Official Distributor
SKU
Weight
0.29 kg
Series ELR-H
ELR H3-IES-PT/500AC-9-IFS - Hybrid motor starter
Networkable hybrid motor starter for starting 3~ AC motors up to 500 V AC, output current: 9 A, emergency stop function, adjustable overload shutdown, and Push-in connection, DIN rail connector provided.
- 22.5 mm wide
- Safety level in accordance with IEC 61508-1: SIL 3, ISO 13849: PL e
- Reduction in wiring
- Space saving
- Long service life
- 3-phase loop bridges
- Adjustable current for bimetal function
- Low-wear switching
Technical Specifications
Product properties
Product family | CONTACTRON |
Operating mode | 100% operating factor |
Electrical properties
Number of phases | 3 |
Motor starter type | Direct starter |
Maximum power dissipation for nominal condition | 12 W |
Switching frequency | ≤ 2 Hz (Load-dependent) |
Maximum power dissipation | 7 W |
Minimum power dissipation | 0.88 W |
Coordination type | 1 |
Supply
Rated control circuit supply voltage US | 24 V DC |
Control supply voltage range | 19.2 V DC ... 30 V DC |
Rated control supply current IS | 60 mA |
Protective circuit | Surge protection |
Protective circuit | Reverse polarity protection; Parallel polarity protection diode |
Insulation characteristics
Rated Insulation Voltage | 550 V |
Rated surge voltage | 6 kV |
Overvoltage category | III |
Degree of pollution | 2 |
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit | Safe isolation (IEC 60947-1) |
Isolation characteristics between the control input and control supply voltage to auxiliary circuit | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
Emergency tripping
Operate threshold | > 60 A |
Response time | < 0.5 s |
Control
Input name | Enable input |
Note | The enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3 ms duration),unblanking pulses of max. 4 ms are tolerated without adversely affecting the safety function. |
Rated actuating voltage UC | 24 V DC |
Triggering voltage range | 19.2 V DC ... 30 V DC |
Rated actuating current IC | 7 mA |
Switching threshold | 9.6 V (“0” signal) |
Switching threshold | 19.2 V (“1” signal) |
Switching level | < 5 V DC (For EMERGENCY STOP) |
Typical turn-off time | < 30 ms |
Protective circuit | Reverse polarity protection |
AC output
Rated operating voltage Ue | 500 V AC |
Operating voltage range | 42 V AC ... 550 V AC |
Rated operating current Ie | 9 A (AC-51) |
Rated operating current Ie | 7 A (AC-53a) |
Mains frequency | 50/60 Hz |
Load current range | 1.5 A ... 9 A (see to derating) |
Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
Cooling time | 20 min. (for auto reset) |
Leakage current | 0 mA |
Protective circuit | Surge protection; Varistor |
Control circuits
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Load circuit
Connection Method | Push-in connection |
Stripping length | 10 mm |
Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 14 |
Signaling
Status display | Yellow LED |
Operating voltage display | Green LED |
Error indication | Red LED |
Dimensions
Width | 22.5 mm |
Height | 107.5 mm |
Depth | 114 mm |
Material specifications
Flammability rating according to UL 94 | V0 (Housing) |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -5 °C ... 60 °C (observe derating) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m |
UKCA
Certificate | UKCA-compliant |
ATEX
Identification | II (2) G [Ex eb] [Ex db] [Ex pxb] |
Identification | II (2) D [Ex tb] [Ex pb] |
Certificate | PTB 15 ATEX 3000 |
UL approval
Certificate | NLDX.E228652 |
Certificate | NRNT.E172140 |
Safety Integrity Level (SIL, IEC 61508)
Identification | ≤ 3 |
Note | Safe shutdown |
Identification | 2 |
Note | Motor protection |
Performance Level (ISO 13849)
Identification | e |
Note | Safe shutdown |
Category (ISO 13849)
Identification | ≤ 3 |
Note | Safe shutdown |
UL data
SCCR | 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
SCCR | 5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) |
FLA | 7.6 A (480 V AC) |
Group installation | 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded) |
Group installation | 30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded) |
Category code | NLDX / NRNT |
Horsepower ratings | 2 hp (208 V AC) |
Horsepower ratings | 2 hp (230 V AC) |
Horsepower ratings | 2 hp (240 V AC) |
Horsepower ratings | 5 hp (480 V AC) |
Standards/regulations
Standards/regulations | IEC 60947-1 |
Standards/regulations | EN 60947-4-2 |
Standards/regulations | IEC 61508 |
Standards/regulations | ISO 13849 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | alignable, for spacing see derating |
Mounting Position | vertical (horizontal DIN rail, motor output below) |
Accessories
- 2201937 - DIN rail connector, color: gray, nominal current: 8 A (parallel contacts), rated voltage (III/2): 125 V, number of positions: 5, product range: TBUS5-22,5.., pitch: 3.81 mm, mounting: DIN rail mounting, locking: without, mounting: without, type of packaging: packed in cardboard, Item with gold-plated contacts, bus connectors for connecting with electronics housings, 5 parallel contacts
Why Proax for Phoenix Contact 2905143?
Proax is an authorized distributor of Phoenix Contact 2905143 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended