3-pole, motor operated, base mounted switch-diconnector with handle for manual operation, terminal bolt kit, handle and spare fuse storage clip and male connector for control circuit
Technical Specifications

ABB EcoSolutions

End Of Life Disassembling Instructions1SCC301138M0201
Environmental Product Declaration - EPD1SCC303093D0201

Dimensions

Product Net Width296 mm
Product Net Height150 mm
Product Net Depth / Length198 mm
Product Net Weight5.1 kg

Technical

Conventional Free-air Thermal Current (Ith)Θ = 40 °C 200 A
Conventional Thermal Current (Ithe)Fully Enclosed 160 A
Degree of ProtectionFront IP00
Distance Between PhasesStandard
Handle colorBlack
Handle TypeDirect mounted handle
Mechanical Durability20000
Motor Operational Voltage220 ... 240 V AC
Mounting TypeBase mounting
Number of Poles3P
Operating modeFront
Pollution degree3
Position of Line TerminalsTop In - Bottom Out
Power Lossat Rated Operating Conditions per Pole 3.2 W
Rated Conditional Short-Circuit Current (Inc)(315 A fuse, 500 V) 100 kA
Rated Conditional Short-Circuit Current (Inc)(355 A fuse, 690 V) 80 kA
Rated Impulse Withstand Voltage (Uimp)12 kV
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)(380 ... 415 V) 200 A
Rated Operational Current AC-21A (Ie)(500 V) 200 A
Rated Operational Current AC-21A (Ie)(690 V) 160 A
Rated Operational Current AC-21A (Ie)(1000 V AC) 160 A
Rated Operational Current AC-22A (Ie)(380 ... 415 V) 200 A
Rated Operational Current AC-22A (Ie)(500 V) 200 A
Rated Operational Current AC-22A (Ie)(690 V) 160 A
Rated Operational Current AC-23A (Ie)(380 ... 415 V) 160 A
Rated Operational Current AC-23A (Ie)(500 V) 160 A
Rated Operational Current AC-23A (Ie)(690 V) 160 A
Rated Operational Power AC-23A (Pe)(220 ... 240 V) 48 kW
Rated Operational Power AC-23A (Pe)(400 ... 415 V) 80 kW
Rated Operational Power AC-23A (Pe)(500 V) 112 kW
Rated Operational Power AC-23A (Pe)(690 V) 144 kW
Rated Operational VoltageMain Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)for 1 s 8 kA
Special FunctionsNo
StandardsIEC 60947-3
Switches Operating MechanismMechanism at the End of the Switch
Terminal TypeScrew Terminals
Tightening torqueacc. IEC 60947-1 15 … 22 N·m

Technical UL/CSA

Tightening torqueacc. IEC 60947-1 15 … 22 N·m

Why Proax for ABB OTM160E3M230C?

Proax is an authorized distributor of ABB OTM160E3M230C and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size1
Recommended

CAD$1,269.43

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability