2798530
SKU
PHX2798530
MPN
UBK 2-500
Weight
0.06 kg
Series UBK
UBK 2-500 - Surge protection device
DIN rail module with coarse surge protection for two signal wires. Self-contacting grounding foot for mounting on NS 32 or NS 35/7.5, housing width: 17.5 mm. Design: 500 V AC
Technical Specifications
Product properties
| Product family | SURGETRAB |
| IEC test classification | C2 |
| IEC test classification | D1 |
| Type | DIN rail module, one-piece |
Insulation characteristics
| Overvoltage category | III |
| Pollution degree | 2 |
Electrical properties
| Nominal voltage UN | 500 V AC |
Connection data
| Connection Method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Dimensions
| Width | 17.5 mm |
| Height | 90 mm |
| Depth | 46 mm (incl. DIN rail 7.5 mm) |
| Horizontal pitch | 1 Div. |
Material specifications
| Color | black (RAL 9005) |
| Flammability rating according to UL 94 | V-2 |
| Housing Material | PA 6.6 |
Protective circuit
| Direction of action | Line-Earth Ground |
| Maximum continuous voltage UC | 500 V AC |
| Rated current | 2 A |
| Operating effective current IC at UC | ≤ 1 µA |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In (8/20) µs (line-line) | 10 kA |
| Nominal discharge current In (8/20) µs (line-ground) | 10 kA |
| Pulse discharge current Iimp (10/350) µs | 2.5 kA |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 2.5 kV |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 2.7 kV (4 kV (1.2/50) µs) |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 1.5 kV |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 1.7 kV (4 kV (1.2/50) µs) |
| Voltage protection level Up (line-line) | 3.5 kV (C2 - 10 kV / 5 kA) |
| Voltage protection level Up (line-earth) | 2.2 kV (C2 - 10 kV / 5 kA) |
| Voltage protection level Up (line-earth) | 2.3 kV (Iimp -2.5 kA) |
| Response time tA (line-line) | ≤ 100 ns |
| Response time tA (line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0 dB (≤ 30 MHz / 50 Ω) |
| Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 60 MHz |
| Capacity (core-core) | typ. 7 pF |
| Surge protection fault message | none |
| Max. required back-up fuse | 2 A (gL) |
| Impulse durability (line-line) | C2 - 10 kV / 5 kA |
| Impulse durability (line-earth) | C2 - 10 kV / 5 kA |
| Impulse durability (line-earth) | D1 - 2.5 kA |
| Alternating current carrying capacity (line-line) | 10 A - 1 s |
| Alternating current carrying capacity (line-earth) | 10 A - 1 s |
Ambient conditions
| Degree of Protection | IP20 |
| Ambient Temperature (Operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 mm (amsl) |
Air clearances and creepage distances
| Standards/regulations | IEC 60664-1 |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 + A1:2008 |
| Standards/specifications | EN 61643-21 |
| Note | 2001 + A1:2009 |
Mounting
| Mounting Type | DIN rail: 35 mm |
Why Proax for Phoenix Contact 2798530?
Proax is an authorized distributor of Phoenix Contact 2798530 and one of Phoenix Contact's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
| Pack Size | 10 |