Official Distributor
SKU
MPN
ELR H5-ES-SC-230AC/500AC-0,6
Weight
0.271 kg
Series ELR-H
ELR H5-ES-SC-230AC/500AC-0,6 - Hybrid motor starter
Hybrid motor starter for reversing 3~ AC motors up to 550 V AC, with 230 V AC input, 0.6 A output current, and emergency stop function.
- 22.5 mm wide
- Safety level in accordance with IEC 61508-1: SIL 3, ISO 13849: PL e
- Reduction in wiring
- Long service life
- Space saving
- 3-phase loop bridges
- Low-wear switching
Technical Specifications
Product properties
Product family | CONTACTRON |
Operating mode | 100% operating factor |
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation | safe isolation |
Electrical properties
Number of phases | 3 |
Service life electrical | 3x 107 cycles |
Reversing frequency | ≤ 2 Hz |
Maximum power dissipation | 2.9 W |
Minimum power dissipation | 2.6 W |
Coordination type | 1 |
Air clearances and creepage distances between the power circuits
Rated Insulation Voltage | 500 V |
Rated surge voltage | 6 kV |
Supply
Rated control circuit supply voltage US | 230 V AC |
Control supply voltage range | 92 V AC ... 253 V AC |
Rated control supply current IS | 4 mA |
Mains frequency | 50/60 Hz |
Protective circuit | Surge protection |
Control
Rated actuating voltage UC | 230 V AC |
Triggering voltage range | 92 V AC ... 253 V AC |
Mains frequency | 50 Hz 60 Hz 50/60 Hz |
Switching threshold | 44 V AC (“0” signal) |
Switching threshold | 85 V AC (“1” signal) |
Switching level | < 5 V AC (For EMERGENCY STOP) |
Typical turn-off time | < 70 ms |
AC output
Rated operating voltage Ue | 500 V AC |
Operating voltage range | 42 V AC ... 550 V AC |
Rated operating current Ie | 0.6 A (AC-51) |
Rated operating current Ie | 0.6 A (AC-53a) |
Mains frequency | 50/60 Hz |
Load current range | 75 mA ... 600 mA (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
Cooling time | 20 min. (for auto reset) |
Leakage current | 0 mA |
Residual voltage | < 0.3 V |
Protective circuit | Surge protection |
Acknowledge output
Note | Confirmation 01: floating changeover contact |
Control circuits
Connection Method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Load circuit
Connection Method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Signaling
Status display | Yellow LED |
Operating voltage display | Green LED |
Error indication | Red LED |
Dimensions
Width | 22.5 mm |
Height | 107 mm |
Depth | 114 mm |
Material specifications
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -25 °C ... 70 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Safety Integrity Level (SIL, IEC 61508)
Identification | ≤ 3 |
Note | Safe shutdown |
Performance Level (ISO 13849)
Identification | e |
Note | Safe shutdown |
Category (ISO 13849)
Identification | ≤ 3 |
Note | Safe shutdown |
UL data
SCCR | 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
SCCR | 5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) |
FLA | 0.6 A (480 V) |
Standards/regulations
Standards/regulations | DIN EN 50178 |
Standards/regulations | EN 60947 |
Power station requirements
Standards/regulations | DWR 1300/ZXX01/DD/7080.8d |
Air clearances and creepage distances between the power circuits
Standards/regulations | DIN EN 50178 |
Mounting
Assembly instructions | Can be aligned with spacing = 20 mm |
Mounting Position | Vertical (horizontal DIN rail) |
Why Proax for Phoenix Contact 2900688?
Proax is an authorized distributor of Phoenix Contact 2900688 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- Démarreur moteur hybride comme alternative au circuit de protection contacteur-inverseur classique. Inverse les moteurs 3~ AC jusqu'à 3 A, offre une protection moteur et un arrêt d'urgence jusqu'à SIL 3 / PL e. Coupure de groupe, alimentation et extension de relais possibles via des connecteurs de bus sur rails DIN.