IB IL SAFE 2-ECO - Safety module
Inline, Safety module, Functional safety, Digital inputs: 4 (for 2 sensor circuits (1- or 2-channel, non-equivalent/equivalent)), Enabling current path: 1 (internal, 2-channel enabling current path), N/O contact, for safety-related shutdown of the segment voltage by means of potential routing, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
- Various safety functions with one module
- 2 sensor circuits
- Several modules can be cascaded
- Diagnostic and status indicators
- Can be used in different bus systems
Dimensions
Width | 24.4 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Inline local bus
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
Module
ID code (dec.) | 190 |
ID code (hex) | BE |
Length code (hex) | 41 |
Length code (dec) | 65 |
Process data channel | 4 bit |
Input address area | 4 bit |
Output address area | 0 bit |
Register length | 4 bit |
Required parameter data | 1 Byte |
Required configuration data | 4 Byte |
Digital:
Input name | Digital inputs |
Description of the input | IEC 61131-2 type 3 |
Number of Inputs | 4 (for 2 sensor circuits (1- or 2-channel, non-equivalent/equivalent)) |
Connection Method | Spring-cage connection |
Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off; at inputs 1.2, 1.3, 3.2, 3.3) |
Input voltage range "0" signal | 0 V DC ... 5 V DC (at inputs 2.3, 4.3) |
Input voltage range "1" signal | 11 V DC ... 30 V DC (at inputs 1.2, 1.3, 2.3, 3.2, 3.3, 4.3) |
Input voltage range "1" signal | 19.2 V DC ... 30 V DC (at inputs 3.4, 4.4) |
Protective circuit | Surge voltage; Suppressor diode |
Protective circuit | Reverse polarity protection |
Relay
Number of Outputs | 1 (internal, 2-channel enabling current path) |
Contact switching type | N/O contact |
Switching current | min. 3 mA |
Switching current | min. 6 A (30 V DC) |
Switching capacity | min. 60 mW |
Min. switching current | min. |
Max. switching current | min. |
Limiting Continuous Current | 6 A (observe derating) |
Mechanical service life | 106 cycles |
Output fuse | 6 A gL/gG (See “Application examples” section) |
Product properties
Product family | Inline |
Application | Functional safety |
Type | modular |
Mounting Position | vertical or horizontal |
Scope of delivery | including Inline connectors and marking fields |
Operating mode | Process data operation with 4 bits |
Operating mode | Process data operation with 4 bits |
Special Properties | for safety-related shutdown of the segment voltage by means of potential routing |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 (in accordance with EN 50178) |
Times
Typical response time | < 100 ms (manual, monitored start) |
Typical response time | < 150 ms (automatic start) |
Typical release time | < 30 ms (when actuation is via the sensor circuit) |
Restart time | < 1 s (Boot time) |
Recovery time | < 500 ms |
Electrical properties
Maximum power dissipation for nominal condition | 4.7 W (at UM = 30 V, IL² = 36 A²) |
Potentials
Power consumption | typ. 1.9 W (at UM) |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC |
Current draw | max. 35 mA |
Potentials: Main circuit supply (UM)
Supply Voltage | 24 V DC -20 % / +15 % |
Current draw | typ. 70 mA |
Supply: Module electronics
Supply Voltage | 24 V DC (via voltage jumper) |
Supply Voltage Range | 19.2 V DC ... 30 V DC |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | 0 °C ... 55 °C (observe derating) |
Degree of Protection | IP20 |
Degree of protection at installation location | min. IP54 |
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Air clearances and creepage distances
Air clearances and creepage distances | EN 50178 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | See derating curve |
Mounting Position | vertical or horizontal |
Why Proax for Phoenix Contact IB IL SAFE 2-ECO?