OTDC200U33 PV Disconnect Switch, Handle and shaft not included, Base mounting, IEC&UL 200 A 1000V
Technical Specifications
ABB EcoSolutions
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 1SCC301114M0201 |
| Environmental Product Declaration - EPD | 1SCC301248D0201 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 66,5 % |
Dimensions
| Product Frame Size | S1.0 |
| Product Net Width | 190 mm |
| Product Net Width | 7.5 in |
| Product Net Height | 255 mm |
| Product Net Height | 10 in |
| Product Net Depth / Length | 85 mm |
| Product Net Depth / Length | 3.3 in |
| Product Net Weight | 3.2 kg |
| Product Net Weight | 7.1 lb |
Technical
| Connection configuration | Triple circuit 7a,7e |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 250 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 250 A |
| Degree of Protection | Front IP20 |
| Handle Type | Handle and shaft not included |
| Mounting Type | Base mounting |
| Number of Circuits | 3 |
| Number of Poles | 6P |
| Operating mode | Front |
| Pollution degree | 3 |
| Position of Line Terminals | Top In - Bottom Out |
| Position of Line Terminals | Bottom In - Top Out |
| Positive Opening Operation Torque (Direct Opening Action) | 5 … 8 N·m |
| Power Loss | at Rated Operating Conditions per Pole 9.5 W |
| Protection Type | Circuit breaker |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1500 V |
| Rated Operational Current DC-21B (Ie) | (1000 V) 200 A |
| Rated Operational Voltage | 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (1000 V DC) 10 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | (1000 V DC) 10 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 5 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 10 kA |
| Shaft Diameter | 6 mm |
| Shaft Diameter | 0.24 in |
| Special Functions | No |
| Standards | UL98B and IEC 60947-1, -3 |
| Switches Operating Mechanism | Mechanism Between the Poles |
| Switches Operating Mechanism | 33 (Between the Poles) |
| Terminal Type | Lug terminals |
| Terminal Width | 19.5 mm |
| Terminal Width | 0.77 in |
| Tightening torque | Cable Lug 15 … 22 N·m |
| Tightening torque | Cable Lug 133 … 195 lbf·in |
| Utilization | Photovoltaic |
| Utilization category | Switching of resistive loads, including moderate overloads - occasional actuation (DC-21B) |
Technical UL/CSA
| Maximum Operating Voltage | 1000Vdc, UL 98B |
| Ampere Rating | 200A,1000Vdc,UL98B |
| Short-circuit current rating (SCCR) | 10 kA |
| Short-circuit current rating (SCCR) | 1000 V DC |
| Tightening torque | Cable Lug 15 … 22 N·m |
| Tightening torque | Cable Lug 133 … 195 lbf·in |
Why Proax for ABB OTDC200U33?
Proax is an authorized distributor of ABB OTDC200U33 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended