Proax

Currency
0 Items
proax logo
Cart
Phoenix ContactOfficial Distributor

By Phoenix Contact

SKU
MPN
2882462
Weight
0.1 kg
This product has been discontinued and replaced with PLT-SEC-T3-3S-230-P
Series PT

PT 4-PE/S-230AC-ST - Type 3 surge protection plug

Type 3 arrester replacement plug (device protection) for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE).

Technical Specifications

Product properties

TypeMale
Number of Positions4
Surge protection fault messageoptical
Arrester can be tested with CHECKMASTER from software version:From SW rev. 3.2
IEC test classificationIII
IEC test classificationT3
EN typeT3

Connection data

Connection MethodScrew connection (in connection with the base element)

Dimensions

Width35.4 mm
Height45 mm
Depth52 mm
Horizontal pitch2 Div.
Complete module width35.4 mm
Complete module height90 mm
Complete module depth65.5 mm

Material specifications

Flammability rating according to UL 94V0
Housing MaterialPA 6.6

Protective circuit

Direction of action3L-N & N-PE
Nominal frequency fN50 Hz
Nominal frequency fN60 Hz
Maximum continuous voltage UC335 V AC (255 V AC / N-PE)
Maximum continuous operating voltage UC (L-N)335 V AC
Maximum continuous operating voltage UC (N-PE)255 V AC
Rated load current IL26 A (30 °C)
Residual current IPE≤ 2.5 µA
Nominal discharge current In (8/20) µs (L-N)1.5 kA (per channel)
Nominal discharge current In (8/20) µs (L-PE)1.5 kA (per channel)
Nominal discharge current In (8/20) µs (N-PE)1.5 kA
Maximum discharge current Imax (8/20) µs (L-N)4.5 kA (10 kA/N-PE)
Maximum discharge current Imax (8/20) µs (L-PE)4.5 kA
Maximum discharge current Imax (8/20) µs (N-PE)10 kA (N-PE)
Voltage protection level Up (L-N)≤ 1.2 kV
Voltage protection level Up (L-PE)≤ 1.5 kV
Voltage protection level Up (N-PE)≤ 1.5 kV
Residual voltage at In≤ 1.2 kV
Response time tA (L-N)≤ 25 ns
Response time tA (L-PE)≤ 100 ns
Response time tA (N-PE)≤ 100 ns
Max. required back-up fuse25 A (gL)
Max. required back-up fuse25 A (MCB B/C)
Short-circuit withstand capability IP with max. backup fuse (r.m.s.)1.5 kA

Ambient conditions

Degree of ProtectionIP20
Ambient Temperature (Operation)-40 °C ... 85 °C

Air clearances and creepage distances

Standards/regulationsDIN VDE 0110-1 / IEC 60664-1

Standards

Standards/regulationsIEC 61643-1
Standards/regulationsEN 61643-11/A11
Standards/regulationsUL 1449
Standards/specificationsIEC 61643-1
Note2005
Standards/specificationsEN 61643-11/A11
Note2007
Standards/specificationsUL 1449
Noteed. 2

Mounting

Mounting Typeon base element

Why Proax for Phoenix Contact PT 4-PE/S-230AC-ST?

Proax is an authorized distributor of Phoenix Contact PT 4-PE/S-230AC-ST and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.

Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!

Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information

Alternate NamesPT4PES230ACST
Pack Size1
Recommended

Available for order