OTDC100U22 PV Disconnect Switch, Terminal bolt kit included, Handle and shaft need to be ordered separately, Base mounting, UL 1000 VDC 100 A, IEC 1000 VDC 160 A
Documents
Technical Specifications
Dimensions
Product Frame Size | S1.0 |
Product Net Width | 185.4 mm |
Product Net Width | 7.3 in |
Product Net Height | 262 mm |
Product Net Height | 10.3 in |
Product Net Depth / Length | 90.5 mm |
Product Net Depth / Length | 3.6 in |
Product Net Weight | 2.2 kg |
Product Net Weight | 4.9 lb |
Technical
Connection configuration | Double circuit 4a, 4c |
Rated Operational Current DC-21B (Ie) | (1000 V) 160 A |
Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 160 A |
Conventional Thermal Current (Ithe) | Fully Enclosed 160 A |
Rated Impulse Withstand Voltage (Uimp) | 12 kV |
Rated Insulation Voltage (Ui) | 1500 V |
Rated Operational Voltage | 1000 V |
Rated Short-Circuit Making Capacity (Icm) | (1000 V DC) 10 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | (1000 V DC) 10 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 5 kA |
Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 10 kA |
Protection Type | Circuit breaker |
Power Loss | at Rated Operating Conditions per Pole 4 W |
Pollution degree | 3 |
Handle Type | Handle and shaft not included |
Positive Opening Operation Torque (Direct Opening Action) | 5 … 8 N·m |
Shaft Diameter | 6 mm |
Shaft Diameter | 0.24 in |
Switches Operating Mechanism | Mechanism Between the Poles |
Switches Operating Mechanism | 22 (Between the Poles) |
Position of Line Terminals | Top In - Bottom Out |
Position of Line Terminals | Bottom In - Top Out |
Operating mode | Front Operated |
Standards | UL98B and IEC 60947-1, -3 |
Special Functions | No |
Mounting Type | Base mounting |
Number of Circuits | 2 |
Number of Poles | 4 |
Degree of Protection | Front IP20 |
Terminal Type | Lug terminals |
Terminal Width | 19.5 mm |
Terminal Width | 0.77 in |
Tightening torque | Cable Lug 15 … 22 N·m |
Tightening torque | Cable Lug 133 … 195 lbf·in |
Utilization | Photovoltaic |
Utilization category | Switching of resistive loads, including moderate overloads - occasional actuation (DC-21B) |
Technical UL/CSA
Maximum Operating Voltage | 1000Vdc, UL 98B |
Ampere Rating | 100A,1000Vdc,UL98B |
Short-circuit current rating (SCCR) | 10 kA |
Short-circuit current rating (SCCR) | 1000 V DC |
Tightening torque | Cable Lug 15 … 22 N·m |
Tightening torque | Cable Lug 133 … 195 lbf·in |
Why Proax for ABB OTDC100U22?
Proax is an authorized distributor of ABB OTDC100U22 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended