Official Distributor
SKU
MPN
FLM BK EIP M12 DI 8 M12-2TX
Weight
0.343 kg
FLM BK EIP M12 DI 8 M12-2TX - Bus coupler
The EtherNet/IP™ bus coupler opens a local bus for up to 16 devices. Additional functions: 10 Mbps and 100 Mbps, auto negotiation, auto crossover, 8 digital inputs, channel-specific diagnostics, short-circuit/overload protection, M12 fast connection technology.
- EtherNet/IP™
- 8 inputs, 24 V DC
- M12 connection technology with SPEEDCON fast locking system
Technical Specifications
Dimensions
Width | 70 mm |
Height | 178 mm |
Depth | 50 mm |
Drill hole spacing | 178 mm |
Material specifications
Color | anthracite |
Ethernet/IP™
Connection Method | M12 connectors, D-coded |
Designation connection point | Copper cable |
Number of Positions | 4 |
Transmission Speed | 10/100 Mbps (auto negotiation) |
Fieldbus: Local bus gateway
Designation | Local bus gateway |
Connection Method | M12 connector, B-coded |
Transmission Speed | 500 kbaud/2 Mbaud, can be selected |
Max. length of local bus | 20 m |
Max. number of local bus devices | 16 |
System limits
Number of local bus devices that can be connected | max. 16 |
Number of devices with parameter channel | max. 16 |
Module
Process data channel | 8 bit |
Input address area | 8 bit |
Output address area | 0 bit |
Register length | 8 bit |
Digital:
Input name | Digital inputs |
Description of the input | IEC 61131-2 type 1 |
Number of Inputs | 8 |
Connection Method | M12 connector |
Connection technology | 2-, 3-, 4-conductor |
Input Voltage | 24 V DC |
Input voltage range "0" signal | -30 V DC ... 5 V DC |
Input voltage range "1" signal | 13 V DC ... 30 V DC |
Nominal input voltage UIN | 24 V DC |
Filter time | 3 ms |
Protective circuit | Short-circuit protection, overload protection of the sensor supply; Reverse polarity protection |
Product properties
Product family | Fieldline |
Type | modular |
No. of channels | 8 |
Potentials
Voltage supply UL | 24 V DC |
Power supply at UL | max. 4 A |
Current consumption from UL | max. 118 mA (At 2 Mbaud) |
Current consumption from UL | typ. 118 mA (At 2 Mbaud) |
Current consumption from UL | max. 60 mA (At 500 kBaud) |
Current consumption from UL | typ. 60 mA (At 500 kBaud) |
Voltage supply US | 24 V DC |
Power supply at US | max. 4 A |
Current consumption from US | typ. 5 mA (plus power supply for sensors) |
Current consumption from US | max. 600 mA |
Supply: Module electronics
Connection Method | M12 connector |
Designation | UL |
Supply Voltage | 24 V DC |
Supply Voltage Range | 18 V DC ... 30 V DC (including ripple) |
Supply current | < 100 mA |
Electrical isolation/isolation of the voltage ranges
Test voltage: To I/O | 500 V DC |
Connection data
Connection Method | M12 connector |
Ambient conditions
Ambient Temperature (Operation) | -25 °C ... 60 °C |
Degree of Protection | IP65/IP67 |
Air pressure (operation) | 80 kPa ... 106 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (storage/transport) | 95 % |
Standards and Regulations
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting
Mounting Type | Wall mounting, optionally on mounting panel |
Mounting Type | Wall mounting |
Accessories
Why Proax for Phoenix Contact 2773322?
Proax is an authorized distributor of Phoenix Contact 2773322 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended