  1. Cored Concrete or Block Wall Cable Penetrations: When to Evaluate the Roxtec RS
  2. 1. What Size Is the Opening?
  3. 2. What Is the Cable Diameter?
  4. 3. What Is the Wall Made Of?
  5. 4. What Rating Does the Opening Need?
  6. 5. Do You Need a Sleeve?
  7. 6. How Is the RS Installed?
  8. 7. Is It Available When You Need It?
  9. Putting It Together
  10. Where the Roxtec RS Fits
  11. When to Look Beyond the RS
  12. Checklist: What to Gather Before You Contact Proax
Quick Answer

The Roxtec RS seals one cable or pipe in a round opening. It attaches by expanding in the hole, and its removable layers adapt to the cable diameter. Before choosing it for a cored concrete or block wall, check the hole diameter against the RS size ranges, the cable diameter, the wall construction and the fire, water or gas rating the opening needs. The certified assembly for your wall and Roxtec’s installation instructions decide whether an RS alone, an RS with a sleeve or another Roxtec solution is right.

Opening→Cable Diameter→Wall Type→Rating Needed→Certified Assembly

A question that comes up in live chats and tickets: is the Roxtec RS single seal suitable for a cable passing through a cored concrete or block wall? The Roxtec RS is a round seal for one cable or pipe. It has two halves with removable layers that adapt to the cable, and compression is built into the seal. Whether it suits your wall depends on the opening, the wall construction and the rating you need.

Three Questions Behind This Post
RS Single

Is the RS Right for a Cored Concrete Wall?

Block Wall

Can It Seal a Cable Through Concrete Block?

One Cable

Which RS Size Fits My Cable?

Seven checks before you seal one cable through a wall: opening, cable diameter, wall material, wall depth, rating needed, sleeve and certified assembly

1. What Size Is the Opening?

The RS seals a round opening, and each size has a narrow aperture range, so the hole has to match it. For core-drilled holes, Roxtec’s instructions call for a hole saw of the right diameter, then cleaning the opening and checking its size before installing.

Size finder showing the cable diameter range and required hole for Roxtec RS 25 to RS 150, from 3.6 to 119 mm

Measure the Hole You Have

If the opening is already cored, measure it before you choose a size. An opening that falls between two RS aperture ranges may need re-drilling or a different solution.

2. What Is the Cable Diameter?

Each RS size covers a range of cable diameters. You peel off layers until the two halves meet around the cable with a gap of 0 to 1.0 mm, and the number of layers removed from each half may differ by no more than one.

Measure the Outside Diameter

Use the cable’s overall diameter, including the jacket, not the conductor size.

Centre the Cable

Pull the cable straight and centred through the opening, parallel to the hole or sleeve.

Support Heavy Cables

Support the cable so its weight doesn’t damage the seal or make it sag.

Install Around Existing Cables

The split halves let you fit the RS around a cable that is already pulled.

3. What Is the Wall Made Of?

The RS attaches by expanding against the inside of the hole, so the material around the hole matters. Roxtec’s RS instructions cover core-drilled holes, gypsum structures with added framing, and cast-in, bolted or welded sleeves. They don’t describe hollow concrete block, so confirm the method for block walls with Roxtec before you drill.

Three Common Wall Types
Solid

Cored Concrete

  • Core-Drill to the RS Aperture Range
  • The Seal Expands Against the Hole Wall
  • Check the Hole Is Clean and Sound
  • Check the Certificate Covers Concrete
Hollow

Concrete Block

  • Cores Leave Voids Around the Hole
  • A Solid Section or Sleeve May Be Needed
  • Not Covered in the RS Instructions
  • Confirm the Method With Roxtec
Framed

Gypsum or Stud Walls

  • Add Steel or Timber Framing at the Opening
  • Follow the Gypsum Method in the Instructions
  • Check the Certificate for the Wall Type
  • Confirm the Rating Needed

Not Every Opening Suits the RS

The RS isn’t a universal answer for concrete or block openings. The exact certified assembly and Roxtec’s installation instructions for your wall control the choice.

4. What Rating Does the Opening Need?

Roxtec lists certificates for the RS by rating and by wall construction, including concrete, brickwork, lightweight concrete and gypsum. They cover fire, water tightness, gas tightness and IP or UL/NEMA tightness, and include CSA and UL listings. The certificate you rely on has to match your wall, its thickness and the rating the opening needs.

FireFire Ratings for the Wall
WaterWater Tightness
GasGas Tightness
IP / NEMAIngress Protection

Approvals and certificates can carry amendments or limitations, so read the one that applies to your installation.

5. Do You Need a Sleeve?

Core-Drilled Hole

The seal goes straight into a hole drilled to its aperture range.

Cast-In Sleeve

In concrete, a Roxtec sleeve can be cast into the wall during construction.

Bolted Sleeve

Attached to the structure with suitable sealing and fasteners.

Welded Sleeve

Welded to steel structures.

6. How Is the RS Installed?

StepWhat to Do
1Clean the opening and check its diameter.
2Centre the cable and keep it parallel to the hole.
3Peel off layers for a 0 to 1.0 mm gap around the cable.
4Lubricate the sealing surfaces with Roxtec Lubricant.
5Insert the halves and tighten crosswise in small steps.
6Check that lubricant shows and the layers bulge outward.
7Wait at least 24 hours before loading the cable.
Summarized from the Roxtec RS installation instructions. Always follow the current instructions for your size.
About 1 N·mRS 25 to RS 31
About 4 N·mRS 43 to RS 100
About 7 N·mRS 125 to RS 200
About 17 N·mRS 225 to RS 400

Approximate tightening torques from the Roxtec RS installation instructions.

7. Is It Available When You Need It?

Proax is an authorized Roxtec distributor. RS sizes are ordered by article number, such as RS00100501023 for the RS 50 AISI316, so ask Proax to check the lead time for the size you need.


Putting It Together

Decision guide: check the opening against an RS aperture range, the cable against the size’s range, whether the wall is solid where the seal sits, and whether a certificate covers your wall and rating

Where the Roxtec RS Fits

The RS suits a single cable or pipe through a round opening, where the hole and the wall construction are covered by a Roxtec certificate. Because it splits in two, it can go around a cable that is already in place.

Roxtec RS at a glance: one cable or pipe per seal, 21 sizes from RS 25 to RS 644, 3.6 to 580 mm cable range, 0 to 1 mm layer gap, 24 hours before loading and a spare core for future capacity
01

One Cable

Seals a single cable or pipe in a round opening.

02

Fits Existing Cables

Two halves install around a cable already in place.

03

Adaptable Layers

Peel layers to match the cable diameter.

04

Built-In Compression

Tightening the seal compresses it in the hole.

05

21 Sizes

From RS 25 to RS 644, for cables and pipes up to 580 mm.

06

Certificates by Wall Type

Fire, water, gas and IP listings for set constructions.

Sources: Roxtec RS seal, Roxtec RS installation instructions and Roxtec at Proax.

When to Look Beyond the RS

  • Several Cables Pass Through the Same Opening
  • The Opening Isn’t Round or Falls Between Sizes
  • The Wall Is Hollow Block With No Solid Section
  • No Certificate Covers Your Wall and Rating
  • The Penetration Needs a Different Roxtec Frame or Sleeve

Checklist: What to Gather Before You Contact Proax

A Wall Penetration Review Goes Faster With This Information:

Wall Material and Thickness
Opening Diameter, or the Planned Core Size
Cable or Pipe Outside Diameter
Number of Cables Through the Opening
Rating Needed: Fire, Water, Gas or IP
Who Must Approve the Penetration
Photos of the Wall and Opening
Whether the Cable Is Already Installed
Proax Technical Support

Sealing a Cable Through a Wall?

Send us the wall type, opening size, cable diameter and the rating you need, and our in-house team will help you check Roxtec options and lead times.