
SKU
MPN
EMD-BL-C-10-PT
Weight
0.071 kg
Series EMD-BL-C
EMD-BL-C-10-PT - Monitoring relay
Monitoring relay for monitoring single-phase currents of 0 ... 5 A AC or 0 ... 10 A AC, overcurrent/undercurrent or window, 1 changeover contact, with Push-in connection
Technical Specifications
Product properties
Operating mode | 100% operating factor |
Mechanical service life | 15x 10⁶ cycles |
Insulation characteristics
Insulation | Basic insulation |
Insulation | Basic insulation |
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Service life electrical | 1x 105 cycles |
Mains type | 1-phase |
Rated Insulation Voltage | 300 V (Supply circuit) |
Rated Insulation Voltage | 250 V (Output circuit) |
Rated Insulation Voltage | 300 V (Measuring circuit) |
Rated surge voltage | 4 kV |
Supply
Supply Voltage | 230 V AC ±15 % |
Supply Voltage Range | 195.5 V AC ... 264.5 V AC |
Nominal Power Consumption | 5 VA (0.8 W) |
Input data
Input name | Measuring input |
Measured value | AC sine (48 Hz ... 63 Hz) |
Input current range | 0 A ... 5 A |
Input current range | 0 A ... 10 A |
Input current range | Configurable via rotary switches |
Overload capacity | 13 A AC |
Input resistance current input | 3 mΩ |
Frequency Range | 48 Hz ... 63 Hz |
Maximum temperature coefficient | ≤ 0.05 % |
Setting range for response delay | 0.1 s ... 10 s |
Min. setting range | 5 % ... 95 % (from IN) |
Max. setting range | 10 % ... 100 % (from IN) |
Function | Overcurrent |
Function | Undercurrent |
Function | Window |
Basic accuracy | ≤ 5 % (of the nominal value) |
Setting accuracy | ± 5 % (of the nominal value) |
Repeat accuracy | ≤ 2 % |
Recovery time | > 500 ms |
Switching
Contact switching type | 1 floating changeover contact |
Maximum Switching Voltage | 250 V AC (in acc. with IEC 60664-1) |
Interrupting rating (ohmic load) max. | 1250 VA (5 A / 250 V AC) |
Output fuse | 5 A (fast-blow) |
Connection data
Connection Method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 26 ... 14 |
Signaling
Status display | Yellow LED |
Operating voltage display | Green LED |
Error indication | Red LED |
Dimensions
Width | 17.5 mm |
Height | 89.5 mm |
Depth | 65.5 mm |
Material specifications
Color | gray (RAL 7042) |
Housing insulation material | Polyamide PA 6.6, self-extinguishing |
Ambient conditions
Degree of protection (Housing) | IP40 (Housing) |
Degree of protection (Connection terminal blocks) | IP20 (Connection terminal blocks) |
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Climatic class | 3K3 (in acc. with EN 60721) |
Permissible humidity (operation) | 15 % ... 85 % |
CE
Certificate | CE-compliant |
UL, USA/Canada
Identification | UL/C-UL Listed UL 508 |
EMC data
Low Voltage Directive | Conformance with Low Voltage Directive |
Noise immunity | EN 61000-6-2 |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-3 |
Standards and Regulations
Standards/regulations | DIN EN 60947-5-1 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
Mounting Position | any |
Why Proax for Phoenix Contact 2903522?
Proax is an authorized distributor of Phoenix Contact 2903522 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended