Official Distributor
SKU
MPN
PLC-BSP-120UC/ 1/SEN/SO46
Weight
0.029 kg
Series PLC-BSP
PLC-BSP-120UC/ 1/SEN/SO46 - Relay base
6.2 mm PLC basic terminal block with interference current and interference voltage protection on the control side, with spring-cage connection, without relay or solid-state relay, with sensor supply voltage distribution (BB), 1 N/O contact, input voltage 120 V AC
- High relay release voltage
- Resistant to interference currents
Technical Specifications
Utilization restriction
EMC note | EMC: class A product, see manufacturer's declaration in the download area |
Product properties
Product family | PLC-INTERFACE |
Application | Filter to prevent interference |
Operating mode | 100% operating factor |
Compatible components | Miniature relay, REL-MR-60DC/21AU, REL-MR-60DC/21; miniature optocoupler, OPT-60DC/48DC/100, OPT-60DC/24DC/2, OPT-60DC/230AC/1 |
Electrical properties
Protective circuit | Bridge rectifier; Bridge rectifier |
Protective circuit | RCZ filter; RCZ filter |
Input data
Nominal input voltage UN | 120 V AC |
Relay assembly
Nominal input voltage UN | 120 V AC |
Input voltage range in reference to UN | 0.8 ... 1.4 |
Typical input current at UN | 7 mA (50 Hz) |
Typical input current at UN | 8 mA (60 Hz) |
Typical response time | 7 ms |
Typical release time | 20 ms |
Typical release voltage | 50 V AC |
Operating voltage display | Yellow LED |
Protective circuit | Bridge rectifier; Bridge rectifier |
Protective circuit | Filter; Filter |
Optocoupler assembly
Nominal input voltage UN | 120 V AC |
Input voltage range in reference to UN | 0.85 ... 1.1 |
Typical input current at UN | 7 mA |
Typical input current at UN | 8 mA |
Switching threshold "0" signal in reference to UN | ≤ 0.4 |
Typical response time | 6 ms |
Typical release time | 10 ms |
Operating voltage display | Yellow LED |
Protective circuit | Bridge rectifier; Bridge rectifier |
Protective circuit | Filter; Filter |
Output data
Compatible components | Miniature relay, REL-MR-60DC/21AU, REL-MR-60DC/21; miniature optocoupler, OPT-60DC/48DC/100, OPT-60DC/24DC/2, OPT-60DC/230AC/1 |
Maximum Switching Voltage | 48 V DC |
Minimum Switching Voltage | 3 V DC |
Limiting Continuous Current | 100 mA |
Voltage drop at max. limiting continuous current | < 1 V DC |
Output circuit | 2-conductor, floating |
Protective circuit | Reverse polarity protection |
Protective circuit | Surge protection |
Maximum Switching Voltage | 30 V DC |
Minimum Switching Voltage | 3 V DC |
Limiting Continuous Current | 3 A |
Voltage drop at max. limiting continuous current | < 200 mV |
Maximum Inrush Current | 15 A (10 ms) |
Output circuit | 2-conductor, floating |
Protective circuit | Reverse polarity protection |
Protective circuit | Surge protection |
Maximum Switching Voltage | 253 V AC (Partition plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal points in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) |
Minimum Switching Voltage | 24 V AC |
Limiting Continuous Current | 0.75 A |
Voltage drop at max. limiting continuous current | < 1 V AC |
Maximum Inrush Current | 30 A (10 ms) |
Output circuit | 2-conductor, floating |
Protective circuit | RCV circuit |
Leakage current | < 1 mA |
Phase angle cos phi min | 0.5 |
Max. load value | 4.5 A2s |
Input side
Connection Method | Spring-cage connection |
Stripping length | 8 mm |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 14 |
Output side
Connection Method | Spring-cage connection |
Stripping length | 8 mm |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 14 |
Signaling
Status display | LED |
Dimensions
Width | 6.2 mm |
Height | 80 mm |
Depth | 94 mm |
Material specifications
Color | green (RAL 6021) |
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | in rows with zero spacing |
Mounting Position | any |
Why Proax for Phoenix Contact 2980364?
Proax is an authorized distributor of Phoenix Contact 2980364 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 10 |
Recommended