CADEN
Cart

AFS146-30-12-33

Official Distributor

By ABB

SKU
ABBAFS146301233
MPN
1SFL467081R3312
Weight
1.3 kg
The AFS146-30-12-33 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted 1 left (1 N.O + 1 N.C.) and fixed 1 right (1 N.C.) side mounted auxiliary contact blocks with double clamp connections, controlling motors up to 75 kW / 400 V AC (AC-3) or 100 hp / 480 V UL and switching power circuits up to 225 A (AC-1) or 200 A UL general use. AFS contactors can be easily integrated in machine manufacturer’s systems complying with main standards EN ISO 13849 and EN 62061 - guaranteeing the safe use of your machinery and equipment. An easily identifiable yellow low energy auxiliary contact block ensures the status feedback circuits required in machine safety applications. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.

AFS contactors for safety applications

AFS contactors are specifically designed to enhance safety in machine applications. Featuring factory-mounted contact blocks with mechanically linked and mirror contacts, these contactors ensure reliable monitoring and control of circuits. With ABB’s comprehensive safety component range, building protection systems becomes more straightforward and efficient.

Main Benefits:

  • Safety Compliance: Meets major safety standards (EN ISO 13849 and EN 62061) for secure machinery and equipment use.

  • Guaranteed Status: Factory-mounted auxiliary contact blocks ensure accurate contactor status monitoring.

  • Easy Identification: Distinct yellow housing simplifies safety chain recognition.

  • Streamlined Safety Calculations: Safety values available in FSDT and Sistema tools for easier safety level assessments.

Main Features:

  • High Power Handling:

    • Up to 400 kW at 400 V AC-3

    • Up to 600 hp at 480 V

    • Up to 1050 A at 690 V AC-1

    • Up to 900 A for general use

  • Certified Safety Contacts: Mirror and mechanically linked contacts with third-party certification.

  • Fast Response: Opening times as low as 20 ms in certain models with PLC interfaces.

  • Precision Switching: Low-energy auxiliary contacts with a minimum switching capacity of 12 V, 3 mA (10⁻⁷).

  • Built-in Protection: Integrated surge suppression for enhanced safety.

Technical Specifications

Dimensions

Product Net Width90 mm
Product Net Depth / Length126 mm
Product Net Height150 mm
Product Net Weight1.3 kg

Technical

Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC2
Number of Poles3P
Rated Operational VoltageMain Circuit 1000 V
Rated Frequency (f)Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 225 A
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 225 A
Rated Operational Current AC-1 (Ie)(1000 V) 60 °C 200 A
Rated Operational Current AC-1 (Ie)(1000 V) 70 °C 175 A
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 225 A
Rated Operational Current AC-1 (Ie)(690 V) 60 °C 200 A
Rated Operational Current AC-1 (Ie)(690 V) 70 °C 175 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 146 A
Rated Operational Current AC-3 (Ie)(440 V) 60 °C 146 A
Rated Operational Current AC-3 (Ie)(500 V) 60 °C 130 A
Rated Operational Current AC-3 (Ie)(690 V) 60 °C 93 A
Rated Operational Current AC-3 (Ie)(1000 V) 60 °C 60 A
Rated Operational Current AC-3 (Ie)(380 / 400 V) 60 °C 146 A
Rated Operational Current AC-3 (Ie)(220 / 230 / 240 V) 60 °C 146 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 146 A
Rated Operational Current AC-3e (Ie)(440 V) 60 °C 146 A
Rated Operational Current AC-3e (Ie)(500 V) 60 °C 130 A
Rated Operational Current AC-3e (Ie)(690 V) 60 °C 93 A
Rated Operational Current AC-3e (Ie)(1000 V) 60 °C 54 A
Rated Operational Current AC-3e (Ie)(380 / 400 V) 60 °C 146 A
Rated Operational Current AC-3e (Ie)(220 / 230 / 240 V) 60 °C 146 A
Rated Operational Power AC-3 (Pe)(415 V) 75 kW
Rated Operational Power AC-3 (Pe)(440 V) 90 kW
Rated Operational Power AC-3 (Pe)(500 V) 90 kW
Rated Operational Power AC-3 (Pe)(690 V) 90 kW
Rated Operational Power AC-3 (Pe)(1000 V) 75 kW
Rated Operational Power AC-3 (Pe)(380 / 400 V) 75 kW
Rated Operational Power AC-3 (Pe)(220 / 230 / 240 V) 45 kW
Rated Operational Power AC-3e (Pe)(415 V) 75 kW
Rated Operational Power AC-3e (Pe)(440 V) 90 kW
Rated Operational Power AC-3e (Pe)(500 V) 90 kW
Rated Operational Power AC-3e (Pe)(690 V) 90 kW
Rated Operational Power AC-3e (Pe)(1000 V) 75 kW
Rated Operational Power AC-3e (Pe)(380 / 400 V) 75 kW
Rated Operational Power AC-3e (Pe)(220 / 230 / 240 V) 45 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Breaking Capacity AC-3e8.5 x Ie AC-3e
Rated Making Capacity AC-310 x Ie AC-3
Rated Making Capacity AC-3e12 x Ie AC-3e
Short-Circuit Protective DevicesgG Type Fuses 315 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
Rated Insulation Voltage (Ui)acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
Maximum Electrical Switching Frequency(AC-2 / AC-4) 150 cycles per hour
Maximum Electrical Switching Frequency(AC-3) 300 cycles per hour
Mechanical Durability5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 100 ... 250 V
Rated Control Circuit Voltage (Uc)60 Hz 100 ... 250 V
Rated Control Circuit Voltage (Uc)DC Operation 100 ... 250 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage DC 4 W
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
Coil ConsumptionPull-in at Max. Rated Control Circuit Voltage DC 135 W
Power Lossat Rated Operating Conditions per Pole 10 W
Operate TimeBetween Coil De-energization and NO Contact Opening 37 ... 47 ms
Operate TimeBetween Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main CircuitFlexible 1 x 10 ... 70 mm²
Connecting Capacity Main CircuitRigid Cu-Cable 2 x 10 ... 95 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible 1x0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitSolid 2 x 1 ... 4 mm²
Connecting Capacity Auxiliary CircuitStranded 2 x 1 .... 4 mm²
Connecting CapacityFlexible 1 x 10 ... 70 mm²
Connecting CapacityRigid Cu-Cable 2 x 10 ... 95 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Recommended Screw DriverMain Circuit M6
Recommended Screw DriverControl Circuit M3.5
Recommended Screw DriverControl Circuit 5.5
Recommended Screw DriverControl Circuit Pozidriv 2
Tightening torqueCable Lug 9 N·m
Tightening torqueMain Circuit 8 N·m
Terminal TypeDouble Clamp
Product NameBlock Contactor

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 200 A
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 40 hp
Horsepower Rating UL/CSA(220 ... 240 V AC) Three Phase 50 hp
Horsepower Rating UL/CSA(440 ... 480 V AC) Three Phase 100 hp
Horsepower Rating UL/CSA(550 ... 600 V AC) Three Phase 125 hp
Full Load Amps Motor Use(200 ... 208 V AC) Three Phase 120 A
Full Load Amps Motor Use(220 ... 240 V AC) Three Phase 130 A
Full Load Amps Motor Use(440 ... 480 V AC) Three Phase 124 A
Full Load Amps Motor Use(550 ... 600 V AC) Three Phase 125 A

ABB EcoSolutions

ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNon-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions1SFC100112M0001
Environmental Product Declaration - EPD1SFC100092D0201
Improved Energy Efficiency for CustomersProduct Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Sustainable Material Content in Product (wt. %)Recycled Metal - 37 %

Why Proax for ABB AFS146-30-12-33?

Proax is an authorized distributor of ABB AFS146-30-12-33 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate NamesAFS146301233
Pack Size1
Recommended

CAD$1,302.12

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability