AS09 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. They are mainly used for controlling 3-phase motors, non-inductive or slightly inductive loads. The AS..S contactors are the spring terminal version of the AS... range. The AS... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front-mounted add-on auxiliary contact blocks (mechanically-linked auxiliary contacts compliant with Annex L of IEC 60947-5-1. N.C. mirror contacts compliant with Annex F of IEC 60947-4-1) - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
Technical Specifications
Dimensions
| Product Net Width | 45 mm |
| Product Net Depth / Length | 72.5 mm |
| Product Net Height | 68 mm |
| Product Net Weight | 0.22 kg |
Technical
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 1 |
| Standards | IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 20 A |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Θ = 40 °C 10 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 20 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 60 °C 15 A |
| Rated Operational Current AC-1 (Ie) | (690 V) 70 °C 12 A |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 9 A |
| Rated Operational Current AC-3 (Ie) | (440 V) 60 °C 8 A |
| Rated Operational Current AC-3 (Ie) | (500 V) 60 °C 8 A |
| Rated Operational Current AC-3 (Ie) | (690 V) 60 °C 5 A |
| Rated Operational Current AC-3 (Ie) | (380 / 400 V) 60 °C 9 A |
| Rated Operational Current AC-3 (Ie) | (220 / 230 / 240 V) 60 °C 9 A |
| Rated Operational Current AC-15 (Ie) | (500 V) NC 2 |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| Rated Operational Current AC-15 (Ie) | (690 V) 2 A |
| Rated Operational Current AC-15 (Ie) | (24 / 127 V) 6 A |
| Rated Operational Current AC-15 (Ie) | (220 / 240 V) 4 A |
| Rated Operational Current AC-15 (Ie) | (400 / 440 V) 3 A |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| Rated Operational Current DC-13 (Ie) | (48 V) 2.8 A / 134 W |
| Rated Operational Current DC-13 (Ie) | (72 V) 1 A / 72 W |
| Rated Operational Current DC-13 (Ie) | (110 V) 0.55 A / 60 W |
| Rated Operational Current DC-13 (Ie) | (125 V) 0.55 A / 69 W |
| Rated Operational Current DC-13 (Ie) | (220 V) 0.27 A / 60 W |
| Rated Operational Current DC-13 (Ie) | (250 V) 0.27 A / 68 W |
| Rated Operational Power AC-3 (Pe) | (400 V) 4 kW |
| Rated Operational Power AC-3 (Pe) | (415 V) 4 kW |
| Rated Operational Power AC-3 (Pe) | (440 V) 4 kW |
| Rated Operational Power AC-3 (Pe) | (500 V) 4 kW |
| Rated Operational Power AC-3 (Pe) | (690 V) 4 kW |
| Rated Operational Power AC-3 (Pe) | (220 / 230 / 240 V) 2.2 kW |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 100 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 20 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 50 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 230 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 65 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 100 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 155 A |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V |
| Rated Insulation Voltage (Ui) | acc. to UL/CSA 600 V |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| Maximum Electrical Switching Frequency | (AC-15) 1200 cycles per hour |
| Maximum Electrical Switching Frequency | (AC-2 / AC-4) 300 cycles per hour |
| Maximum Electrical Switching Frequency | (AC-3) 1200 cycles per hour |
| Maximum Electrical Switching Frequency | (DC-13) 900 cycles per hour |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 230 V |
| Rated Control Circuit Voltage (Uc) | 60 Hz 230 V |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 0.9 W |
| Power Loss | at Rated Operating Conditions AC-3 per Pole 0.18 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 7 ... 22 ms |
| Operate Time | Between Coil De-energization and NO Contact Opening 5 ... 19 ms |
| Operate Time | Between Coil Energization and NC Contact Opening 6 ... 18 ms |
| Operate Time | Between Coil Energization and NO Contact Closing 9 ... 24 ms |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Main Circuit | Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm² |
| Connecting Capacity Main Circuit | Rigid 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Auxiliary Circuit | Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm² |
| Connecting Capacity Auxiliary Circuit | Rigid 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Connecting Capacity Control Circuit | Flexible with Insulated Ferrule 1/2x 0.75 ... 1.5 mm² |
| Connecting Capacity Control Circuit | Rigid 1/2x 0.75 ... 2.5 mm² |
| Wire Stripping Length | Auxiliary Circuit 10 mm |
| Wire Stripping Length | Control Circuit 10 mm |
| Wire Stripping Length | Main Circuit 10 mm |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 |
| Terminal Type | Spring Terminals |
| Product Name | Block Contactor |
Technical UL/CSA
| General Use Rating UL/CSA | (600 V AC) 12 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 1/3 hp |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 2 hp |
| Horsepower Rating UL/CSA | (220 ... 240 V AC) Three Phase 2 hp |
| Horsepower Rating UL/CSA | (240 V AC) Single Phase 1 hp |
| Horsepower Rating UL/CSA | (440 ... 480 V AC) Three Phase 5 hp |
| Horsepower Rating UL/CSA | (550 ... 600 V AC) Three Phase 7.5 hp |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Stranded 1/2x 18-14 AWG |
| Full Load Amps Motor Use | (120 V AC) Single Phase 7.2 A |
| Full Load Amps Motor Use | (200 ... 208 V AC) Three Phase 7.8 A |
| Full Load Amps Motor Use | (220 ... 240 V AC) Three Phase 6.8 A |
| Full Load Amps Motor Use | (240 V AC) Single Phase 8 A |
| Full Load Amps Motor Use | (440 ... 480 V AC) Three Phase 7.6 A |
| Full Load Amps Motor Use | (550 ... 600 V AC) Three Phase 9 A |
Why Proax for ABB AS09-30-01S-26?
Proax is an authorized distributor of ABB AS09-30-01S-26 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Alternate Names | AS093001S26 |
| Pack Size | 1 |
Recommended