By ABB
SKU
MPN
1SVR740712R1200
Weight
0.163 kg
The CM-MSS.41P belongs to the CM-MSS thermistor motor protection relay range. It operates with a rated control supply voltage of 24 - 240 V AC / DC and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. It features one sensor circuit to monitor PTC temperature sensors and works according to the closed-circuit principle. The sensor circuit of this CM-MSS.41P is short-circuit (configurable), as well as interrupted-wire monitored and can be reset automatically, manually or remotely after the failure has been removed. This protection relay is certified according to the ATEX directive 94/9/EC and is equipped with a reset / test button. The non-volatile fault storage and the short circuit detection can be enabled/disabled via DIP switches. A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers maintenance free Easy Connect Technology with push-in terminals.
Technical Specifications
Dimensions
Product Net Width | 22.5 mm |
Product Net Height | 85.6 mm |
Product Net Depth / Length | 103.7 mm |
Product Net Weight | 0.13 kg |
Technical
Function | 1 sensor circuit |
Function | Auto, manual or remote reset |
Function | ATEX approved |
Function | Dynamic interrupted wire detection |
Function | Short-circuit detection, configurable |
Function | Non-volatile fault storage, configurable |
Rated Control Supply Voltage (Us) | 24 ... 240 V AC/DC |
Rated Operational Voltage | Auxiliary Circuit 250 V AC |
Rated Frequency (f) | Supply Circuit 15 ... 400 Hz |
Output | 2 c/o (SPDT) contacts |
Terminal Type | Screwless Terminals |
Rated Operational Current AC-12 (Ie) | (230 V) 4 A |
Rated Operational Current AC-15 (Ie) | (230 V) 3 A |
Rated Operational Current DC-12 (Ie) | (24 V) 4 A |
Rated Operational Current DC-13 (Ie) | (24 V) 2 A |
Minimum switching capacity | 24 V |
Minimum switching capacity | 10 mA |
Rated Impulse Withstand Voltage (Uimp) | Output Circuit 1 / Output Circuit 2 4 kV |
Rated Impulse Withstand Voltage (Uimp) | Output Circuit 4 kV |
Rated Insulation Voltage (Ui) | Measuring Circuit / Output Circuit 300 V |
Rated Insulation Voltage (Ui) | Output Circuit 1 / Output Circuit 2 300 V |
Rated Insulation Voltage (Ui) | Supply Circuit / Measuring Circuit 300 V |
Rated Insulation Voltage (Ui) | Supply Circuit / Output Circuit 300 V |
Degree of Protection | Housing IP50 |
Degree of Protection | Terminals IP20 |
Overvoltage category | III |
Pollution degree | 3 |
Short-Circuit Protective Devices | Output Circuit NC - F Type Fuses 10 A |
Short-Circuit Protective Devices | Output Circuit NO - F Type Fuses 10 A |
Electrical Durability | AC-12 100000 cycle |
Mechanical Durability | 30000000 cycle |
Connecting Capacity | Flexible 2x 0.5 ... 1.5 mm² |
Connecting Capacity | Rigid 2x 0.5 ... 1.5 mm² |
Wire Stripping Length | 8 mm |
Mounting Position | 1 ... 6 |
Mounting on DIN Rail | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
Standards | CAN/CSA C22.2 No.14 |
Standards | EN 50495 |
Standards | IEC/EN 63000 |
Standards | IEC/EN 60079-7 |
Standards | IEC/EN 60947-5-1 |
Standards | IEC/EN 60947-8 |
Standards | UL 508 |
Technical UL/CSA
Maximum Operating Voltage UL/CSA | Output Circuit 300 V AC |
Contact Rating UL/CSA | B300 |
Connecting Capacity UL/CSA | Flexible 2x 18-16 AWG |
Connecting Capacity UL/CSA | Rigid 2x 20-16 AWG |
Pilot Duty UL/CSA | B300 |
Flammability According to UL94 | V-0 |
Why Proax for ABB CM-MSS.41P?
Proax is an authorized distributor of ABB CM-MSS.41P and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Alternate Names | CMMSS41P |
Pack Size | 1 |
Recommended