Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
2702877
Weight
2.075 kg
This product is Not Cancellable/Not Returnable
Series RAD

RAD-900-DAIO6 - Wireless module

Radioline - 900 MHz wireless transceiver with six integrated I/O channels, NEMA 4X enclosure, N (female) antenna connection, omnidirectional antenna, point-to-point, star, and mesh networks up to 250 stations, range of up to 32 km (line of sight), for use in North America

  • Range of several kilometers thanks to adjustable data rates for the wireless interface
  • NEMA 4X housing reduces time and complexity of installation
  • Power using AC mains or DC control voltages
  • Completely compatible with existing Radioline installations
Technical Specifications

Trade restriction

CE noteThe products are offered exclusively for export outside the EU and the European Economic Area.

Insulation characteristics

Overvoltage categoryII
Degree of pollution2

Electrical properties

Electrical isolation300 V (Rated insulation voltage (in each case between the analog inputs/analog outputs/AC supply, reinforced insulation according to EN 61010))
Electrical isolation50 V (Rated insulation voltage (in each case between the analog inputs/analog outputs/DC supply, reinforced insulation according to EN 61010))
Electrical isolation300 V (Rated insulation voltage (in each case between the digital inputs and digital outputs, reinforced insulation according to EN 61010))
Electrical isolation300 V (Rated insulation voltage (in each case between the digital inputs and outputs // analog inputs and outputs, reinforced insulation in accordance with EN/IEC 61010))
Test voltage for digital I/Os2.5 kV AC (60 Hz, 2 s)
Test voltage for analog I/Os1.5 kV AC (60 Hz, 2 s)
Transient surge protectionYes

Supply

Supply Voltage24 V DC
Supply Voltage Range10.8 V DC ... 30.5 V DC
Supply Voltage Range100 V AC ... 240 V AC
Typical current consumption110 mA (120 V AC)
Max. current consumption368 mA (10.8 V DC)
Max. current consumption135 mA (30.5 V DC)
Max. current consumption116 mA (100 V AC)
Max. current consumption60 mA (240 V AC)
Power consumption7.4 W (peak; 30 dBm)

Digital

Max. current consumption< 1 mA

Analog

Description of the inputAnalog input
Number of Inputs1
Current Input Signal0 mA ... 20 mA (can be set via DIP switches)
Current Input Signal4 mA ... 20 mA (can be set via DIP switches)
Max. current input signal22 mA
Input resistance current input< 70 Ω
Resolution16 bit
Precision≤ 0.02 % (at 25 °C)
Protective circuitShort-circuit and overload protection
Temperature coefficient, typicaltyp. 0.0025 %/K (at -40 °C ... +70 °C)
Supply Voltage≥ 12 V DC (For passive sensors (via terminal PWR1, +I1))

Digital

Description of the inputDigital input
Number of Inputs2
Min. voltage input signal0 V AC/DC
Max. voltage input signal250 V AC/DC
Switching level "0" signal0 V AC/DC ... 4 V AC/DC (Low-voltage input)
Switching level "0" signal0 V AC/DC ... 20 V AC/DC (High-voltage input)
Switching level "1" signal10 V AC/DC ... 50 V AC/DC (Low-voltage input)
Switching level "1" signal50 V AC/DC ... 250 V AC/DC (High-voltage input)
Input Frequency≤ 2 Hz
Output nameRelay output
Number of Outputs2
Contact switching typeChangeover contact
Contact MaterialAgSnO2
Maximum Switching Voltage250 V AC
Maximum Switching Voltage24 V DC
Min. switching current≥ 10 mA
Max. switching current2 A
Mechanical service life1x 107 cycles
Electrical service life2x 105 cycles (At 2 A, 250 V AC, cosφ 0.4)
Electrical service life2x 105 cycles (At 1 A, 24 V DC, L/R = 48 ms)
Maximum switching frequency2 Hz
Switching capacity48 W (24 V DC)
Switching capacity60 W (30 V DC)
Switching capacity20 W (48 V DC)
Switching capacity18 W (60 V DC)
Switching capacity22 W (110 V DC)
Switching capacity40 W (220 V DC)
Switching capacity42 W (250 V DC)
Behavior of the outputs (adjustable via DIP switch)Hold / Reset

Analog

Output nameAnalog output
Number of Outputs1
Voltage output signal0 V ... 10 V
Max. voltage output signalapprox. 10.83 V
Current Output Signal0 mA ... 20 mA
Current Output Signal4 mA ... 20 mA
Max. current output signalapprox. 21.67 mA
Load≥ 10 kΩ
Load≤ 500 Ω
Resolution16 bit
Protective circuitTransient protection of outputs

Digital

Output nameRF link relay output
Number of Outputs1
Contact switching typeChangeover contact
Contact MaterialPdRu, gold-plated
Maximum Switching Voltage30 V AC/DC
Max. switching current500 mA
Electrical service life5x 105 switching cycles with 0.5 A at 30 V DC

Analog

Output nameRSSI voltage output
Number of Outputs1
Voltage output signal0 V ... 3 V

Connection data

Connection MethodScrew connection
Stripping length11 mm
Conductor cross section, rigid min.0.14 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.14

Wireless

Range± 32 km (The range may be considerably above or below that stated, and depends on the environment, antenna technology, and the product used)
Interface descriptionTrusted Wireless
DirectionBi-directional
Frequency900 MHz
Frequency Range902 MHz ... 928 MHz
Transmission powermax. 1 W (adjustable)
Data rate16 kbps (adjustable)
Data rate125 kbps (adjustable)
Data rate250 kbps (adjustable)
Data rate500 kbps (adjustable)
Minimum receiver sensitivity-112 dBm (16 kbps)
Minimum receiver sensitivity-105 dBm (125 kbps)
Minimum receiver sensitivity-102 dBm (250 kbps)
Minimum receiver sensitivity-95 dBm (500 kbps)
Antenna Connection MethodN (female)
Security128-bit data encryption

Functions

Country supportUSA (FCC, Part 15.247, ID: SGV-SHR-900)
Country supportCanada (IC, RSS210, ID: 4720C-SHR900)

Wireless

Frequency Range902 MHz ... 928 MHz
Frequency band900 MHz
Wireless StandardTrusted Wireless

Signaling

Status displayGreen LED (supply voltage, PWR)
Status displayGreen LED (bus communication, DAT)
Status displayRed LED (periphery error, ERR)
Status display3x green, 1x yellow LED (LED bar graph receive quality, RSSI)
Status displayYellow LED (digital input, DI1)
Status displayYellow LED (digtial input, DI2)
Status displayYellow LED (digtial output, DO1)
Status displayYellow LED (digtial output, DO2)

Dimensions

Width220 mm
Height90 mm
Depth120 mm

Material specifications

Colorblack
Flammability rating according to UL 94V0
Housing MaterialGlass-reinforced plastic (GRP)

Ambient conditions

Degree of ProtectionNEMA 4
Ambient Temperature (Operation)-40 °C ... 70 °C (DC)
Ambient Temperature (Operation)-40 °C ... 65 °C (AC)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °F ... 185 °F
Altitude2000 m
Permissible humidity (operation)20 % ... 85 %
Permissible humidity (storage/transport)20 % ... 85 %
Shockin accordance with DIN EN 60068-2-27: 30g, 18 ms
Vibration (Operation)in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz

Conformity/Approvals

ConformanceFCC Directive, Part 15.247
ConformanceISC Directive RSS 210
UL, USA / CanadaANSI/ISA/CSA 22.2 61010-2-201, UL 50E Type 4
UL, USA / CanadaClass I, Div. 2, Groups A, B, C, D T4Class I, Zone 2, IIC T4

EMC data

Electromagnetic compatibilityConformance with EMC Directive 2004/108/EC

Mounting

Mounting TypePanel mount
Accessories

Why Proax for Phoenix Contact RAD-900-DAIO6?

Proax is an authorized distributor of Phoenix Contact RAD-900-DAIO6 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesRAD900DAIO6
Pack Size1