CADEN
Cart

EF146-150

Official Distributor

By ABB

SKU
ABBEF146150
MPN
1SAX351001R1101
Weight
0.879 kg
The EF146 is an self-supplied electronic overload relay, which means no extra external supply is needed. It offers reliable and fast protection for motors in the event of overload or phase failure. Easy to use like a thermal overload relay and compatible with standard motor applications, the electronic overload relay is convincing, above all, due to its wide setting range, high accuracy, high operational temperature range and the possibility to select a trip class (10E, 20E, 30E). Further features are the temperature compensation, trip contact (NC), signal contact (NO), automatic- or manual reset selectable, trip-free mechanism, STOP- and Test function and a trip indication. The overload relays are connected directly to the contactors. The EF65, EF96 and EF146 have ATEX and IECEx certification 1) 1) ATEX is valid for products produced from week 42, 2014. IECEx is valid for products produced from week 15, 2017.
Technical Specifications

Dimensions

Product Net Width89.05 mm
Product Net Height150.4 mm
Product Net Depth / Length105.2 mm
Product Net Weight0.879 kg

Technical

Setting range54 ... 150 A
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC
Rated Operational VoltageMain Circuit 1000 V AC
Rated Operational Current (Ie)150 A
Rated Frequency (f)Auxiliary Circuit 50 Hz
Rated Frequency (f)Auxiliary Circuit 60 Hz
Rated Frequency (f)Auxiliary Circuit DC
Rated Frequency (f)Main Circuit 50 Hz
Rated Frequency (f)Main Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp)Auxiliary Circuit 6 kV
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Rated Insulation Voltage (Ui)1000 V
Number of Poles3P
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (Ith)Auxiliary Circuit NC 6 A
Conventional Free-air Thermal Current (Ith)Auxiliary Circuit NO 6 A
Rated Operational Current AC-15 (Ie)(240 V) NC 3 A
Rated Operational Current AC-15 (Ie)(240 V) NO 3 A
Rated Operational Current AC-15 (Ie)(400 V) NC 1.1 A
Rated Operational Current AC-15 (Ie)(400 V) NO 1.1 A
Rated Operational Current AC-15 (Ie)(500 V) NC 0.75 A
Rated Operational Current AC-15 (Ie)(500 V) NO 0.75 A
Rated Operational Current DC-13 (Ie)(125 V) NC 0.55 A
Rated Operational Current DC-13 (Ie)(125 V) NO 0.5 A
Rated Operational Current DC-13 (Ie)(24 V) NC 1.5 A
Rated Operational Current DC-13 (Ie)(24 V) NO 1.5 A
Rated Operational Current DC-13 (Ie)(250 V) NC 0.27 A
Rated Operational Current DC-13 (Ie)(250 V) NO 0.27 A
Rated Operational Current DC-13 (Ie)(60 V) NC 0.55 A
Rated Operational Current DC-13 (Ie)(60 V) NO 0.55 A
Degree of ProtectionHousing IP20
Degree of ProtectionMain Circuit Terminals IP10
Pollution degree3
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitFlexible 1/2x 0.75 ... 2.5 mm²
Connecting Capacity Auxiliary CircuitRigid 1/2x 1 ... 4 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1x 10 ... 70 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 2x 10 ... 35 mm²
Connecting Capacity Main CircuitFlexible with Insulated Ferrule 1x 10 ... 70 mm²
Connecting Capacity Main CircuitFlexible with Insulated Ferrule 2x 2 ... 35 mm²
Connecting Capacity Main CircuitFlexible 1x 10 ... 70 mm²
Connecting Capacity Main CircuitFlexible 2x 10 ... 35 mm²
Connecting Capacity Main CircuitRigid 1x 10 ... 95 mm²
Connecting Capacity Main CircuitRigid 2x 10 ... 35 mm²
Tightening torqueAuxiliary Circuit 0.8 ... 1.2 N·m
Tightening torqueMain Circuit 10 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm
Wire Stripping LengthMain Circuit 20 mm
Recommended Screw DriverAuxiliary Circuit Pozidriv 2
Recommended Screw DriverMain Circuit Hexagon 4
Mounting Position1 ... 6
Power Lossat Rated Operating Conditions per Pole 0.204 ... 1.575 W
Suitable forAF116
Suitable forAF140
Suitable forAF146
StandardsIEC/EN 60947-1
StandardsIEC/EN 60947-4-1
StandardsIEC/EN 60947-5-1
StandardsUL 60947-1
StandardsUL 60947-4-1

Technical UL/CSA

Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600
Contact Rating UL/CSA(NC:) Q600
Contact Rating UL/CSA(NO:) B600
Contact Rating UL/CSA(NO:) Q600
Connecting Capacity Main Circuit UL/CSAFlexible 1x 6-00 AWG
Connecting Capacity Main Circuit UL/CSAFlexible 2x 6-2 AWG
Connecting Capacity Main Circuit UL/CSAStranded 2x 6-2 AWG
Connecting Capacity Main Circuit UL/CSAStranded 1x 6-00 AWG
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 18-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSAStranded 1/2x 18-10 AWG
Tightening Torque UL/CSAAuxiliary Circuit 7 ... 1 in·lb
Tightening Torque UL/CSAMain Circuit 70 in·lb

ABB EcoSolutions

ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetUL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions1SAC200283H0001
Environmental Information1SAC200100H0001
Environmental Product Declaration - EPD1SAC200236H0001

Why Proax for ABB EF146-150?

Proax is an authorized distributor of ABB EF146-150 and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate NamesEF146150
Pack Size1
Recommended

CAD$684.41

Not in stock

Request lead time or order—we'll ensure quick delivery

ABB Availability