- 24DC/3X1AU/1X2AU/FG - Safety relays
Safety relay with force-guided contacts in accordance with DIN EN 61810-3 (type A), input voltage 24 V DC, with multi-layer gold contact, 3 N/O contacts and 1 N/C contacts
Technical Specifications
Product properties
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 10⁷ cycles |
| B10d | 810000 Cycles (AC15, 250 V / 0.5 A, 1 NO) |
| B10d | 170000 Cycles (AC15; 250 V / 2 A; 1 NO) |
| B10d | 318000 Cycles (DC13, 24 V / 1 A, 1 NO) |
| B10d | 208000 Cycles (DC13, 24 V / 2 A, 1 NO) |
Insulation characteristics
| Insulation | Basic insulation |
| Insulation | Safe isolation, reinforced insulation and 6 KV between the coil and the contact circuit and between the contacts 3-4, 5-6 to 7-8, 9-10 |
Insulation characteristics: Air clearances and creepage distances between the power circuits
| Insulation | Basic insulation |
| Insulation | Safe isolation, reinforced insulation and 6 KV between the coil and the contact circuit and between the contacts 3-4, 5-6 to 7-8, 9-10 |
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Maximum power dissipation for nominal condition | 0.36 W |
| Test voltage (Winding/contact) | 4 kVrms (50 Hz, 1 min., winding/contact) |
| Test voltage (Contact/contact) | 2.5 kVrms (50 Hz, 1 min., contact/contact) |
Air clearances and creepage distances between the power circuits
| Rated Insulation Voltage | 250 V AC |
| Rated surge voltage | 4 kV |
Coil side
| Nominal input voltage UN | 24 V DC |
| Input voltage range | 19.2 V DC ... 26.4 V DC |
| Input voltage range in reference to UN | see diagram |
| Drive and function | monostable |
| Drive (polarity) | non-polarized |
| Typical input current at UN | 15 mA |
| Typical response time | 10 ms |
| Typical release time | 5 ms |
Switching
| Contact switching type | 3 N/O contacts, 1 N/C contact, force-guided |
| Type of switch contact | Single contact |
| Contact Material | AgSnO, hard gold-plated |
| Maximum Switching Voltage | 250 V AC |
| Maximum Switching Voltage | 300 V DC |
| Minimum Switching Voltage | 10 V |
| Limiting Continuous Current | 6 A |
| Maximum Inrush Current | 35 A (20 ms) |
| Min. switching current | 5 mA (10 V) |
| Interrupting rating (ohmic load) max. | 144 W (24 V DC) |
| Interrupting rating (ohmic load) max. | 100 W (48 V DC) |
| Interrupting rating (ohmic load) max. | 75 W (60 V DC) |
| Interrupting rating (ohmic load) max. | 55 W (110 V DC) |
| Interrupting rating (ohmic load) max. | 50 W (220 V DC) |
| Interrupting rating (ohmic load) max. | 1500 VA (250 V AC) |
| Switching capacity | 2 A (24 V, DC13) |
| Switching capacity | 3 A (230 V, AC15) |
| Force-guided contacts in accordance with EN 61810-3 | Type A |
Connection data
| Connection Method | Plug / solder connection |
Dimensions
| Width | 13 mm |
| Height | 24 mm |
| Depth | 40 mm |
Ambient conditions
| Degree of protection (Relay) | RT II |
| Degree of protection (Installation location) | IP54 (Installation location) |
| Ambient Temperature (Operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m |
Corrosive gas test
| Identification | ISA-S71.04. G3 Harsh Group |
| Identification | EN 60068-2-60 |
Air clearances and creepage distances between the power circuits
| Standards/regulations | DIN EN 50178 |
| Standards/regulations | EN 61810-1 |
Mounting
| Mounting Position | any |
Why Proax for Phoenix Contact 1157954?
Proax is an authorized distributor of Phoenix Contact 1157954 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 10 |
Recommended