2800388
SKU
PHX2800388
MPN
VAL-SQ SE 200-120/240HLD /D
Weight
0.222 kg
Series VAL-SQ-SE
VAL-SQ SE 200-120/240HLD /D - Type 2 surge protection replacement module
Surge protection device for 120/240 V High-Leg Delta configurations typically used as service entry protection. NEMA rated enclosure provides a monitor with surge counter, status LEDs and audible alarm with remote monitor capability. Hybrid Sine Wave Tracking provides 200 kA surge protection.
Technical Specifications
Product properties
| IEC power supply system | TN-S |
| IEC power supply system | TT |
| Type | Parallel MOV |
| Surge protection fault message | Phase LEDs |
| Surge protection fault message | Audible alarm |
| Surge protection fault message | Remote indication contact |
General
| Power Systems | 120/240 V High-Leg Delta |
Connection data
| Connection Method | Screw terminal blocks |
| Tightening torque, min | 4 Nm |
| Connection Method | Screw connection |
Dimensions
| Width | 418 mm |
| Depth | 562 mm |
Material specifications
| Housing Material | Metal |
Protective circuit
| Direction of action | 3L-N & N-GND |
| Maximum continuous voltage UC | 150 V |
| Response time tA | < 1 ns |
Ambient conditions
| Degree of Protection | NEMA 3R/12 |
| Ambient Temperature (Operation) | -20 °C ... 65 °C |
| Ambient temperature (storage/transport) | -20 °C ... 65 °C |
| Altitude | 3658 m |
| Permissible humidity (operation) | 0 % ... 95 % |
UL specifications
| Maximum continuous operating voltage MCOV | 150 V |
| Short-circuit current rating (SCCR) | 200 kA |
| Voltage protection rating VPR (L-L) | 1500 V |
| Voltage protection rating (VPR HL-L) | 300 V |
| Voltage protection rating VPR (L-N) | 700 V |
| Voltage protection rating (VPR HL-N) | 150 V |
| Voltage protection rating (VPR L-PE) | 1200 V |
| Voltage protection rating (VPR HL-G) | 150 V |
| Voltage protection rating (VPR L-PEN) | 700 V |
| UL type | type 2 |
| Nominal discharge current In | 20 kA |
| Maximum Surge Current per Phase | 200 kA |
| EMI/RFI filtering | -30 dB |
Standards
| Standards/regulations | UL 1449 3rd edition, Sept. 2009 |
| Standards/regulations | UL 1283 |
| Standards/regulations | IEEE C62.41 |
| Standards/regulations | IEEE C62.45 |
Mounting
| Mounting Type | Wall mounting |
| Mounting Position | any |
Why Proax for Phoenix Contact 2800388?
Proax is an authorized distributor of Phoenix Contact 2800388 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended
Surge protection device for 277/480 V AC Wye configurations with a high-resistance ground typically used as service entry protection. NEMA rated enclosure provides a monitor with surge counter, status LEDs and audible alarm with remote monitor capability. Hybrid Sine Wave Tracking provides 200 kA surge protection.
Surge protection device for 120/208 V AC Wye configurations typically used as service entry protection. Protects across all phases and directions. NEMA rated enclosure provides a monitor with surge counter, status LEDs and audible alarm with remote monitor capability. Hybrid Sine Wave Tracking provides 360 kA surge protection.