Official Distributor
SKU
MPN
VAL-MS 350VF
Weight
0.131 kg
This product is Not Cancellable/Not Returnable
Series VAL-MS
VAL-MS 350VF - Type 2 surge arrester
Surge voltage arrester consisting of base element with protective plug with a connection in series with a varistor and a gas-filled spark gap, for mounting on NS 35/7.5, nominal voltage: 230 V AC, 1-channel
- Quality proven millions of times over in the widest range of applications
- Rapid installation with bridges, thanks to industry-standard overall width of 1 HP
- Easy testing and insulation measurement, thanks to pluggable protection modules
- Suitable for use in insulation-monitored systems due to combination of varistor and gas discharge tube free of leakage current
- Can be used in applications with increased insulation strength, e.g., railway technology
Technical Specifications
General
Note | Usable in all low-voltage systems between L-N or L-PEN.Only usable in IT Systems between L-PE, if the exposed-conductive-parts (bodies) of the equipment of the low-voltage installation is connected to the earthing arrangement of the transformer substation. (interconnected earthing arrangement of the HV-transformer substation with the bodies of the LV-installation. RE = RA accordance to IEC 60364-4-442 / VDE 0100-442 Fig. 44D / Example a) |
Product properties
Product family | VALVETRAB MS |
IEC test classification | II |
IEC test classification | T2 |
EN type | T2 |
IEC power supply system | TN |
IEC power supply system | TT |
IEC power supply system | IT |
Type | DIN rail module, two-section, divisible |
Number of Positions | 1 |
Surge protection fault message | optical |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal frequency fN | 50 Hz (60 Hz) |
Connection data
Connection Method | Screw connection |
Screw thread | M5 |
Tightening torque | 3 Nm (1.5 mm² ... 16 mm²) |
Tightening torque | 4.5 Nm (25 mm² ... 35 mm²) |
Stripping length | 16 mm |
Conductor cross section flexible | 1.5 mm² ... 25 mm² |
Conductor cross section rigid | 1.5 mm² ... 35 mm² |
Conductor cross section AWG | 15 ... 2 |
Connection Method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 16 mm² |
Dimensions
Width | 17.6 mm |
Height | 89.8 mm |
Depth | 65.7 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 1 Div. |
Material specifications
Color | black (RAL 9005) |
Flammability rating according to UL 94 | V-0 |
CTI value of material | 600 |
Insulating material | PA 6.6/PBT |
Material group | I |
Housing Material | PA 6.6 |
Housing Material | PBT |
Protective circuit
Mode of protection | L-N |
Mode of protection | L-PE |
Mode of protection | L-PEN |
Direction of action | 1L-N/PE |
Nominal voltage UN | 240/415 V AC (TN) |
Nominal voltage UN | 240/415 V AC (TT) |
Nominal voltage UN | 230 V AC (IT) |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 350 V AC |
Rated load current IL | 80 A |
Residual current IPE | ≤ 5 µA |
Standby power consumption PC | ≤ 2.00 mVA |
Nominal discharge current In (8/20) µs | 10 kA |
Maximum discharge current Imax (8/20) µs | 20 kA |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up | ≤ 1.5 kV |
Residual voltage Ures | ≤ 1.2 kV (at In) |
Residual voltage Ures | ≤ 1.2 kV (at 10 kA) |
Residual voltage Ures | ≤ 1.1 kV (at 5 kA) |
Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
TOV behavior at UT | 415 V AC (5 s / withstand mode) |
TOV behavior at UT | 440 V AC (120 min / withstand mode) |
Response time tA | ≤ 100 ns |
Max. backup fuse with V-type through wiring | 80 A (gG) |
Max. backup fuse with branch wiring | 125 A (gG) |
Additional technical data
Impulse discharge current (10/350) µs, charge | 0.25 As |
Impulse discharge current (10/350) µs, specific energy | 62.5 J/Ω |
Impulse discharge current (10/350) µs, peak value limp | 500 A |
Ambient conditions
Degree of Protection | IP20 (only when all terminal points are used) |
Ambient Temperature (Operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (Operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
UL specifications
Maximum continuous operating voltage MCOV (L-N) | 350 V AC |
Nominal discharge current In (L-N) | 10 kA |
Mode of protection | L-N |
Nominal Voltage | 240 V AC |
Power distribution system | Single phase |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-N) | 2420 V |
SPD Type | 4CA |
UL connection data
Tightening torque | 30 lbf-in. |
Conductor cross section AWG | 14 ... 2 |
Standards and Regulations
Standards/specifications | IEC 61643-11 |
Note | 2011 |
Standards/specifications | EN 61643-11 |
Note | 2012 |
Mounting
Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 2856582?
Proax is an authorized distributor of Phoenix Contact 2856582 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended