Safety switch, 4-p. 415V AC23 160A, 88kW. Mounted auxiliary contact: 2NO1NC. Plastic enclosure. IP65. Black Pistol handle. Interlocked cover. Defeatable interlocking. The enclosure in the OT series is using a rigid glass reinforced polycarbonate enclosure. The enclosure is UV protected, protected against low-pressure water jets (IP65), and hence built for outdoor and indoor use. The cable entries knock out types for II-flanges. Cables can be inserted from top and bottom. The handle is padlockable and made for three padlocks. The cover is interlocked. The interlocking can be defeated. PE terminals included.
Technical Specifications
Dimensions
| Product Net Width | 380 mm |
| Product Net Height | 560 mm |
| Product Net Depth / Length | 180 mm |
| Product Net Weight | 7.5 kg |
Technical
| Cable Entry Position | Top/Bottom |
| Cable Outlets Per Side | II-flange / II-flange |
| Connecting Capacity Main Circuit | Hole Diameter 8 mm |
| Connecting Capacity Main Circuit | Screw Clamp / PE Terminal 2pc,10 ... 70 mm² |
| Conventional Thermal Current (Ithe) | Fully Enclosed 160 A |
| Degree of Protection | acc. to IEC 60529 IP65 |
| Enclosure Material | Plastic |
| Enclosure Type | Fibox |
| Handle color | Black |
| Handle Type | Pistol handle |
| Impact Resistance Rating | Housing IK08 |
| Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
| Mounted Auxiliary Contacts | 2 NO, 1 NC |
| Neutral Type | Switchable Neutral |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 2 |
| Number of Poles | 4P |
| Pollution degree | 3 |
| Position of Line Terminals | Top In - Bottom Out |
| Rated Conditional Short-Circuit Current (Inc) | 40.5 kA |
| Rated Insulation Voltage (Ui) | 750 V |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 160 A |
| Rated Operational Current AC-22A (Ie) | (500 V) 160 A |
| Rated Operational Current AC-22A (Ie) | (690 V) 160 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 160 A |
| Rated Operational Current AC-23A (Ie) | (500 V) 160 A |
| Rated Operational Current AC-23A (Ie) | (690 V) 160 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 80 kW |
| Rated Operational Power AC-23A (Pe) | (500 V) 112 kW |
| Rated Operational Power AC-23A (Pe) | (690 V) 144 kW |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (1000 V AC) 30 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 8 kA |
| Recommended Screw Driver | Main Circuit M8 |
| Standards | IEC 60947-1, -3 |
| Terminal Type | Bolt |
| Tightening torque | Main Circuit 6 N·m |
Technical UL/CSA
| Recommended Screw Driver | Main Circuit M8 |
| Tightening torque | Main Circuit 6 N·m |
Why Proax for ABB OT160EVFCC4T?
Proax is an authorized distributor of ABB OT160EVFCC4T and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended