NFZ22E-30
By ABB
SKU
ABBNFZ22E30
MPN
1SBH136001R3022
Weight
0.43 kg
NFZ contactor relays are used for switching auxiliary and control circuits. NFZ contactor relays with coil 30 include a 24 V DC electronic coil interface with a built-in surge suppression, obtaining a reduced holding coil consumption up to 1.7 W for a low panel energy consumption and a direct control by PLC-output ≥ 250 mA 24 V DC, without need of additional interface relay. Only NFZ..-30 contactor relays need to respect the polarity on the coil terminals (A1+ and A2-). - Poles: 4-pole contactor relays (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1 and including the "Mechanically Linked" symbol on the contactor relay side) - Accessories: a wide range of accessories is available.
Technical Specifications
Dimensions
| Product Net Width | 45 mm |
| Product Net Depth / Length | 97 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.43 kg |
Technical
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-5-1, UL 60335-2-40 LZGH2 A2L, UL 508, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 14-13 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| Rated Operational Current AC-15 (Ie) | (690 V) 2 A |
| Rated Operational Current AC-15 (Ie) | (24 / 127 V) 6 A |
| Rated Operational Current AC-15 (Ie) | (220 / 240 V) 4 A |
| Rated Operational Current AC-15 (Ie) | (400 / 440 V) 3 A |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| Rated Operational Current DC-13 (Ie) | (48 V) 2.8 A / 134 W |
| Rated Operational Current DC-13 (Ie) | (72 V) 1 A / 72 W |
| Rated Operational Current DC-13 (Ie) | (110 V) 0.55 A / 60 W |
| Rated Operational Current DC-13 (Ie) | (125 V) 0.55 A / 69 W |
| Rated Operational Current DC-13 (Ie) | (220 V) 0.27 A / 60 W |
| Rated Operational Current DC-13 (Ie) | (250 V) 0.27 A / 68 W |
| Rated Operational Current DC-13 (Ie) | (400 V) 0.15 A / 60 W |
| Rated Operational Current DC-13 (Ie) | (500 V) 0.13 A / 65 W |
| Rated Operational Current DC-13 (Ie) | (600 V) 0.1 A / 60 W |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-5-1 690 V |
| Rated Insulation Voltage (Ui) | acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-15) 1200 cycles per hour |
| Maximum Electrical Switching Frequency | (DC-13) 900 cycles per hour |
| Maximum Mechanical Switching Frequency | 6000 cycles per hour |
| Rated Control Circuit Voltage (Uc) | DC Operation 24 V |
| Power Loss | at 6 A per Pole 0.1 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 22 ... 57 ms |
| Operate Time | Between Coil De-energization and NO Contact Opening 17 ... 29 ms |
| Operate Time | Between Coil Energization and NC Contact Opening 20 ... 35 ms |
| Operate Time | Between Coil Energization and NO Contact Closing 27 ... 53 ms |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² |
| Connecting Capacity Auxiliary Circuit | Rigid Solid 1/2x 1 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Rigid Stranded 1/2x 1 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² |
| Connecting Capacity Control Circuit | Rigid Solid 1/2x 1 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Rigid Stranded 1/2x 1 ... 2.5 mm² |
| Wire Stripping Length | Auxiliary Circuit 10 mm |
| Wire Stripping Length | Control Circuit 10 mm |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Tightening torque | Auxiliary Circuit 1.2 N·m |
| Tightening torque | Control Circuit 1.2 N·m |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor Relay |
Technical UL/CSA
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Stranded 1/2x 18-14 AWG |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Tightening Torque UL/CSA | Control Circuit 11 in·lb |
ABB EcoSolutions
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| Sustainable Material Content in Packaging (wt. %) | Recycled Cardboard - 86 % |
| Sustainable Material Content in Product (wt. %) | Recycled Metal - 28 % |
Why Proax for ABB NFZ22E-30?
Proax is an authorized distributor of ABB NFZ22E-30 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Alternate Names | NFZ22E30 |
| Pack Size | 1 |
Recommended