PT 4-EX(I)-24DC-ST - Surge protection plug
PT protective connector with protective circuit for a 4-wire floating Ex-i signal circuit. Nominal voltage: 24 V DC
- Easy testing and documentation with CHECKMASTER 2 with pluggable protective modules
- Maximum ease of maintenance, thanks to the 2-piece design
- Easy selection for all possible demands in MCR applications with a complete product portfolio
- The signal is not influenced during maintenance work, thanks to the impedance-neutral insertion and removal of protective plugs
Technical Specifications
Product properties
Product family | PLUGTRAB PT |
IEC test classification | C1 |
IEC test classification | C2 |
IEC test classification | C3 |
IEC test classification | D1 |
Type | Male |
Number of Positions | 4 |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Insulation characteristics
Overvoltage category | III |
Pollution degree | 2 |
Electrical properties
Nominal voltage UN | 24 V DC |
Connection data
Connection Method | Screw connection (in connection with the base element) |
Screw thread | M3 |
Tightening torque | 0.5 Nm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section rigid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Ex data
Maximum inner capacitance Ci | 1.1 nF |
Max. internal inductance Li | 1 µH |
Max. input current Ii | 500 mA (T4 / ≤ 80°C) |
Max. input current Ii | 500 mA (T5 / ≤ 55 °C) |
Max. input current Ii | 500 mA (T6 / ≤ 40 °C) |
Max. input voltage Ui | 30 V DC |
max. input power Pi | 850.00 mW (T4 / ≤ 80°C) |
max. input power Pi | 700.00 mW (T5 / ≤ 55 °C) |
max. input power Pi | 700.00 mW (T6 / ≤ 40 °C) |
Maximum inner time factor (Ri/Li) | ≤ 10 µs |
Ambient Temperature (Operation) | -40 °C ... 80 °C (T4) |
Ambient Temperature (Operation) | -40 °C ... 55 °C (T5) |
Ambient Temperature (Operation) | -40 °C ... 40 °C (T6) |
Dimensions
Width | 17.7 mm |
Height | 44.8 mm |
Depth | 51.7 mm |
Horizontal pitch | 1 Div. |
Complete module width | 17.7 mm |
Complete module height | 90 mm |
Complete module depth | 65.5 mm |
Material specifications
Color | blue (RAL 5015) |
Flammability rating according to UL 94 | V-0 |
Housing Material | PA 6.6 |
Mechanical data
Open side panel | No |
Protective circuit
Direction of action | Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
Maximum continuous voltage UC | 30 V DC |
Maximum continuous voltage UC | 21 V AC |
Rated current | 500 mA (40 °C) |
Operating effective current IC at UC | ≤ 5 µA |
Residual current IPE | ≤ 4 µA |
Nominal discharge current In (8/20) µs (line-line) | 308 A |
Nominal discharge current In (8/20) µs (line-ground) | 10 kA |
Pulse discharge current Iimp (10/350) µs (line-earth) | 1 kA |
Pulse discharge current Iimp (10/350) µs (line-earth) | 2 kA (in total) |
Total discharge current Itotal (8/20) µs | 20 kA |
Total discharge current Itotal (10/350) µs | 2 kA |
Max. discharge current Imax (8/20) µs maximum (line-line) | 308 A |
Max. discharge current Imax (8/20) µs maximum (line-earth) | 20 kA (in total) |
Nominal pulse current Ian (10/1000) µs (line-line) | 59 A |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 45 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1 kV |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 45 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 1 kV |
Residual voltage at In (conductor-conductor) | ≤ 70 V |
Residual voltage with Ian (10/1000) µs (line-line) | ≤ 65 V |
Voltage protection level Up (line-line) | ≤ 60 V (C1 - 500 V / 250 A) |
Voltage protection level Up (line-line) | ≤ 50 V (C3 - 10 A) |
Voltage protection level Up (line-line) | ≤ 50 V (C3 - 25 A) |
Voltage protection level Up (line-earth) | ≤ 1 kV (C1 - 1 kV / 500 A) |
Voltage protection level Up (line-earth) | ≤ 1 kV (C2 - 2 kV/1 kA) |
Voltage protection level Up (line-earth) | ≤ 1 kV (C2 - 10 kV / 5 kA) |
Voltage protection level Up (line-earth) | ≤ 1 kV (D1 - 1 kA) |
Response time tA (line-line) | ≤ 1 ns |
Response time tA (line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.1 dB (≤ 1 MHz / 50 Ω) |
Input attenuation aE, sym. | typ. 0.1 dB (≤ 500 kHz / 150 Ω) |
Input attenuation aE, sym. | typ. 0.1 dB (≤ 100 kHz / 600 Ω) |
Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 7 MHz |
Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 2.5 MHz |
Cut-off frequency fg (3 dB), sym. in 600 Ω system | typ. 600 kHz |
Resistance per path | 0 Ω |
Surge protection fault message | none |
Max. required back-up fuse | 500 mA (T) |
Impulse durability (line-line) | C1 - 0.5 kV / 250 A |
Impulse durability (line-line) | C3 - 10 A |
Impulse durability (line-line) | C3 - 25 A |
Impulse durability (line-earth) | C1 - 1 kV / 500 A |
Impulse durability (line-earth) | C2 - 2 kV / 1 kA |
Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
Impulse durability (line-earth) | D1 - 1 kA |
Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Ambient conditions
Degree of Protection | IP20 |
Ambient Temperature (Operation) | -40 °C ... 85 °C |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 2000 m (amsl) |
Conformity/Approvals
ATEX | II 1G Ex ia IIC T4...T6 Ga |
ATEX | II 1D Ex ia IIIC T135°C...T85°C Da |
IECEx | Ex ia IIC T4...T6 Ga |
IECEx | Ex ia IIIC T135 °C...T85 °C Da |
Standards and Regulations
Standards/specifications | EN 61643-21 |
Note | A2:2013 |
Standards/specifications | EN 60079-0 |
Note | 2018 |
Standards/specifications | EN 60079-11 |
Note | 2012 |
Standards/specifications | IEC 61643-21 |
Note | A2:2012 |
Standards/specifications | IEC 60079-0 |
Note | 2017 |
Standards/specifications | IEC 60079-11 |
Note | 2011 |
Mounting
Mounting Type | on base element |
Accessories
Why Proax for Phoenix Contact 2839253?
Proax is an authorized distributor of Phoenix Contact 2839253 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended
- 3212125 - Component terminal block, The max. current is determined by the diode. Installed: diode 1N 5408, reverse voltage: 1000 V, maximum continuous current: 1.5 A, with integrated diode 1N5408, nom. voltage: 800 V, nominal current: 1.5 A, connection method: Push-in connection, Rated cross section: 4 mm2, cross section: 0.2 mm2 - 6 mm2, mounting: NS 35/7,5, NS 35/15, color: gray
- 3212112 - Component terminal block, The max. current is determined by the diode. Installed: diode 1N 5408, reverse voltage: 1000 V, maximum continuous current: 1.5 A, with integrated diode 1N5408, nom. voltage: 800 V, nominal current: 1.5 A, connection method: Push-in connection, Rated cross section: 1 mm2, cross section: 0.2 mm2 - 6 mm2, mounting: NS 35/7,5, NS 35/15, color: gray