IB IL CNT-XC-PAC - Function module
Inline, Function terminal, Counter input for 24 V signals: 1, Control input for 24 V signals: 1, Switching output: 1, 24 V DC, 0.5 A, Extreme conditions version, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
- 1 counter input
- 1 control input
- 1 freely parameterizable switching output
- Four operating modes: event counting, time or state-controlled frequency measurement, time measurement (period or pulse length), and pulse generator
- Processing of 5 V or 24 V signals
- Input frequency of up to 100 kHz
- 16-bit counter value for time measurement
- 24-bit counter value for event counting and frequency measurement
- Can be used under extreme ambient conditions
- Extended temperature range of -40 °C ... +70 °C (see “Tested successfully: use under extreme ambient conditions” in the data sheet)
- Coated PCBs
Technical Specifications
Dimensions
Width | 24.4 mm |
Height | 135 mm |
Depth | 71.5 mm |
Inline local bus
Number of interfaces | 2 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
Transmission physics | Copper |
Module
ID code (dec.) | 191 |
ID code (hex) | BF |
Length code (hex) | 02 |
Length code (dec) | 02 |
Process data channel | 32 bit |
Input address area | 4 Byte |
Output address area | 4 Byte |
Register length | 4 Byte |
Required parameter data | 1 Byte |
Required configuration data | 5 Byte |
Counter:
Input name | Counter input for 24 V signals |
Connection Method | Spring-cage connection |
Connection technology | 2-, 3-conductor |
Number of Inputs | 1 (only one counter input can be used, either for 24 V or for 5 V signals) |
Operating mode | Event counting, frequency/time measurement |
Input Voltage | 24 V DC (Nominal voltage) |
Input Voltage | 30 V DC (maximum) |
Input voltage range "0" signal | 0 V DC ... 5 V DC |
Input voltage range "1" signal | 15 V DC ... 30 V DC |
Input Frequency | max. 100 kHz |
Input Current | typ. 5 mA |
Input resistance | approx. 5.7 kΩ |
Input name | Counter input for 5 V signals |
Connection Method | Spring-cage connection |
Connection technology | 2-conductor (shielded), external 5 V supply |
Number of Inputs | 1 (only one counter input can be used, either for 24 V or for 5 V signals) |
Operating mode | Event counting, frequency/time measurement |
Input Voltage | 5 V DC (Nominal voltage) |
Input Voltage | 8 V DC (maximum) |
Input voltage range "0" signal | 0 V ... 1.5 V |
Input voltage range "1" signal | 3.5 V ... 8 V |
Input Frequency | max. 100 kHz |
Input Current | typ. 5 mA |
Input resistance | approx. 1.7 kΩ |
Digital:
Output name | Switching output |
Connection Method | Spring-cage connection |
Connection technology | 2-conductor |
Number of Outputs | 1 |
Protective circuit | Short-circuit protection; Yes, short-circuit-proof (automatically switched on again) |
Protective circuit | Overload protection |
Output Voltage | 24 V DC (Nominal voltage) |
Output Current | max. 0.5 A (Nominal current) |
Nominal load, inductive | max. 12 VA (1.2 H, 48 Ω) |
Nominal load, lamp | max. 12 W |
Nominal load, ohmic | max. 12 W (48 Ω) |
Reverse voltage resistance to short pulses | Reverse voltage proof |
Behavior in the event of ohmic overload | Auto restart after eliminating the overload |
Behavior with inductive overload | Output can be destroyed |
Behavior in the event of lamp overload | Auto restart after eliminating the overload |
Overcurrent shut-down | min. 0.7 A |
Product properties
Product family | Inline |
Type | modular |
Scope of delivery | including Inline connectors and marking fields |
Operating mode | Process data operation with 2 words |
Special Properties | Extreme conditions version |
Diagnostics messages | Sensor supply short-circuit |
Diagnostics messages | Sensor supply overload |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 50 mA |
Current draw | typ. 40 mA |
Power consumption | max. 0.375 W (at UL) |
Potentials: Segment circuit supply (US)
Supply Voltage | 24 V DC (via voltage jumper) |
Current draw | max. 1 A |
Current draw | min. 0 A (without connected peripherals) |
Supply:
Designation | Power supply for sensors |
Supply Voltage | 24 V DC (generated from segment supply US) |
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 7.5 V supply (bus logic)/functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 24 V supply (I/O) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C (Standard) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.) |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact IB IL CNT-XC-PAC?
Proax is an authorized distributor of Phoenix Contact IB IL CNT-XC-PAC and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | IBILCNTXCPAC |
Pack Size | 1 |
Recommended