Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
RAD-DO8-IFS
Weight
0.179 kg

RAD-DO8-IFS - I/O extension module

Radioline - I/O extension module, 8 digital transistor outputs (30.5 V DC/200 mA)

  • Easy startup via thumbwheel
  • Channel-to-channel electrical isolation
  • Extended temperature range of -40 °C … +70 °C
  • Easy module replacement even during operation (hot swap)
  • 8 transistor outputs (30.5 V DC/200 mA)
  • Approved for use in zone 2
Technical Specifications

Product properties

MTTF1594 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
MTTF600 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
MTTF230 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)

Insulation characteristics

Overvoltage categoryII
Degree of pollution2

Electrical properties

Rated Insulation Voltage60 V (In accordance with EN/IEC 60079-7)
Electrical isolation50 V (Rated insulation voltage (in each case between channel groups 1...4 and 5...8 / TBUS supply, reinforced insulation in accordance with EN 61010))
Electrical isolation300 V (Rated insulation voltage (to adjacent devices, basic insulation in accordance with EN/IEC 61010))
Test voltage for digital I/Os1.5 kV AC (50 Hz, 1 min.)
Maximum power dissipation for nominal condition0.528 W
Transient surge protectionYes

Supply

Supply Voltage Range19.2 V DC ... 30.5 V DC (DIN rail connector)
Max. current consumption≤ 22 mA (At 24 V DC, at 25°C)

Digital

Output nameTransistor output, active
Number of Outputs8
Contact switching typeTransistor
Supply Voltage Range12 V DC ... 30.5 V DC (for digital outputs)
Maximum Switching Voltage30.5 V DC
Max. switching current0.2 A (per channel)
Output current when switched off≤ 300 µA
Output voltage when switched off≤ 2 V
Maximum switching frequency10 Hz
Behavior of the outputs (adjustable via DIP switch)Hold / Reset

Connection data

Tightening torque0.5 Nm ... 0.6 Nm
Tightening torque5 lbf-in. ... 7 lbf-in.
Connection MethodScrew connection
Stripping length7 mm
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14

Signaling

Status displayGreen LED (supply voltage, PWR)
Status displayGreen LED (bus communication, DAT)
Status displayRed LED (periphery error, ERR)
Status displayYellow LED (digital output, DO1)
Status displayYellow LED (digital output, DO2)
Status displayYellow LED (digital output, DO3)
Status displayYellow LED (digital output, DO4)
Status displayYellow LED (digital output, DO5)
Status displayYellow LED (digital output, DO6)
Status displayYellow LED (digital output, DO7)
Status displayYellow LED (digital output, DO8)

Dimensions

Width17.5 mm
Height113 mm
Depth114.5 mm

Material specifications

Color (Housing)gray (RAL 7042)
Material (Housing)PA 6.6-FR
Flammability rating according to UL 94V0

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 70 °C
Ambient Temperature (Operation)-40 °F ... 158 °F
Ambient temperature (storage/transport)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °F ... 185 °F
Altitude2000 m
Permissible humidity (operation)20 % ... 85 %
Permissible humidity (storage/transport)20 % ... 85 %
Shock16g, 11 ms
Vibration (Operation)in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz

CE

CertificateCE-compliant

UKCA

CertificateUKCA-compliant

ATEX

Identification II 3 G Ex ec IIC T4 Gc
CertificateIBExU 15 ATEX B008 X
NotePlease follow the special installation instructions in the documentation!

IECEx

IdentificationEx ec IIC T4 Gc
CertificateIECEx IBE 13.0019X

EAC Ex

Identification2Ex nA nC IIC T4 Gc X
CertificateRU C-DE.HB49.B.00033/20

UL, USA/Canada

Identification508 Listed
IdentificationClass I, Div. 2, Groups A, B, C, D T4A
IdentificationClass I, Zone 2, IIC T4

CCC / China-Ex

IdentificationEx ec IIC T4 Gc
Certificate2022122310115625

Corrosive gas test

IdentificationISA-S71.04-1985 G3 Harsh Group A

EMC data

Noise immunityEN 61000-6-2
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Noise emissionEN 61000-6-4

Standards and Regulations

Standard designationEMC Directive 2014/30/EU
Standards/specificationsEN 61000-6-2
Standard designationEMC Directive 2014/30/EU
Standards/specificationsEN 61000-6-4
Standard designationEx Directive (ATEX)
Standards/specificationsEN 60079-0
Standard designationEx Directive (ATEX)
Standards/specificationsEN 60079-15

Mounting

Mounting TypeDIN rail mounting
Assembly instructionson standard DIN rail NS 35 in accordance with EN 60715
Mounting Positionany
Accessories

Why Proax for Phoenix Contact 2902811?

Proax is an authorized distributor of Phoenix Contact 2902811 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Pack Size1
Recommended

Available for order

Phoenix Contact Availability