2882569
SKU
PHX2882569
MPN
S-PT-1X2-24DC-1/2"
Weight
0.425 kg
Series S-PT
S-PT-1X2-24DC-1/2" - Surge protection device
Surge protection in the IP67 screw-on module for measuring sensors, direct mounting with 1/2" NPT outer thread, cable gland for the signal cable, two-stage protective circuit. HART-compatible.
- Easiest field mounting with standardized thread
- Versatile in use with universal protective circuit
- Use under extreme ambient conditions with robust design
Technical Specifications
Notes
| Notes on operation | When the bridge is disconnected, the shield connection is indirectly connected to the housing or reference potential. |
Product properties
| Product family | SURGETRAB |
| IEC test classification | C1 |
| IEC test classification | C2 |
| IEC test classification | C3 |
| IEC test classification | D1 |
| Type | Screw-in module |
| Number of Positions | 3 |
| Surge protection fault message | none |
| Wire pairs per module | 1 |
Insulation characteristics
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Nominal voltage UN | 24 V DC |
Connection data
| Connection Method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.6 Nm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 16 |
Dimensions
| Width | 33.5 mm |
| Height | 33.5 mm |
| Depth | 148 mm |
Material specifications
| Color | Steel / stainless steel |
| Color | black (RAL 9005) |
| Housing Material | Zinc die-cast, surface bronzed and nickel-plated |
Mechanical data
| Open side panel | No |
Protective circuit
| Direction of action | Line-Line & Line-Earth Ground |
| Maximum continuous voltage UC | 40 V DC |
| Maximum continuous voltage UC | 28 V AC |
| Rated current | 450 mA (55 °C) |
| Operating effective current IC at UC | ≤ 10 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In (8/20) µs (line-line) | 10 kA |
| Nominal discharge current In (8/20) µs (line-ground) | 10 kA (per path) |
| Nominal discharge current In (8/20) µs (shield-ground) | 10 kA (optional) |
| Pulse discharge current Iimp (10/350) µs | 1 kA |
| Total discharge current Itotal (8/20) µs | 20 kA |
| Total discharge current Itotal (10/350) µs | 2 kA |
| Max. discharge current Imax (8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax (8/20) µs maximum (line-earth) | 10 kA (per path) |
| Discharge surge current Imax (8/20) µs maximum (shield-ground) | 10 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 23 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
| Nominal pulse current Ian (10/1000) µs (shield-ground) | 100 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 55 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V (Direct grounding) |
| Output voltage limitation at 1 kV/µs (shield-ground) spike | ≤ 600 V (optional) |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 55 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 450 V (Direct grounding) |
| Residual voltage at In (conductor-conductor) | ≤ 55 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 65 V |
| Voltage protection level Up (line-line) | ≤ 80 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up (line-earth) | ≤ 450 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up (shield-ground) | ≤ 600 V (C2 - 10 kV / 5 kA) |
| Voltage protection level Up static (line-line) | ≤ 50 V (C2 - 10 kV / 5 kA) |
| Response time tA (line-line) | ≤ 1 ns |
| Response time tA (line-earth) | ≤ 100 ns |
| Response time tA (shield-ground) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 1.5 MHz / 50 Ω) |
| Input attenuation aE, sym. | typ. 0.2 dB (≤ 300 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 6 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 2 MHz |
| Resistance per path | 2.2 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C2 - 10 kV / 5 kA |
| Impulse durability (line-line) | D1 - 1 kA |
| Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
| Impulse durability (line-earth) | D1 - 1 kA |
| Impulse durability (shield-ground) | C2 - 10 kV/5 kA |
| Impulse durability (shield-ground) | D1 - 1 kA |
Ambient conditions
| Degree of Protection | IP67 |
| Ambient Temperature (Operation) | -40 °C ... 85 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl) |
Air clearances and creepage distances
| Standards/regulations | IEC 60664-1 / VDE 0110-1 |
| Standards/specifications | IEC 61643-21 |
| Note | 2002 |
Mounting
| Mounting Type | direct screw connection |
Why Proax for Phoenix Contact 2882569?
Proax is an authorized distributor of Phoenix Contact 2882569 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |
Recommended