Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
2868606
Weight
0.078 kg

STEP-DIODE/5-24DC/2X5/1X10 - Redundancy module

Redundancy module, 5 ... 24 V DC, 2x 5 A, 1x 10 A

  • Flexible mounting by simply snapping onto the DIN rail
  • Save energy
  • Rugged design
  • Permanent monitoring of redundancy
  • Consistent redundancy up to the load
Technical Specifications

DC operation

Nominal input voltage range5 V DC ... 24 V DC
Input voltage range4.5 V DC ... 30 V DC
Voltage type of supply voltageDC
Reverse polarity protection< yes60 V
Nominal input current (IN)2x 5 A (-25 °C ... 55 °C)
Nominal input current (IN)1x 10 A (-25 °C ... 55 °C)
Nominal input current (IN)2x 5 A (-25 °C ... 55 °C)
Nominal input current (IN)1x 10 A (-25 °C ... 55 °C)
Transient surge protectionTransil diode
Voltage drop, input/output0.5 V

Output data

Efficiency> 97 %
Efficiency> 97 %
Nominal Output Voltage24 V DC
Setting range of the output voltage (USet)5 V DC ... 24 V DC
Nominal output current (IN)10 A (Increasing power)
Nominal output current (IN)5 A (Redundancy)
Derating55 °C ... 70 °C (2.5 %/K)
Power loss nominal load max.2.5 W (IOUT = 5 A)
Connection in seriesNo
Derating60 °C ... 70 °C (2.5 %/K)

Input

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length6.5 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Output

Connection MethodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length6.5 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Electrical properties

Insulation voltage input, output / housing500 V DC

Product properties

Product familySTEP DIODE
MTBF (IEC 61709, SN 29500)> 25822000 h (40 °C)
LEDNo

Insulation characteristics

Protection classIII
Degree of pollution2

Dimensions

Width18 mm
Height90 mm
Depth61 mm
Horizontal pitch1 Div.

Installation dimensions

Installation distance right/left0 mm / 0 mm
Installation distance top/bottom30 mm / 30 mm

Mounting

Mounting TypeDIN rail: 35 mm
Assembly instructionsalignable: 0 mm horizontally, 30 mm vertically
Mounting Positionhorizontal DIN rail NS 35, EN 60715

Material specifications

Housing MaterialMetal
Housing MaterialPlastic

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (Operation)15 Hz ... 150 Hz, 2.3g, 90 min.

Standards and Regulations

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard - Electrical safetyIEC 62368-1 (SELV)

Approvals

UL approvalsUL/C-UL listed UL 508
UL approvalsUL/C-UL Recognized UL 60950-1

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge4 kV (Test Level 2)
Discharge in air8 kV (Test Level 3)
CommentsCriterion B

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range1 GHz ... 2 GHz
Test field strength10 V/m (Test Level 3)
Frequency Range2 GHz ... 3 GHz
Test field strength10 V/m (Test Level 3)
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input2 kV (Test Level 3 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
CommentsCriterion B

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input0.5 kV (Test Level 1 - asymmetrical)
Input0.5 kV (Test Level 1 - symmetrical)
Output0.5 kV (Test Level 1 - asymmetrical)
Output0.5 kV (Test Level 1 - symmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
I/O/Sasymmetrical
Frequency Range150 kHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Voltage dips

Standards/regulationsEN 61000-4-11

Emitted interference

Standards/regulationsEN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.

Why Proax for Phoenix Contact STEP-DIODE/5-24DC/2X5/1X10?

Proax is an authorized distributor of Phoenix Contact STEP-DIODE/5-24DC/2X5/1X10 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesSTEPDIODE524DC2X51X10
Pack Size1
Recommended