CADEN
Cart

2906450

Official Distributor

By Phoenix Contact

SKU
PHX2906450
MPN
PLT-T3-IT-230-FM
Weight
0.086 kg
This product is Not Cancellable/Not Returnable
Series PLT-T3

PLT-T3-IT-230-FM - Type 3 surge protection device

Surge protection type 3, as device protection for termination devices in IT systems, error indication and remote indicator contact. Design: 230 V AC

Technical Specifications

Product properties

IEC power supply systemIT
TypeBase element, DIN rail mounting
Number of Positions2
Surge protection fault messageOptical, remote indicator contact

Insulation characteristics

Overvoltage categoryIII
Pollution degree2
IEC test classificationIII
IEC test classificationT3
EN typeT3
Number of PortsOne

Indicator/remote signaling

Connection nameRemote fault indicator contact
Switching functionN/C contact
Operating Voltage250 V AC
Operating Voltage125 V DC (200 mA DC)
Operating current3 A AC
Operating current1 A DC (30 V DC)

Connection data

Connection MethodScrew connection
Screw threadM3
Tightening torque0.8 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions

Width17.7 mm
Height90 mm
Depth65.5 mm
Horizontal pitch1 Div.

Material specifications

Colorblack (RAL 9005)
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA 6.6
Housing MaterialPA 6.6

Protective circuit

Mode of protectionL-L
Mode of protectionL-PE
Direction of action1L-N & N-PE
Nominal voltage UN230 V AC (IT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-L)275 V AC
Maximum continuous operating voltage UC (L-N)275 V AC
Maximum continuous operating voltage UC (L-PE)440 V AC
Rated load current IL16 A (60 °C)
Residual current IPE≤ 1 µA
Standby power consumption PC≤ 340.00 mVA
Reference test voltage UREF255.00 V AC
Nominal discharge current In (8/20) µs3 kA
Maximum discharge current Imax (8/20) µs8 kA
Combination wave UOC6 kV
Voltage protection level Up (L-L)≤ 1.2 kV
Voltage protection level Up (L-N)≤ 1.2 kV
Voltage protection level Up (L-PE)≤ 1.5 kV
Residual voltage at Iamax, (L-PE)≤ 1 kV (at 1 kA)
Residual voltage at Iamax, (L-PE)≤ 1.5 kV (at UOC)
TOV behavior at UT (L-PE)440 V AC (120 min / withstand mode)
TOV behavior at UT (L-PE)1455 V AC (200 ms / safe failure mode)
Response time tA (L-N)≤ 25 ns
Response time tA (L-PE)≤ 100 ns
Max. required back-up fuse16 A (MCB B)
Short-circuit current rating ISCCR1.5 kA AC
Max. backup fuse with branch wiring16 A (MCB B)

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 70 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and Regulations

Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2012

Mounting

Mounting TypeDIN rail: 35 mm
Accessories

Why Proax for Phoenix Contact 2906450?

Proax is an authorized distributor of Phoenix Contact 2906450 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size1
Recommended

CAD$248.11

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability