VAL-MS 230-UD-ST - Type 2 surge protection plug

Surge protection connector type 2 with high-capacity varistor for VAL-MS base element, thermal monitoring, visual fault warning. Design: 230 V AC

Technical Specifications

Product properties

Product familyVALVETRAB MS
IEC test classificationII
IEC test classificationT2
EN typeT2
IEC power supply systemTN
IEC power supply systemTT
TypeDIN rail module, two-section, divisible
Number of Positions1
Surge protection fault messageoptical
Arrester can be tested with CHECKMASTER from software version:From SW rev. 1.10

Insulation characteristics

Overvoltage categoryIII
Pollution degree2

Electrical properties

Nominal frequency fN50 Hz (60 Hz)

Connection data

Connection Methodpluggable

Dimensions

Width17.5 mm
Height52.4 mm
Depth55.3 mm
Horizontal pitch1 Div.

Material specifications

Colorblack (RAL 9005)
Flammability rating according to UL 94V-0
CTI value of material600
Insulating materialPA 6.6
Material groupI
Housing MaterialPA 6.6

Protective circuit

Mode of protectionL-PEN
Mode of protectionL-N
Direction of action1L-N/PE
Nominal voltage UN240/415 V AC (TN)
Nominal voltage UN240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC275 V AC
Residual current IPE≤ 0.45 mA
Standby power consumption PC≤ 120.00 mVA
Nominal discharge current In (8/20) µs20 kA
Maximum discharge current Imax (8/20) µs40 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 1.35 kV
Residual voltage Ures≤ 1.35 kV (at In)
Residual voltage Ures≤ 1.1 kV (at 10 kA)
Residual voltage Ures≤ 1 kV (at 5 kA)
Residual voltage Ures≤ 0.9 kV (at 3 kA)
TOV behavior at UT335 V AC (5 s / withstand mode)
TOV behavior at UT440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiring125 A (gG)

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (Operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

UL specifications

Maximum continuous operating voltage MCOV (L-N)275 V AC
Nominal discharge current In (L-N)20 kA
Mode of protectionL-N
Nominal Voltage230 V AC
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)1910 V
SPD Type4CA

Air clearances and creepage distances

Standards/regulationsDIN VDE 0110-1 / IEC 60664-1 / VDE 0675-6
Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2012

Mounting

Mounting Typeon base element
Accessories

Why Proax for Phoenix Contact 2858962?

Proax is an authorized distributor of Phoenix Contact 2858962 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability