Technical Specifications
Dimensions
Product Net Weight | 0.8 kg |
Technical
Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 32 A |
Rated Operational Current AC-21A (Ie) | (500 V AC) 32 A |
Rated Operational Current AC-21A (Ie) | (690 V AC) 32 A |
Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 32 A |
Rated Operational Current AC-22A (Ie) | (500 V) 32 A |
Rated Operational Current AC-22A (Ie) | (690 V) 32 A |
Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 32 A |
Rated Operational Current AC-23A (Ie) | (500 V) 32 A |
Rated Operational Current AC-23A (Ie) | (690 V) 32 A |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 12 kV |
Rated Operational Voltage | Main Circuit 690 V AC |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 1 kA |
Rated Conditional Short-Circuit Current (Inc) | (690 V AC) 80 kA |
Power Loss | at Rated Operating Conditions per Pole 2 W |
Fuse Size | 30 A |
Fuse System | Class CC |
Operating mode | Front Operated |
Standards | UL98 |
Standards | IEC 60947-3 |
Mounting Type | Base mounting |
Number of Poles | 4 |
Terminal Type | Lug terminals |
Tightening torque | 1.5 … 2 N·m |
Rated Current (In) | Main Circuit 30 A |
Technical UL/CSA
Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
Maximum Operating Voltage UL/CSA | Main Circuit 250 V DC |
Ampere Rating | 30 A |
Tightening torque | 1.5 … 2 N·m |
Why Proax for ABB OS30FACC22F?
Proax is an authorized distributor of ABB OS30FACC22F and one of ABB's largest distributors in North America. Our highly skilled in-house technical team is ready to assist with any technical needs.
Have a question in mind? to help you get the right product as quickly as possible for your project. We're always here to help!
Short Lead Time
Highly Trained Staff
Live Chat
Technical Support
Local Inventory
60+ Years Experience
Additional Information
Pack Size | 1 |
Recommended