Official Distributor
SKU
MPN
CN-LAMBDA/4-0.47-BB
Weight
0.194 kg
This product is Not Cancellable/Not Returnable
Series CN-LAMBDA
CN-LAMBDA/4-0.47-BB - Surge protection device
Attachment plug with Lambda/4 technology as surge protection for coaxial signal interfaces. Connection: N connectors socket-socket
- Easy installation with system-compliant connection
- Use under extreme ambient conditions with robust design
- Service-friendly with maintenance-free protective circuit
- Exceptional protective properties with Lambda/4 technology
Technical Specifications
Product properties
IEC test classification | C2 |
IEC test classification | C3 |
IEC test classification | D1 |
VDE requirement class | C2 |
VDE requirement class | C3 |
VDE requirement class | D1 |
Type | Attachment plug |
Number of Positions | 1 |
Surge protection fault message | none |
Connection data
Connection Method | N Connector |
Dimensions
Width | 32 mm |
Height | 32 mm |
Depth | 83 mm |
Material specifications
Color | Nickel |
Seal material | Silicon |
Housing Material | Brass (CuZn) |
Housing surface material | Guard plate (TM) |
Inner conductor material | BeCu |
Inner conductor surface material | Gold |
Insulation body material | PTFE |
Mechanical data
Open side panel | No |
Protective circuit
Direction of action | Line-Shield/Earth Ground |
Rated current | 5 A (25 °C) |
Nominal discharge current In (8/20) µs (line-ground) | 20 kA |
Nominal discharge current In (8/20) µs (line-shield) | 20 kA |
Pulse discharge current Iimp (10/350) µs | ≤ 15 kA |
Total discharge current Itotal (8/20) µs | 30 kA |
Total discharge current Itotal (10/350) µs | 15 kA |
Max. discharge current Imax (8/20) µs maximum (line-earth) | 30 kA |
Max. discharge current Imax (8/20) µs maximum (line-shield) | 30 kA |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 55 V (6 kV / 3 kA) |
Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 55 V (6 kV / 3 kA) |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 55 V (6 kV / 3 kA) |
Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 55 V (6 kV / 3 kA) |
Voltage protection level Up (line-earth) | ≤ 95 V (C2 - 10 kV / 5 kA) |
Voltage protection level Up (line-shield) | ≤ 95 V (C2 - 10 kV / 5 kA) |
Input attenuation aE, asym. | typ. 0.05 dB (≤ 0.10 dB) |
Frequency Range | 380 MHz ... 470 MHz |
Voltage standing wave ratio VSWR in a 50 Ω system | typ. 1.05 (≤ 1,15) |
Permissible HF power Pmax at VSWR = xx (50 ohm system) | ≤ 800 W |
Permissible HF power Pmax at VSWR = xx (50 ohm system) | ≤ 4 kW (peak) |
Surge protection fault message | none |
Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
Impulse durability (line-earth) | D1 - 2.5 kA |
Impulse durability (line-shield) | C2 - 10 kV/5 kA |
Impulse durability (line-shield) | D1 - 2.5 kA |
Ambient conditions
Degree of Protection | IP68 |
Ambient Temperature (Operation) | -40 °C ... 90 °C |
Standards and Regulations
VDE requirement class | C2 |
VDE requirement class | C3 |
VDE requirement class | D1 |
Standards Information technology specification
Standards/regulations | IEC 61643-21 |
Standards/regulations | IEC 61643-21 |
Standards/specifications | IEC 61643-21 |
Note | 2005 |
Mounting
Mounting Type | Connection-specific intermediate plugging |
Accessories
Why Proax for Phoenix Contact 2800021?
Proax is an authorized distributor of Phoenix Contact 2800021 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |