Official Distributor
SKU
MPN
IBS IL 24 BK-T/U-PAC
Weight
0.264 kg
This product is Not Cancellable/Not Returnable
Series IBS-IL
IBS IL 24 BK-T/U-PAC - Bus coupler
Inline, Bus coupler, INTERBUS, Inline shield connector, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
- Remote bus connections using copper technology
- An Inline station can be supplied with all of the required 24 V voltages for low-level signals
- Automatic configuration of the outgoing interface as a remote bus or local bus interface
- Up to 15 connected terminals with remote bus branch supported
- Electrical isolation of the remote bus segments
Technical Specifications
Dimensions
Width | 48.8 mm |
Height | 135 mm |
Depth | 71.5 mm |
Utilization restriction
CCCex note | Use in potentially explosive areas is not permitted in China. |
INTERBUS
Number of interfaces | 2 |
Connection Method | Inline shield connector |
Transmission Speed | 500 kbps |
Transmission physics | Copper |
Number of interfaces | 1 |
Connection Method | Inline data jumper |
Transmission Speed | 500 kbps |
System limits
Number of supported devices | max. 63 |
Number of local bus devices that can be connected | max. 63 |
Number of devices with parameter channel | max. 62 |
Number of supported branch terminals with remote bus branch | max. 15 |
Module
ID code (dec.) | 04 |
ID code (hex) | 04 |
Length code (hex) | 00 |
Length code (dec) | 00 |
Process data channel | 0 bit |
Input address area | 0 bit |
Output address area | 0 bit |
Register length | 0 bit |
Product properties
Product family | Inline |
Type | modular |
Scope of delivery | including Inline connectors and marking fields |
Diagnostics messages | I/O error yes, if the segment voltage US is not present |
Insulation characteristics
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Electrical properties
Maximum power dissipation for nominal condition | 30 W |
Protective circuit | Short-circuit protection of the communications power; electronic |
Protective circuit | Short-circuit protection of the analog supply; electronic |
Protective circuit | Surge protection (segment supply, main supply, bus coupler supply); Input protective diodes (can be destroyed by permanent overload)Pulse loads up to 1500 W are short circuited by the input protective diode. |
Protective circuit | Protection against polarity reversal (segment supply/main supply); Parallel diodes for protection against polarity reversal; in the event of an error the high current flowing through the diodes causes the fuse connected upstream to blow. |
Protective circuit | Protection against polarity reversal (bus coupler supply); Serial diode in the lead path of the power supply unit; in the event of an error only a low current flows. In the event of an error, no fuse trips within the external power supply unit. |
Supply Voltage | 24 V DC (via Inline connector) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 1.25 A (with max. number of connected I/O terminal blocks) |
Current draw | typ. 100 mA (without connected I/O terminal blocks) |
Potentials: Communications power (UL)
Supply Voltage | 7.5 V DC |
Potentials: Supply of analog modules (UANA)
Supply Voltage | 24 V DC |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Potentials: Main circuit supply (UM)
Supply Voltage | 24 V DC (via Inline connector) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Potentials: Segment circuit supply (US)
Supply Voltage | 24 V DC (via Inline connector) |
Supply Voltage Range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply, incoming remote bus / 5 V supply outgoing remote bus | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply incoming remote bus / 7.5 V communications power, 24 V analog supply, 24 V bus coupler supply | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply, incoming remote bus / 24 V main supply, 24 V segment supply | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply incoming remote bus / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply outgoing remote bus / I/O (UM, US) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply outgoing remote bus / communications power (UBK, UL, UANA) | 500 V AC, 50 Hz, 1 min. |
Test voltage: 5 V supply outgoing remote bus / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: Communications power (UBK, UL, UANA) / functional ground | 500 V AC, 50 Hz, 1 min. |
Test voltage: Communications power (UBK, UL, UANA) / I/O (UM, US) | 500 V AC, 50 Hz, 1 min. |
Test voltage: I/O (UM, US) / functional ground | 500 V AC, 50 Hz, 1 min. |
Connection technology
Connection name | Inline connector |
Conductor connection
Connection Method | Spring-cage connection |
Conductor cross section rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector
Connection Method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 55 °C |
Degree of Protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | DIN rail mounting |
Accessories
Why Proax for Phoenix Contact 2861580?
Proax is an authorized distributor of Phoenix Contact 2861580 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 2742586 - Inline, Bus coupler, INTERBUS, Inline shield connector, Digital inputs: 16, 24 V DC, connection technology: 3-conductor, Digital outputs: 16, 24 V DC, 500 mA, connection technology: 3-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields