Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
CN-LAMBDA/4-0.47-SB
Weight
0.191 kg
This product is Not Cancellable/Not Returnable
Series CN-LAMBDA

CN-LAMBDA/4-0.47-SB - Surge protection device

Attachment plug with Lambda/4 technology as surge protection for coaxial signal interfaces. Connection: N connectors plug/socket

  • Easy installation with system-compliant connection
  • Use under extreme ambient conditions with robust design
  • Service-friendly with maintenance-free protective circuit
  • Exceptional protective properties with Lambda/4 technology
Technical Specifications

Product properties

IEC test classificationC2
IEC test classificationC3
IEC test classificationD1
VDE requirement classC2
VDE requirement classC3
VDE requirement classD1
TypeAttachment plug
Number of Positions1
Surge protection fault messagenone

Connection data

Connection MethodN Connector

Dimensions

Width32 mm
Height32 mm
Depth81 mm

Material specifications

ColorNickel
Seal materialSilicon
Housing MaterialBrass (CuZn)
Housing surface materialGuard plate (TM)
Inner conductor materialBeCu
Inner conductor surface materialGold
Insulation body materialPTFE

Mechanical data

Open side panelNo

Protective circuit

Direction of actionLine-Shield/Earth Ground
Rated current5 A (25 °C)
Nominal discharge current In (8/20) µs (line-ground)20 kA
Nominal discharge current In (8/20) µs (line-shield)20 kA
Pulse discharge current Iimp (10/350) µs≤ 15 kA
Total discharge current Itotal (8/20) µs30 kA
Total discharge current Itotal (10/350) µs15 kA
Max. discharge current Imax (8/20) µs maximum (line-earth)30 kA
Max. discharge current Imax (8/20) µs maximum (line-shield)30 kA
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 55 V (6 kV / 3 kA)
Output voltage limitation at 1 kV/µs (line-shield) spike≤ 55 V (6 kV / 3 kA)
Output voltage limitation at 1 kV/µs (line-earth) static≤ 55 V
Output voltage limitation at 1 kV/µs (line-shield) static≤ 55 V
Voltage protection level Up (line-earth)≤ 95 V (C2 - 10 kV / 5 kA)
Voltage protection level Up (line-shield)≤ 95 V (C2 - 10 kV / 5 kA)
Input attenuation aE, asym.typ. 0.05 dB (≤ 0.10 dB)
Frequency Range380 MHz ... 470 MHz
Voltage standing wave ratio VSWR in a 50 Ω systemtyp. 1.05 (≤ 1,15)
Permissible HF power Pmax at VSWR = xx (50 ohm system)≤ 800 W
Permissible HF power Pmax at VSWR = xx (50 ohm system)≤ 4 kW (peak)
Surge protection fault messagenone
Impulse durability (line-earth)C2 - 10 kV / 5 kA
Impulse durability (line-earth)D1 - 2.5 kA
Impulse durability (line-shield)C2 - 10 kV/5 kA
Impulse durability (line-shield)D1 - 2.5 kA

Ambient conditions

Degree of ProtectionIP68
Ambient Temperature (Operation)-40 °C ... 90 °C

Standards and Regulations

VDE requirement classC2
VDE requirement classC3
VDE requirement classD1

Standards Information technology specification

Standards/regulationsIEC 61643-21
Standards/regulationsIEC 61643-21
Standards/specificationsIEC 61643-21
Note2005

Mounting

Mounting TypeConnection-specific intermediate plugging
Accessories

Why Proax for Phoenix Contact 2800022?

Proax is an authorized distributor of Phoenix Contact 2800022 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability