Clearance
2869913
SKU
PHX2869913
MPN
IB IL EX-IS TEMP 4 RTD/TC-PAC
Weight
0.301 kg
This product is Not Cancellable/Not Returnable
IB IL EX-IS TEMP 4 RTD/TC-PAC - Inline terminal
Inline intrinsically safe temperature terminal, 4 configurable input channels, complete with accessories
- Fieldbus-independent diagnostics using FDT/DTM technology
- Module-based electrical isolation
- RTD inputs: Pt 100, etc.
- 2- or 3-conductor RTD sensors
- Single-channel diagnostics
- 4 configurable I/O channels
- TC inputs: J, K, E, etc.
Technical Specifications
Dimensions
| Width | 48.8 mm |
| Height | 136.8 mm |
| Depth | 71.5 mm |
Utilization restriction
| CCCex note | Use in potentially explosive areas is not permitted in China. |
Material specifications
| Color | blue |
Inline local bus
| Connection Method | Inline data jumper |
| Transmission Speed | 500 kbps |
Analog:
| Voltage input signal | -15 mV ... 85 mV |
Analog
| Number of Inputs | 4 |
| Connection Method | Inline shield connector |
| Connection technology | 2-, 3-conductor |
| A/D converter resolution | 16 bit (15 bit + sign bit) |
| Sensor types (RTD) that can be used | 2 and 3-wire, Pt, Ni (DIN 100, 200, 500, 1000) |
| Sensor types that can be used (TC) | J, K, E, R, S, T |
| Data formats | IB IL, S7-compatible |
| Linear resistance measuring range | 0 Ω ... 800 Ω |
| Linear resistance measuring range | 0 Ω ... 5000 Ω |
| Protective circuit | Polarity protection, surge protection |
Product properties
| Type | modular |
| Type | Inline |
Potentials
| Power consumption | 1.5 W (all channels) |
Potentials: Communications power (UL)
| Supply Voltage | 5 V DC (via voltage jumper) |
| Current draw | max. 50 mA |
Potentials:
| Supply Voltage | 28 V DC |
| Current draw | max. 80 mA |
Conductor connection
| Connection Method | Spring-cage connection |
| Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
| Connection Method | Spring-cage connection |
| Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
| Stripping length | 8 mm |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -25 °C ... 60 °C |
| Degree of Protection | IP20 |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
Ex data
| ATEX | II 3(1)GD Ex nA [ia Ga Da] IIC T4 Gc Sira 09ATEX2339X |
| IECEx | Ex nA [ia Ga Da] IIC T4 Gc IECEx SIR 10.0033X |
| FM approval | Class I, Div. 2, Groups A, B, C, D |
| UL, USA / Canada | Class I, Div. 2, Groups A, B, C, D |
Mounting
| Mounting Type | DIN rail mounting |
Safety data
| Max. output voltage Uo | max. 5.88 V DC |
| Max. output current Io | max. 95 mA |
| Max. output power Po | max. 139 mW |
| IIC (A, B): Max. external inductivity Lo / Max. external capacitance Co | 0.984 mH / 42 µF |
| IIB, [IIIC, IIIB] (C, E, F, G): Max. external inductivity Lo / Max. external capacitance Co | 2.9 mH / 999 µF |
| IIA (D): Max. external inductivity Lo / Max. external capacitance Co | 7.8 mH / 999 µF |
Why Proax for Phoenix Contact 2869913?
Proax is an authorized distributor of Phoenix Contact 2869913 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |