1328357
SKU
PHX1328357
MPN
PLC-RSC- 24DC/1/CB1-6
Weight
0.044 kg
PLC-RSC- 24DC/1/CB1-6 - Relay module
Combination of relay interface and electronic fuse protection on overall width: 6.2 mm, individual configuration of the nominal current (1 A ... 6 A), adjustable output characteristic, active signal output, easy system integration, with screw connection
Documents
Technical Specifications
Notes
| Notes on operation | Repeated hard short circuits can reduce the melting integral of the integrated backup fuse. |
| Notes on operation | A suitable flyback diode must be used when switching inductive loads |
| Notes on operation | If the DIP switches are not covered by an adjacent module, the PLC-ATP partition plate must be used for ESD protection |
| Notes on operation | The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2. |
| Notes on operation | The PLC-ATP separating plate should be installed for safe isolation between adjacent modules |
| Notes on operation | Do not connect adjacent channels to SELV/ PELV and voltages dangerous to the touch. |
| Notes on operation | At least one functional insulation against adjacent modules is complied with in the support rail direction.If the application has higher requirements on the insulation (basic or reinforced insulation), then these must be realized through suitable measures (e. g., partition plates). |
| Notes on operation | Do not use to separate SELV / PELV circuits from other circuits, because safe isolation is not guaranteed. |
Product properties
| Product family | PLC-INTERFACE |
| Application | with integrated electronic circuit breaker |
| Operating mode | 100% operating factor |
Insulation characteristics: Air clearances and creepage distances
| Insulation | Functional insulation |
| Overvoltage category | I |
| Pollution degree | 2 |
Electrical properties
| Maximum power dissipation for nominal condition | < 1.6 W |
| Fuse | electronic |
Input data
| Operating voltage (UN) | 24 V DC (UIn+ - UA2) |
| Operating voltage range (DC) | 19.2 V DC ... 30 V DC (UIn+ - UA2) |
| Current consumption (In+) | 12 mA |
| Tripping current (IN) | 1 A (adjustable) |
| Tripping current (IN) | 2 A (adjustable) |
| Tripping current (IN) | 3 A (adjustable) |
| Tripping current (IN) | 4 A (adjustable) |
| Tripping current (IN) | 5 A (adjustable) |
| Tripping current (IN) | 6 A (preset) |
| Measuring tolerance | ± 15 % |
| Power dissipation | 0.06 W (Without load, A1 low) |
| Power dissipation | 0.4 W (Without load, A1 high) |
| Power dissipation | < 1.6 W (Normal operation) |
Switching: Switching input A1
| Nominal switch-on voltage | 24 V (UA1 - UA2) |
| Switch-on voltage range | 11 V ... 30 V (UA1 - UA2) |
| Switch-off voltage range | 0 V ... 2 V (UA1 - UA2) |
| Current consumption (IA1) | 4 mA (24 V) |
| Switch-on time | 36 ms |
| Switch-off time | 10 ms |
| Switching frequency | ≤ 2.5 Hz |
Load circuit: Power MOSFET switching output (positive switching)
| Voltage drop | 0.16 V (6 A, UIn+ - Uout) |
| Short-circuit switching capacity | 100 A DC |
| Short-circuit switching capacity | 300 A DC (<5 short circuits) |
| Required backup fuse | Only required if Imax of power supply unit > short-circuit switching capacity. Integrated failsafe element |
| Fail-safe element | 15 A |
| Surge voltage protection | > 33 V |
| Max. capacitive load | 12000 µF (Depending on the current setting and the short-circuit current available) |
| Shutdown time () | ≤ 15 ms (Short circuit ≥3 x IN) |
| Shutdown time () | 0.1 s (Short circuit 2 ... <3 x IN) |
| Shutdown time () | 1 s (Short circuit 1.5 ... <2 x IN) |
| Shutdown time () | 4 s (Short circuit 1.1 ... <1.5 x IN) |
| Undervoltage switch-off | ≤ 17.8 V (active) |
| Undervoltage switch-off | ≥ 19 V (inactive) |
| Overvoltage switch-off | ≥ 30.5 V (active) |
| Overvoltage switch-off | ≤ 29.5 V (inactive) |
| Waiting time | 5 s (Between the pulses) |
| Number | 5 (Start attempts in hiccup mode) |
Signal: Feedback contact
| Output Voltage | UIn+ - 0.7 V (high level) |
| Current (Maximum current) | ≤ 20 mA |
| State condition (Normal operation) | low |
| State condition (Error) | high (Fuse has blown) |
| State condition (Hiccup mode) | high (After all 5 start attempts have been completed) |
Connection data
| Connection Method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section rigid (2 conductors with same cross section) | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section flexible (2 conductors with same cross section) | 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) |
| Conductor cross section AWG | 30 ... 12 |
| Tightening torque | 0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing)) |
Item dimensions
| Width | 6.2 mm |
| Height | 80 mm |
| Depth | 94 mm |
Ambient conditions
| Degree of Protection | IP20 |
| Degree of protection (Installation location) | ≥ IP54 |
| Ambient Temperature (Operation) | -25 °C ... 55 °C (Observe derating in the connected state) |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Altitude | ≤ 2000 m (Without derating) |
| Altitude | ≤ 3000 m (With correction factor for ambient temperature (operation) x 0.88) |
| Permissible humidity (operation) | 95 % |
UL, USA/Canada
| Identification | UL 2367 |
| Identification | UL 60947-1 |
| Identification | UL 60947-5-1 |
| Identification | CSA C22.2 No. 60947-1 |
| Identification | CSA C22.2 No. 60947-5-1 |
UL data
| Operating mode | Indoor use |
Electromagnetic compatibility (EMC)
| Standards/regulations | EN 61000-6-2 |
| Standards/regulations | EN 61000-6-3 |
Air clearances and creepage distances
| Standards/regulations | IEC 60664 |
Mounting
| Mounting Type | DIN rail mounting |
| Assembly note | in rows with zero spacing |
| Mounting Position | any |
Why Proax for Phoenix Contact 1328357?
Proax is an authorized distributor of Phoenix Contact 1328357 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |