Official Distributor
SKU
MPN
FLKMIL-50/4FLK14/EZ-DR/1000/CS
Weight
1.549 kg
Series FLKMIL
FLKMIL-50/4FLK14/EZ-DR/1000/CS - Cable
Assembled shielded round cable; controller: Yokogawa CS3000 CentumVP (ADV561, ADV161); connection 1: IDC/FLK socket strip (1x 50-position); connection 2: IDC/FLK socket strip (4x 14-position); cable length: 10 m
Technical Specifications
Ambient conditions
Degree of Protection | IP00 |
Degree of protection (Installation location) | ≥ IP54 (Installation location) |
Ambient Temperature (Operation) | -40 °C ... 70 °C (fixed installation) |
Ambient Temperature (Operation) | -10 °C ... 70 °C (flexible installation) |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m |
Electrical properties
Operating voltage (DC) | ≤ 30 V DC |
Nominal operating mode | 100% operating factor |
Current (Per path) | ≤ 500 mA (uncoiled) |
Supported controller YOKOGAWA CS3000 CentumVP
Suitable I/O card | ADV161 |
Suitable I/O card | ADV561 |
Supported controller YOKOGAWA STARDOM
Suitable I/O card | NFDV161 |
Suitable I/O card | NFDV561 |
Cable/line
Cable Length | 10 m |
40X0.14 [PVC]
UL AWM style | 2464/1061 |
Number of Positions | 40 |
Shielded | yes |
Cable Type | 40X0.14 [PVC] |
Conductor type | Assembled shielded round cable |
Conductor structure signal line | 7x 0.16 mm |
AWG Signal Line | 26 |
Conductor Cross Section | 40x 0.14 mm² |
Wire diameter incl. insulation | 1 mm ±0.03 mm |
External Cable Diameter | 9.80 mm ±0.3 mm |
Outer sheath, material | Semi-rigid PVC |
External sheath, color | gray |
Conductor material | Tin-plated Cu litz wires |
Cable resistance | ≤ 145 Ω/km (at 20 °C) |
Insulation resistance | ≥ 20 MΩ*km (20 °C) |
Smallest bending radius, fixed installation | 101 mm |
Smallest bending radius, movable installation | 182 mm |
Max. bending cycles | 5000 (at a radius of ≥ 18x outside diameter) |
Halogen-free | no |
Flame resistance | IEC 60332-1-2 (raw cable) |
Flame resistance | VDE 0842, Part 332-1-2 (raw cable) |
Flame resistance | IEC 60332-3-22 (raw cable) |
Flame resistance | UL VW-1 |
Flame resistance | CSA FT-1 |
Resistance to Oil | can withstand occasional splashes (raw cable) |
Cable Type | Splitting cable for four modules |
Connection 1
Connection in acc. with standard | based on IEC 60603-13 |
Connection Method | IDC/FLK socket strip |
Number of Connections | 1 |
Number of Positions | 50 |
Insertion/withdrawal cycles | > 50 |
Pitch | 2.54 mm |
Connection 2
Connection in acc. with standard | based on IEC 60603-13 |
Connection Method | IDC/FLK socket strip |
Number of Connections | 4 |
Number of Positions | 14 |
Insertion/withdrawal cycles | > 50 |
Pitch | 2.54 mm |
Notes
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Why Proax for Phoenix Contact 2306980?
Proax is an authorized distributor of Phoenix Contact 2306980 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended