SKU
MPN
TC-2D37SUB-DO16-F&G-AR-UNI
Weight
1.521 kg
Series TC
TC-2D37SUB-DO16-F&G-AR-UNI - Module carrier
Universal Termination Carrier for redundantly connecting 16 PSR-ETP modules to digital output cards, via two D-SUB connectors, 37-pos. (1:1 connection). Solution for Fire & Gas (F&G) applications
- Mechanically decoupled, passive PCB
- Robust aluminum profile with integrated DIN rail
- Side parts with integrated end clamps
- Redundant D-SUB pin strip system connection, 37-pos. (1:1 connection)
- Simple or redundant supply, decoupled from diode, protected against polarity reversal
- Error message in the event of power supply failure or fuse fault
- Relay output (N/O contact, floating) and flashing LED for error message
- Undervoltage monitoring at input at < 18 V DC
- Suitable for safe state on applications
- Cable sets for signal connection are not supplied as standard and must be ordered separately
Technical Specifications
Notes
Notes on operation | For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Insulation characteristics
Insulation | Basic insulation |
Insulation characteristics: Air clearances and creepage distances
Insulation | Basic insulation |
Electrical properties
Max. permissible current | 1 A (Signal/channel) |
Nominal voltage UN | < 50 V DC (Per signal/channel) |
Air clearances and creepage distances
Rated Insulation Voltage | 50 V |
Rated surge voltage | 0.5 kV |
Supported controller universal
Suitable I/O card | universal |
Supply
Designation | Device supply |
Fuse | 2.5 A on PCB, slow-blow (replaceable) |
Input voltage range | 21.1 V DC ... 26.4 V DC |
Input Current | ≤ 2 A |
Redundant supply | yes, decoupled from diodes |
Polarization and surge protection | Yes |
Output name | Switching output |
Contact switching type | 1 N/C contact (alarm = open) |
Power supply
Connection Method | Screw connection |
Stripping length | 7 mm |
Number of Connections | 1 |
Number of Positions | 6 |
Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
Conductor cross section AWG | 24 ... 12 |
Controller level
Connection Method | D-SUB pin strip |
Number of Connections | 2 |
Number of Positions | 37 |
Signaling
Status display | 2 x red LED (error) |
Status display | 2x green LEDs (PWR1 and PWR2) |
Dimensions
Width | 304 mm |
Height | 170 mm |
Depth | 159.5 mm |
Material specifications
Flammability rating according to UL 94 | V0 |
Ambient conditions
Degree of Protection | IP00 |
Ambient Temperature (Operation) | -20 °C ... 60 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Shock | 15g, according to IEC 60068-2-27 |
Vibration (Operation) | 2g, according to IEC 60068-2-6 |
UL, USA/Canada
Identification | UL 61010 Listed |
Identification | Class I, Div. 2, Groups A, B, C, D T4 |
Identification | Class I, Zone 2, Group IIC |
Air clearances and creepage distances
Standards/regulations | DIN EN 50178 |
Mounting
Mounting Type | DIN rail mounting |
Assembly instructions | No end clamp |
Mounting Position | vertical, horizontal |
Why Proax for Phoenix Contact 2902914?
Proax is an authorized distributor of Phoenix Contact 2902914 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended