2908724
SKU
PHX2908724
MPN
F-MS 12/FM/120
Weight
0.125 kg
Series F-MS
F-MS 12/FM/120 - Type 2 surge arrester
Surge arrester type 2, consisting of base element with remote indicator contact and protective plug with N-PE total current spark gap for mounting on NS 35/7.5, housing width: 17.5 mm (1 Div.)
Technical Specifications
Product properties
| Product family | VALVETRAB MS |
| IEC test classification | II |
| IEC test classification | T2 |
| EN type | T2 |
| IEC power supply system | TN |
| IEC power supply system | TT |
| Type | DIN rail module, two-section, divisible |
| Number of Positions | 1 |
| Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Nominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling
| Connection name | Remote fault indicator contact |
| Switching function | Changeover contact |
| Operating Voltage | 5 V AC ... 250 V AC |
| Operating Voltage | 30 V DC |
| Operating current | 5 mA AC ... 1 A AC |
| Operating current | 1 A DC |
Connection data
| Connection Method | Screw connection |
| Screw thread | M5 |
| Tightening torque | 3 Nm (1.5 mm² ... 16 mm²) |
| Tightening torque | 4.5 Nm (25 mm² ... 35 mm²) |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section rigid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
| Connection Method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 16 mm² |
Remote fault indicator contact
| Connection Method | Plug-in/screw connection via COMBICON |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Dimensions
| Width | 17.6 mm |
| Height | 96.8 mm |
| Depth | 65.7 mm (incl. DIN rail 7.5 mm) |
| Horizontal pitch | 1 Div. |
Material specifications
| Flammability rating according to UL 94 | V-0 |
| CTI value of material | 600 |
| Insulating material | PA 6.6/PBT |
| Material group | I |
| Housing Material | PA 6.6 |
| Housing Material | PBT |
Protective circuit
| Mode of protection | N-PE |
| Direction of action | N-PE |
| Nominal voltage UN | 240/415 V AC (TN - only N-PE) |
| Nominal voltage UN | 240/415 V AC (TT - only N-PE) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 260 V AC |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 5 µA |
| Standby power consumption PC | ≤ 1.50 mVA |
| Nominal discharge current In (8/20) µs | 20 kA |
| Maximum discharge current Imax (8/20) µs | 40 kA |
| Follow current interrupt rating Ifi | 100 A |
| Voltage protection level Up | ≤ 1.5 kV |
| Residual voltage Ures | ≤ 0.4 kV (at In) |
| Residual voltage Ures | ≤ 0.25 kV (at 10 kA) |
| Residual voltage Ures | ≤ 0.15 kV (at 5 kA) |
| Residual voltage Ures | ≤ 0.1 kV (at 3 kA) |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
| TOV behavior at UT | 1200 V AC (200 ms / withstand mode) |
| Response time tA | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 80 A (gG) |
Additional technical data
| Maximum continuous voltage UC | 305 V AC |
Ambient conditions
| Degree of Protection | IP20 (only when all terminal points are used) |
| Ambient Temperature (Operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (Operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
UL specifications
| Maximum continuous operating voltage MCOV (N-G) | 260 V AC |
| Nominal discharge current In (N-G) | 20 kA |
| Mode of protection | N-G |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (N-G) | 1490 V |
| SPD Type | 4CA |
UL indicator/remote signaling
| Operating Voltage | 125 V AC |
| AC operating current | 1 A AC |
UL connection data
| Tightening torque | 30 lbf-in. |
| Conductor cross section AWG | 10 ... 2 |
Standards and Regulations
| Standards/specifications | IEC 61643-11 |
| Note | 2011 |
| Standards/specifications | EN 61643-11 |
| Note | 2012 |
Mounting
| Mounting Type | DIN rail: 35 mm |
Why Proax for Phoenix Contact 2908724?
Proax is an authorized distributor of Phoenix Contact 2908724 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 120 |
Recommended