Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
IB IL 24 DO 4
Weight
0.064 kg
This product has been discontinued and replaced with 2861276
Series IB-IL

IB IL 24 DO 4 - Inline terminal

Inline digital output terminal, without accessories, 4 outputs, 24 V DC, 500 mA, 3-conductor connection technology

  • 4 digital outputs
  • Connection of actuators in 2- and 3-conductor technology
  • Nominal current per output: 500 mA
  • Total current of the terminal: 2 A
  • Short-circuit and overload-protected outputs
  • Diagnostic and status indicators
Technical Specifications

Product properties

Typemodular
No. of channels4
Diagnostics messagesShort-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module

Module

ID code (dec.)189
ID code (hex)BD
Length code (hex)41
Length code (dec)65
Process data channel4 bit
Input address area0 Byte
Output address area4 bit
Register length4 bit
Required parameter data 3 Byte
Required configuration data 4 Byte

Potentials: Communications power (UL)

Supply Voltage7.5 V DC (via voltage jumper)
Current drawmax. 44 mA

Potentials: Segment circuit supply (US)

Supply Voltage24 V DC (via voltage jumper)
Supply Voltage Range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 2 A

Electrical isolation/isolation of the voltage ranges

Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O)500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground500 V AC, 50 Hz, 1 min.

Digital:

Output nameDigital outputs
Connection MethodSpring-cage connection
Connection technology2-, 3-conductor
Number of Outputs4
Protective circuitOverload protection, short-circuit protection of outputs; electronic
Output Voltage24 V DC (US - 1 V)
Limitation of the voltage induced on circuit interruption-46 V ... -15 V
Maximum Output Current per channel500 mA
Maximum Output Current per module2 A
Nominal Output Voltage24 V DC (voltage difference at Inom ≤ 1 V)
Output voltage when switched offmax. 2 V
Output current when switched offmax. 300 µA
Nominal load, inductive12 VA (1.2 H, 50 Ω)
Nominal load, lamp12 W
Nominal load, ohmic12 W (48 Ω)
Maximum operating frequency with ohmic nominal loadmax. 300 Hz (this switching frequency is limited by the data rate selected, the number of bus devices, the structure of the bus, the software used and the control or computer system used)
Reverse voltage resistance to short pulsesReverse voltage proof
Behavior with overloadAuto restart
Behavior with inductive overloadOutput can be destroyed
Behavior at voltage switch-offThe output follows the power supply without delay
Overcurrent shut-downmin. 0.7 A
Output current with ground connection interrupt when switched offmax. 25 mA

Inline connector

Connection MethodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Inline local bus

Connection MethodInline data jumper
Transmission Speed500 kbps

Diagnostic messages

DiagnosticsShort-circuit or overload of the digital outputs
MessageError message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module

Dimensions

Width12.2 mm
Height119.8 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Material specifications

Colorgreen

Ambient conditions

Ambient Temperature (Operation)-25 °C ... 55 °C
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-25 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)10 % ... 95 % (according to DIN EN 61131-2)

Standards and Regulations

Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting

Mounting TypeDIN rail mounting

Why Proax for Phoenix Contact 2726256?

Proax is an authorized distributor of Phoenix Contact 2726256 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Not in stock

Request lead time or order—we'll ensure quick delivery

Phoenix Contact Availability