TRIO2-DIODE/12-24DC/2X20/1X40 - Redundancy module

Redundancy module, 12 V - 24 V DC, 2 x 20 A, 1 x 40 A

  • Quick and easy installation with Push-in connection technology
  • Save energy
  • Redundant wiring up to the load
  • Permanent monitoring of redundancy
  • Consistent redundancy up to the load
Technical Specifications

DC operation

Nominal input voltage range12 V DC ... 24 V DC
Input voltage range10 V DC ... 30 V DC
Voltage type of supply voltageDC
Reverse polarity protection< yes60 V
Nominal input current (IN)2x 20 A (-25 °C ... 60 °C)
Nominal input current (IN)1x 40 A (-25 °C ... 60 °C)
Maximum current Imax2x 25 A (-25 °C ... 40 °C)
Maximum current Imax1x 50 A (-25 °C ... 40 °C)
Nominal input current (IN)2x 20 A (-25 °C ... 60 °C)
Nominal input current (IN)1x 40 A (-25 °C ... 60 °C)
Transient surge protectionVaristor
Voltage drop, input/output0.5 V

Output data

Efficiency> 97 %
Nominal Output VoltageUIn - 0,5 V
Nominal output current (IN)40 A
Nominal output current (IN)20 A
Derating60 °C ... 70 °C (2.5 %/K)
Power loss nominal load max.10 W (IOUT = 20 A)
Connection in seriesNo

Input

Connection MethodPush-in connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.10 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.6 mm²
Conductor cross section AWG min.12
Conductor cross section AWG max.8
Stripping length15 mm

Output

Connection MethodScrew connection
Conductor cross section, rigid min.0.75 mm²
Conductor cross section, rigid max.16 mm²
Conductor cross section flexible min.0.75 mm²
Conductor cross section flexible max.16 mm²
Conductor cross section AWG min.8
Conductor cross section AWG max.4
Stripping length18 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

Electrical properties

Insulation voltage input, output / housing500 V

Product properties

Product familyTRIO DIODE
MTBF (IEC 61709, SN 29500)82870031 h (25 °C)
MTBF (IEC 61709, SN 29500)50190012 h (40 °C)
MTBF (IEC 61709, SN 29500)26315113 h (60 °C)
LEDNo

Insulation characteristics

Protection classIII
Degree of pollution2

Dimensions

Width41 mm
Height130 mm
Depth115 mm

Installation dimensions

Installation distance right/left0 mm / 0 mm
Installation distance top/bottom50 mm / 50 mm

Mounting

Mounting TypeDIN rail mounting
Assembly instructionsalignable: horizontally 0 mm, vertically 50 mm
Mounting Positionhorizontal DIN rail NS 35, EN 60715

Material specifications

Flammability rating according to UL 94 (housing / terminal blocks)V0
Housing MaterialMetal
Type of housingSteel sheet, zinc-plated
Side element versionAluminum

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)≤ 95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (Operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
Vibration (Operation)15 Hz ... 150 Hz, 2.3g, 90 min.

Standards and Regulations

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard - Electrical safetyIEC 62368-1 (SELV)
Standard – Safety extra-low voltageIEC 62368-1 (SELV) und EN 60204-1 (PELV)

Approvals

UL approvalsUL/C-UL listed UL 508
UL approvalsUL/C-UL Recognized UL 60950-1

EMC data

Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EMC requirements for noise emissionEN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EMC requirements for noise immunityEN 61000-6-2
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU

Electrostatic discharge

Standards/regulationsEN 61000-4-2
Contact discharge4 kV (Test Level 3)
Discharge in air8 kV (Test Level 3)
CommentsCriterion B

Electromagnetic HF field

Standards/regulationsEN 61000-4-3
Frequency Range80 MHz ... 1 GHz
Test field strength10 V/m
Frequency Range1 GHz ... 2 GHz
Test field strength10 V/m
Frequency Range2 GHz ... 3 GHz
Test field strength10 V/m
CommentsCriterion A

Fast transients (burst)

Standards/regulationsEN 61000-4-4
Input2 kV (Test Level 3 - asymmetrical)
Output2 kV (Test Level 3 - asymmetrical)
CommentsCriterion B

Surge voltage load (surge)

Standards/regulationsEN 61000-4-5
Input0.5 kV (Test Level 2 - symmetrical)
Input0.5 kV (Test Level 3 - asymmetrical)
Output0.5 kV (Test Level 1 - symmetrical)
Output0.5 kV (Test Level 1 - asymmetrical)
CommentsCriterion B

Conducted interference

Standards/regulationsEN 61000-4-6
I/O/Sasymmetrical
Frequency Range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V (Test Level 3)

Voltage dips

Standards/regulationsEN 61000-4-11

Emitted interference

Standards/regulationsEN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential

Criteria

Criterion ANormal operating behavior within the specified limits.
Criterion BTemporary impairment to operational behavior that is corrected by the device itself.

Why Proax for Phoenix Contact 2907379?

Proax is an authorized distributor of Phoenix Contact 2907379 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability