PLC-ASC-PT100-IN - Analog module
Pt 100/Pt 1000 temperature transducer for PLC logic logic modules (Generation 2 only), single-channel, signal type (Pt 100, Pt 1000) configurable via DIP switch, screw connection
Technical Specifications
Notes
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Product properties
Product family | PLC logic |
Operating mode | 100% operating factor |
Insulation characteristics
Insulation | Basic insulation |
Insulation characteristics: Air clearances and creepage distances
Insulation | Basic insulation |
Overvoltage category | III |
Pollution degree | 2 |
Air clearances and creepage distances
Rated Insulation Voltage | 50 V |
Rated surge voltage | 0.5 kV |
Supply
Rated control circuit supply voltage US | 24 V DC |
Rated control supply voltage range with reference to US | 0.8 ... 1.1 |
Rated control supply current IS | 14 mA |
Protective circuit | Reverse polarity protection |
Protective circuit | Surge protection |
Analog input resistance
Sensor types (RTD) that can be used | Pt 100 (IEC 60751, α = 0,00385) |
Number of Inputs | 1 |
Connection technology | 2-conductor |
Sensor input current | 900 µA |
Temperature measuring range | -50 °C ... 200 °C |
Maximum temperature coefficient | 0.01 %/K |
Maximum transmission error | 1 % |
Surge voltage protection | > 33 V |
Resolution | 10 bit (scaled to 0 to 1000) |
Sensor types (RTD) that can be used | Pt 1000 (IEC 60751, α = 0.00385) |
Number of Inputs | 1 |
Connection technology | 2-conductor |
Sensor input current | 900 µA |
Temperature measuring range | -50 °C ... 200 °C |
Maximum temperature coefficient | 0.01 %/K |
Maximum transmission error | 1 % |
Surge voltage protection | > 33 V |
Resolution | 10 bit (scaled to 0 to 1000) |
Digital
Output name | Digital output |
Switching voltage range | 5 V DC ... 30 V DC |
Switching current | ≤ 3 mA |
Connection data
Connection Method | Screw connection |
Stripping length | 8 mm |
Screw thread | M3 |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² (Single ferrule) |
Conductor cross section flexible | 2x 0.5 mm² ... 1.5 mm² (TWIN ferrule) |
Conductor cross section AWG | 26 ... 14 |
Tightening torque | 0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing)) |
Signaling
Operating voltage display | Green LED |
Error indication | Red LED |
Dimensions
Width | 6.2 mm |
Height | 80 mm |
Depth | 95 mm |
Material specifications
Color | gray (RAL 7042) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -20 °C ... 50 °C |
Ambient temperature (storage/transport) | -20 °C ... 70 °C |
CE
Certificate | CE-compliant |
UL, USA/Canada
Identification | UL 508 Listed |
Air clearances and creepage distances
Standards/regulations | DIN EN 50178 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | in rows with zero spacing |
Mounting Position | any |
Why Proax for Phoenix Contact 2906918?
Proax is an authorized distributor of Phoenix Contact 2906918 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 1079392 - 14 mm PLC basic terminal block for high continuous currents, resistant to interference voltages of up to 190 V AC, thanks to defined activation and deactivation thresholds with screw connection, without relay, for mounting on DIN rail NS 35/7,5, 1 changeover contact, input voltage of 230 V AC