2910357
SKU
PHX2910357
MPN
VAL-US-120/65/2+0-FM
Weight
0.305 kg
This product is Not Cancellable/Not Returnable
Series VAL-US
VAL-US-120/65/2+0-FM - Type 1 surge protection device
Surge protective device, two channel with remote indicator contact for 120/240 V split phase AC, 3-wire.
- With floating remote indication contact
- UL open terminal listed SPD
- Thermal disconnect device for each individual plug
- Mechanical coding of all slots
- Optical, mechanical status indication for the individual arresters
- Pluggable
Technical Specifications
Product properties
| Product family | VALVETRAB US |
| IEC test classification | I / II |
| IEC test classification | T1 / T2 |
| EN type | T1 / T2 |
| IEC power supply system | TN-C |
| Type | DIN rail module, two-section, divisible |
| Number of Positions | 2 |
| Surge protection fault message | Optical, remote indicator contact |
Insulation characteristics
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Nominal frequency fN | 50 Hz (60 Hz) |
Indicator/remote signaling
| Connection name | Remote fault indicator contact |
| Switching function | Changeover contact |
| Operating Voltage | 5 V AC ... 250 V AC |
| Operating Voltage | 30 V DC |
| Operating current | 5 mA AC ... 1.5 A AC |
| Operating current | 1 A DC |
Connection data
| Connection Method | Screw connection |
| Screw thread | M5 |
| Tightening torque | 4.5 Nm (1.5 mm² ... 16 mm²) |
| Tightening torque | 4.5 Nm (25 mm² ... 35 mm²) |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section rigid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
Remote fault indicator contact
| Connection Method | Screw connection |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section rigid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Dimensions
| Width | 35.6 mm |
| Height | 96.8 mm |
| Depth | 77.5 mm (incl. DIN rail 7.5 mm) |
| Horizontal pitch | 2 Div. |
Material specifications
| Color | black (RAL 9005) |
| Flammability rating according to UL 94 | V-0 |
| CTI value of material | 600 |
| Insulating material | PA 6.6/PBT |
| Material group | I |
| Housing Material | PA 6.6 |
| Housing Material | PBT |
Protective circuit
| Mode of protection | L-PEN |
| Direction of action | 2L-GND |
| Nominal voltage UN | 120/240 V AC (TN-C) |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC (L-PEN) | 175 V AC |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 0.8 mA |
| Nominal discharge current In (8/20) µs | 20 kA |
| Nominal discharge current In (8/20) µs (L-PEN) | 12.5 kA |
| Total discharge current Itotal (10/350) µs | 25 kA |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 0.8 kV |
| Residual voltage Ures | ≤ 0.8 kV (at In) |
| Residual voltage Ures | ≤ 0.75 kV (at 10 kA) |
| Residual voltage Ures | ≤ 0.65 kV (at 5 kA) |
| Residual voltage Ures | ≤ 0.5 kV (at 3 kA) |
| TOV behavior at UT | 208 V AC (5 s / withstand mode) |
| TOV behavior at UT | 240 V AC (120 min / safe failure mode) |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with V-type through wiring | 80 A (gG) |
| Max. backup fuse with branch wiring | 160 A (gG) |
Ambient conditions
| Degree of Protection | IP20 (only when all terminal points are used) |
| Ambient Temperature (Operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (Operation) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
UL specifications
| Maximum continuous operating voltage MCOV (L-L) | 350 V AC |
| Maximum continuous operating voltage MCOV (L-G) | 175 V AC |
| Short-circuit current rating (SCCR) | 200 kA |
| Voltage protection rating VPR (L-L) | 1200 V |
| Voltage protection rating VPR (L-G) | 700 V |
| UL type | type 1 |
| Nominal discharge current In | 20 kA |
| Maximum Surge Current per Phase | 65 kA (acc. IEC61643-1) |
| Maximum Surge Current per Phase | 80 kA (acc. NEMA LS1) |
| Mode of protection | L-L |
| Mode of protection | L-G |
| Nominal Voltage | 120/240 V AC (Split phase) |
| Power distribution system | Split phase |
| Nominal frequency | 50/60 Hz |
| SPD Type | 1 |
UL indicator/remote signaling
| Operating Voltage | 125 V AC |
| AC operating current | 1 A AC |
UL connection data
| Tightening torque | 30 lbf-in. |
| Conductor cross section AWG | 14 ... 2 |
Air clearances and creepage distances
| Standards/regulations | EN 60664-1 / EN 61643-11 |
| Standards/specifications | IEC 61643-11 |
| Note | 2011 |
| Standards/specifications | EN 61643-11 |
| Note | 2012 |
Mounting
| Mounting Type | DIN rail: 35 mm |
Accessories
Why Proax for Phoenix Contact 2910357?
Proax is an authorized distributor of Phoenix Contact 2910357 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 1 |